Carrier 48LC 04 Controls, Start-Up, Operation And Troubleshooting page 52

Single package rooftop units with comfortlink controls version 1.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

DISPLAY NAME
POINT DESCRIPTION
Input power from MBB
RM.OC
Remote occupancy switch
ENTH or
Outdoor enthalpy switch, or
IAQ.S
Indoor air quality switch
IAQ
Indoor air quality sensor
OAQ or
Outdoor air quality sensor, or
SP .RH
Relative humidity sensor
Sensor Common
Actuator Common
Output power to enthalpy switch
Output power for loop power sensors
Output power to economizer actuator
PE.1
Power exhaust 1 relay
PE.2
Power exhaust 2 relay
EC.CP
Commanded Economizer position
Local Equipment Network (LEN)
Carrier Comfort Network (CCN)
EC.CP &
Economizer actuator position
EC.AP
(digital control)
Table 17 – Economizer Control Board (ECB) Connections
INPUTS
OUTPUTS
COMMUNICATION
SENSOR
TYPE OF I/O
LOCATION
control box
24 VAC
field installed
switch input
economizer, or
switch input
return/space
return/space
0--- 20 mA
field installed
0--- 20 mA
Ground
Ground
24 VAC
24 VDC
24 VAC
0--- 20 mA
communication
communication
MFT communication
52
CONNECTION
PIN NUMBER
J1, 1--- 2
J4, 2
J4, 4
J5, 2
J5, 5
J5, 3
J7, 3
J4, 3
J5, 1
J7, 2
relay
J8, 3
relay
J8, 6
J9, 1
J2, 1--- 3
J3
J7, 1