6.2 Setting the valve characteristic

The parameters on the heating valve and cooling valve pages allow an exact adjustment to the
available valve type or allow the slight adjustment of the control.
Example for a valve that starts to open from a position of 10 % and is already completely open at
80 %.
Figure 9
Table 59
Description
X
Actuating value from the controller
Y
Resulting valve setting
A
Parameter: Minimum valve setting
B
Parameter: Maximum valve setting
C
Parameter: Open from actuating value
D
Parameter: Maximum valve setting from actuating
value
Updated: Feb-16 (subject to changes)
Value
0 .. 100 %
0 .. 100 %
20 %
80 %
10 %
90 %