Fan Coil Actuator FCA 2
3.4.14

Parameter page Filter monitoring

This parameter page is only visible if this function has been selected on the General parameter
page (parameter: Should a filter change be reported).
Table 33
Designation
Report filter change after
fan operation
(1..127 weeks)
Cyclical transmission of
filter change
Transmit fan duty time*
(in hours)
Send cyclically
* To reset the filter status and the meter reading, see object 31.
Updated: Feb-16 (subject to changes)
Values
manual input: 1..127
(Standard 12)
only at filter change
always cyclically
send never
(reading is possible)
only at change
cyclically and at change
every 3 min, every 5 min
every 10 min, every 15 min
every 20 min, every 30 min
every 45 min, every 60 min
Meaning
interval between 2 filter
changes in weeks.
Object 31 only sends when
filter change is required:
1 = Change filter
Object 31 sends the filter
status cyclically:
0 = Filter OK
1 = Change filter
The fan duty time is counted
to the second internally, but
not transmitted.
The meter reading can be read
from object 30.
The meter reading is
transmitted every time the fan
duty time increases by 1 hour.
The meter reading is
transmitted at regular
intervals and at changes.
Cyclical transmission time for
meter reading.