Parameter Page Actuating Value Loss - Theben FCA 2 Manual

Fan coil actuator
Table of Contents

Advertisement

Fan Coil Actuator FCA 2
3.4.15

Parameter page Actuating value loss

This parameter page is only visible if an external controller is used and if this function has been
selected on the General parameter page (parameter: Should the actuating value be monitored).
Table 34
Designation
Monitoring time for
actuating value
Substitute actuating value
in case of actuating value
loss
(emergency program)
Report actuating value
loss
(1 = actuating value loss)
Report cyclically
Updated: Feb-16 (subject to changes)
Values
30 min
60 min
0 %, 10 %, 20 %
30 %, 40 %, 50 %, 60 %,
70 %, 80 %, 90 %, 100 %
only if object value = 1
always cyclically
every 3 min, every 5 min
every 10 min, every 15 min
every 20 min, every 30 min
every 45 min, every 60 min
Meaning
If no actuating value is
received within the
configured time, the substitute
activating value applies.
Actuating value for the
emergency program as long
as no new actuating value is
received by the room
thermostat
Object 20 only transmits at
actuating value loss.
Object 20 always transmits
the status of the actuating
value.
0 = OK
1 = actuating value loss
Cycle time for actuating value
status.
Page
51