APPENDIX — LOCAL DISPLAY AND CCN TABLES
ITEM
EXPANSION
ECON (cont)
Economizer Configuration
MP .50
Econ Min at 50% Fanspeed
MP .75
Econ Min at 75% Fanspeed
MP .MX
Econ Min at Max Fanspeed
MP .LO
Econ Min at Low Fanspeed
MP .VT
Econ Min at Vent Fanspeed
EC.MX
Econo Cool Max Position
M.ANG
Min Actuator Ctrl Angle
EH.LO
Econo Cool Hi Temp Limit
EL.LO
Econo Cool Lo Temp Limit
DF.DB
Diff Dry Bulb Control
UEFC
Unoccupied Free Cooling
FC.TM
Free Cool PreOcc Time
FC.LO
Free Cool Low Temp Limit
PE.EN
Power Exhaust Installed
PE.1
PE Stage1 Econo Position
PE.2
PE Stage2 Econo Position
PE1C
Power Exhaust Stage1
CFM
PE2C
Power Exhaust Stage2
CFM
IDF.C
Indoor Fan Max Speed
CFM
EN.SW
Enthalpy Switch
E.TRV
Economizer Travel Time
E.MXB
Bottom Stage Max Econo
LOG.F
Log Title 24 Faults
EC.MD
T24 Econ Move Detect
EC.ST
T24 Econ Move SAT Test
S.CHG
T24 Econ Move SAT Change
E.SOD
T24 Econ RAT---OAT Diff
E.CHD
T24 Heat/Cool End Delay
ET.MN
T24 Test Mininmum Pos.
ET.MX
T24 Test Maximum Pos.
AIR.Q
Air Quality Config.
IA.CF
IAQ Analog Input Config
IA.FN
IAQ Analog Fan Config
II.CF
IAQ Switch Input Config
II.FN
IAQ Switch Fan Config
AQ.MN
Econo Min IAQ Position
OVR.P
IAQ Override Position
OA.CF
OAQ Analog Input Config
OAQ.L
OAQ Lockout Limit
AQD.L
AQ Differential Low
AQD.H
AQ Differential High
DF.ON
Fan On AQ Differential
DF.OF
Fan Off AQ Differential
I.4M
IAQ Sensor Value at 4mA
I.20M
IAQ Sensor Value at 20mA
O.4M
OAQ Sensor Value at 4mA
O.20M
OAQ Sensor Value at 20mA
H.4M
RH Sensor Value at 4mA
H.20M
RH Sensor Value at 20mA
MODE — CONFIGURATION (cont)
RANGE
UNITS
0 to 100
%
0
0 to 100
%
0
0 to 100
%
30
0 to 100
%
40
0 to 100
%
50
0 to 100
%
100
75 to 90
88
40 to 100
° F
65
--- 30 to 50
° F
0
0=Disable
0=Disable
1=RAT --- 0° F
2=RAT --- 2° F
3=RAT --- 4° F
4=RAT --- 6° F
0=Disabled
2
1=Unoccpied
2=PreOccupancy
1 to 9999
mins
120
--- 30 to 70
° F
50
No/Yes
No
0 to 100
%
40
0 to 100
%
75
0 to 15000
CFM
800
0 to 15000
CFM
0
500 to 15000
CFM
1200 (04)
1600 (05)
2000 (06)
0=No Switch
0: no FIOP
1=Normal Open
1: FIOP
2=Normal Closed
5 to 300
secs
150
0 to 100
%
50
No/Yes
1 to 10
10 to 20
0 to 5
5 to 20
0 to 60
0 to 50
50 to 100
0=No IAQ
0: no FIOP
1=DCV
1: FIOP
2=Override IAQ
3=Ctrl Min Pos
0=Never
0
1=Occupied
2=Always
0=No IAQ
0
1=DCV N/O
2=DCV N/C
3=Override N/O
4=Override N/C
0=Never
0
1=Occupied
2=Always
0 to 100
%
10
0 to 100
%
100
0=No OAQ
0
1=DCV
2=Lockout OAQ
0 to 5000
600
0 to 5000
100
0 to 5000
700
0 to 5000
600
0 to 5000
200
0 to 5000
0
0 to 5000
2000
0 to 5000
0
0 to 5000
2000
0 to 50
%
0
60 to 100
%
100
73
CCN TABLE/
DEFAULT
Sub--- TABLE
ECON_CFG
IAQ_CFG
PAGE
CCN POINT
NO.
MINP_50
22
MINP_75
22
MINP_MAX
22
MINP_LOW
21
MINPVENT
21
ECONOMAX
MINANGLE
21
OATLECLH
22
OATLECLL
22
DIFFBULB
22
UEFC_CFG
22
UEFCTIME
22
OATLUEFC
22
PE_ENABL
23
PE1_POS
23
PE2_POS
23
PE1_CFM
PE2_CFM
IDF_CFM
7
ENTHLCFG
9
ECONOTRV
ECONMAXB
22
T24LOGFL
20
T24ECMDB
20
T24ECSTS
20
T24SATMD
20
T24RATDF
20
T24CHDLY
20
T24TSTMN
20
T24TSTMX
20
IAQANCFG
9
IAQANFAN
24
IAQINCFG
23
IAQINFAN
24
IAQMINP
23
IAQOVPOS
24
OAQANCFG
24
OAQLOCK
22
DAQ_LOW
23
DAQ_HIGH
23
DAQFNON
24
DAQFNOFF
24
IAQ_4MA
23
IAQ_20MA
23
OAQ_4MA
24
OAQ_20MA
24
RH_4MA
17
RH_20MA
17