Carrier 48LC 04 Controls, Start-Up, Operation And Troubleshooting page 50

Single package rooftop units with comfortlink controls version 1.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

DISPLAY
POINT DESCRIPTION
NAME
Input power from TRAN2
IGC.F
IGC Fan Request
FDWN
Fire shutdown switch
G
Thermostat G (Fan)
W2
Thermostat W2 (2nd Stage Heat)
W1
Thermostat W1 (1st Stage Heat)
Y2
Thermostat Y2 (2nd Stage Cool)
Y1
Thermostat Y1 (1st Stage Cool)
FIL.S
Filter status switch
HUM
Humidistat switch input
Not Used
Not Used
SPT
Space temperature (T55/56)
SPTO
Space temperature offset (T56)
OAT
Outdoor air temperature
SAT
Supply air temperature
SCT.A
Saturated condenser temperature, circuit A
Not Used
RAT
Return Air Temperature
FAN.S
Fan status switch
SSP .A
Suction pressure, circuit A
Not Used
Not Used
L.ODF
Low Ambient Outdoor Fan
Not Used
Not Used
IDF.1
Indoor Fan Speed relay 1
IDF.2
Indoor Fan Speed relay 2
IDF.3
Indoor Fan Speed relay 3
ALRM
Alarm relay
COMP .A
Circuit A Compressor
LDR.A
Circuit A Loader
HT.1
Heat Stage 2 relay
HT.2
Heat Stage 1 relay
Local Equipment Network (LEN)
Carrier Comfort Network (CCN)
Network device power
Scrolling Marquee Display (LEN)
Scrolling Marquee Display power
Expansion LEN Bus
Optional ECB power
Table 16 – Main Base Board (MBB) Connections
SENSOR LOCATION
INPUTS
control box
gas section
supply/return/space
space
space
space
space
space
indoor fan section
space
space
space
outdoor coil support
indoor fan housing, or
supply duct
outdoor coil, circuit A
Return
indoor fan section
compressor A suction pipe
OUTPUTS
COMMUNICATION
50
CONNECTION
TYPE OF I/O
PIN NUMBER
24 VAC
J1, 1--- 3
switch input
J6, 4
switch input
J6, 6
switch input
J7, 2
switch input
J7, 4
switch input
J7, 6
switch input
J7, 8
switch input
J7, 10
switch input
J9, 2--- 3
switch input
J9, 5--- 6
0--- 5vdc digital input
J9, 7--- 9
0--- 5vdc digital input
J9, 10--- 12
10k thermistor
J8, 1--- 2
10k thermistor
J8, 2--- 3
10k thermistor
J8, 5--- 6
10k thermistor
J8, 7--- 8
5k thermistor
J8, 9--- 10
5k thermistor
J8, 11--- 12
10k thermistor
J8, 13--- 14
switch input
J8, 15--- 16
0--- 5 VDC pressure
J8, 18--- 20
transducer
0--- 5 VDC pressure
J8, 21--- 23
transducer
0--- 5 VDC
J8, 24--- 26
relay
J10, 3
relay
J10, 6
relay
J10, 9
relay
J10, 11
relay
J10, 13
relay
J10, 16
relay
J10, 19
relay
J10, 21
relay
J10, 23
relay
J10, 25
relay
J10, 27
communication
J5, 1--- 3
communication
J5, 5--- 7
24 VAC
J5, 9--- 10
communication
J4, 1--- 3
24 VAC
J4, 5--- 6
communication
J3, 1--- 3
24 VAC
J2, 1--- 2

Advertisement

Table of Contents
loading

This manual is also suitable for:

48lc 0550lc 0550lc 0648lc 0650lc 04

Table of Contents