Parameter Page Operating Mode And Operation (Internal Controller) - Theben FCA 2 Manual

Fan coil actuator
Table of Contents

Advertisement

Fan Coil Actuator FCA 2
3.4.13
Parameter page Operating mode and operation (internal
controller)
Table 32
Designation
Operating mode after reset Frost/heat protection
Transmission of current
operating mode every
Objects for operating
mode selection
Type of presence detector
Updated: Feb-16 (subject to changes)
Values
Temperature reduction at night
Standby
Comfort
do not send cyclically
3 min, 5 min, 10 min
15 min, 20 min, 30 min
60 min
new: operating mode, presence,
window status
old: Comfort, night, frost (not
recommended)
Presence detector
Presence buttons
Meaning
Operating mode after start-up
or reprogramming
Cyclical transmission time of
operating mode (object 24)
FCA 2 can switch the
operating mode depending on
the window and presence
contacts.
Traditional setting without
window and presence status.
The presence sensor activates
the comfort operating mode
Comfort operating mode as
long as the presence object is
set.
If the operating mode object
(Object 3) is called up again
after setting the presence
object, the new operating
mode will be accepted and the
presence object reset.
If the presence object is set
during night/frost mode, it is
reset after the configured
comfort extension finishes
(see below).
The presence object is not
reported back on the bus.
Page
48
89
of

Advertisement