11.6

K3I050 LON/mimic display converter

Item
Component
1
Mounting plate
2
'S3' programming switch: LON bus
address
3
'S4-1' programming switch: Define
LED states of data bus devices
4
'R1' resistor: 'LON bus' terminator
resistor
11.7

K3I090 PSA interface board

Item
Component
1
'S1' programming switch, 'X16/17'
bridges, 'R70'...'R73' resistors:
Determination of interface
2
'X9/10' bridges : For mode of oper-
ation
3
'X/Y11....15' bridges: For
RAM/EPROM equipment
Building Technologies
Fire Safety
Preparation
Remove, fit according to system documentation, see
also description in document 001260
Set in accordance with system documentation
Set to 'ON' if the LEDs of the data bus devices are to
flash (applies to devices with a 5...8 address only)
When using stub line: If K3I050 is not the last device,
remove resistor 'R1', also see description in document
001260
1
S3
S4
R1
Then refit board on mounting plate, connect data bus and LON bus cable, sup-
ply cable as well as peripherals.
Preparation
Set, resolder, depending on application, see descrip-
tion in document 1669
Set, depending on application, see description in
document 1669
Set, depending on application, see description in
document 1669
1
X16/17
R70...R73
X9/10
X/Y11...15
S1
2
Operation and floor repeater display
2
3
4
3
Default ex factory
Fitted
Address 0
To 'OFF'
100 ς used
Default ex factory
'S1' to 'OFF'
'X16/17' 'open'
'R70'.....'R73' used
'Open'
Attached 'Y11', 'X12', 'X13', 'X14',
'Y15'
EPROM: 2x512Kx8 bits
RAM: 2x128Kx8 bits
008726_e_en_--
06.2017
29