Carrier 48LC 04 Controls, Start-Up, Operation And Troubleshooting page 83

Single package rooftop units with comfortlink controls version 1.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

ITEM
EXPANSION
AIR.Q
Air Quality Config.
IA.CF
IAQ Analog Input Config
IA.FN
IAQ Analog Fan Config
II.CF
IAQ Switch Input Config
II.FN
IAQ Switch Fan Config
AQ.MN
Econo Min IAQ Position
OVR.P
IAQ Override Position
OA.CF
OAQ Analog Input Config
OAQ.L
OAQ Lockout Limit
AQD.L
AQ Differential Low
AQD.H
AQ Differential High
DF.ON
Fan On AQ Differential
DF.OF
Fan Off AQ Differential
I.4M
IAQ Sensor Value at 4mA
I.20M
IAQ Sensor Value at 20mA
O.4M
OAQ Sensor Value at 4mA
O.20M
OAQ Sensor Value at 20mA
H.4M
RH Sensor Value at 4mA
H.20M
RH Sensor Value at 20mA
ALM.O
Alarm Relay Config.
A.SPC
SPT/SPRH Sensor Failure
A.SRT
SAT/RAT Sensor Failure
A.OAT
OAT Thermistor Failure
A.CS
Current Sensor Failure
A.CMP
Compressor Failure
A.CKT
Refrig Circuit Failure
A.SSP
SSP Transducer Failure
A.SCT
SCT Thermistor Failure
A.FAN
Indoor Fan Failure
A.FIL
Dirty Filter
A.TST
Thermostat Failure
A.ECO
Economizer Failure
PID
PID Configurations
EC.P
Economizer PID --- kP
EC.I
Economizer PID --- kI
EC.D
Economizer PID --- kD
EC.DT
Economizer PID --- rate
EC.DB
Economizer PID Deadband
LK.P
Linkage Staging PID --- kP
LK.I
Linkage Staging PID --- kI
LK.D
Linkage Staging PID --- kD
LK.DT
Linkage Staging PID --- rate
(GENERIC = CCN only)
POINT 01 Definition
POINT 02 Definition
POINT 03 Definition
POINT 04 Definition
POINT 05 Definition
POINT 06 Definition
POINT 07 Definition
POINT 08 Definition
POINT 09 Definition
POINT 10 Definition
POINT 11 Definition
POINT 12 Definition
POINT 13 Definition
POINT 14 Definition
POINT 15 Definition
POINT 16 Definition
POINT 17 Definition
POINT 18 Definition
POINT 19 Definition
POINT 20 Definition
MODE — CONFIGURATION (cont)
RANGE
UNITS
0=No IAQ
0: no FIOP
1=DCV
1: FIOP
2=Override IAQ
3=Ctrl Min Pos
0=Never
0
1=Occupied
2=Always
0=No IAQ
0
1=DCV N/O
2=DCV N/C
3=Override N/O
4=Override N/C
0=Never
0
1=Occupied
2=Always
0 to 100
%
10
0 to 100
%
100
0=No OAQ
0
1=DCV
2=Lockout OAQ
0 to 5000
600
0 to 5000
100
0 to 5000
700
0 to 5000
600
0 to 5000
200
0 to 5000
0
0 to 5000
2000
0 to 5000
0
0 to 5000
2000
0 to 50
%
0
60 to 100
%
100
No/Yes
Yes
No/Yes
Yes
No/Yes
Yes
No/Yes
No
No/Yes
Yes
No/Yes
Yes
No/Yes
Yes
No/Yes
Yes
No/Yes
Yes
No/Yes
Yes
No/Yes
Yes
No/Yes
Yes
0.00 to 99.90
2.5
0.00 to 99.90
0.12
0.00 to 99.90
1
10.00 to 180.00
secs
15
0 to 25
%
3
0.00 to 99.90
10
0.00 to 99.90
5
0.00 to 99.90
5
10.00 to 180.00
secs
30
83
CCN TABLE/
DEFAULT
Sub--- TABLE
IAQ_CFG
ALM_CFG
PID_CFG
GENERICS
CCN
ENTRY
POINT
IAQANCFG
IAQANFAN
IAQINCFG
IAQINFAN
IAQMINP
IAQOVPOS
OAQANCFG
OAQLOCK
DAQ_LOW
DAQ_HIGH
DAQFNON
DAQFNOFF
IAQ_4MA
IAQ_20MA
OAQ_4MA
OAQ_20MA
RH_4MA
RH_20MA
SPACE_AL
SATRATAL
OAT_AL
CS_AL
COMP_AL
CKT_AL
SSP_AL
SCT_AL
FAN_AL
FILT_AL
TSTAT_AL
ECON_AL
ECONO_P
ECONO_I
ECONO_D
ECONO_DT
ECONBAND
LINK_P
LINK_I
LINK_D
LINK_DT
Point_01
Point_02
Point_03
Point_04
Point_05
Point_06
Point_07
Point_08
Point_09
Point_10
Point_11
Point_12
Point_13
Point_14
Point_15
Point_16
Point_17
Point_18
Point_19
Point_20