Carrier 48LC 04 Controls, Start-Up, Operation And Troubleshooting page 71

Single package rooftop units with comfortlink controls version 1.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

APPENDIX — LOCAL DISPLAY AND CCN TABLES
ITEM
EXPANSION
CONFIGURATION
DISP
Display Configuration
METR
Metric Display
LANG
Language Selection
PROT
Password Enable
PSWD
Service Password
TEST
Test Display LEDs
UNIT
Unit Configuration
S.DLY
Startup Delay
U.CTL
Unit Control Type
T.CTL
Thermostat Control Type
FN.SW
Fan Status Switch
FL.SW
Filter Status Switch
FS.SW
Fire Shutdown Switch
RM.SW
Remote Occupancy Switch
SAT.T
SAT Settling Time
RAT.S
RAT Sensor Installed
RH.S
RH Sensor on OAQ Input
RH.SW
Space Humidity Switch
TCS.C
Temp Cmp Strt Cool Factr
TCS.H
Temp Cmp Strt Heat Factr
I.FAN
INDOOR FAN CONFIG
FTYP
Indoor Fan Type
NSPD
Number of Speeds
SMT.F
Smart Fan Control
OC.FN
Fan On When Occupied
IDF.F
Shut Down on IDF Failure
FS.MX
Supply Fan Maximum
Speed
F.SP1
Supply Fan Speed 1
F.SP2
Supply Fan Speed 2
F.SP3
Supply Fan Speed 3
FS.VN
Fan Speed --- Ventilation
S.VFD
SUPPLY FAN VFD CONFIG
N.VLT
VFD1 Nominal Motor Volts
N.AMP
VFD1 Nominal Motor Amps
N.FRQ
VFD1 Nominal Motor Freq
N.RPM
VFD1 Nominal Motor RPM
N.PWR
VFD1 Nominal Motor HPwr
MAX.A
VFD1 Maximum Amps
M.DIR
VFD1 Motor Direction
ACCL
VFD1 Acceleration Time
DECL
VFD1 Deceleration Time
SW.FQ
VFD1 Switching Frequency
MODE — CONFIGURATIONS
RANGE
UNITS
Off/On
Off
0=English
0
1=Spanish
2=French
3=Portuguese
Disable/Enable
Enable
0000 to 9999
1111
Off/On
Off
10 to 600
sec
30
2=Thermostat
2
3=Space Sensor
0=Adaptive
0
1=1 Stage Y1
2=2 Stage Y1
3=Digital
0=No Switch
0
1=Normal Open
2=Normal Closed
0=No Switch
0
1=Normal Open
2=Normal Closed
0=No Switch
0: no FIOP
1=Normal Open
1: FIOP
2=Normal Closed
0=No Switch
0
1=Normal Open
2=Normal Closed
10 to 900
sec
240
No/Yes
Yes
No/Yes
No
0=No Switch
0
1=Normal Open
2=Normal Closed
0 to 60
mins
0
0 to 60
mins
0
1=LEN VFD
1
2=ECM
2: Direct Drive Fan
2 or 3
0
No/Yes
Yes
No (Direct Drive Fan)
No/Yes
Yes
No/Yes
Yes
80 to 100
100
0 to 100
70 (04)
57 (05 & 06)
0 to 100
87 (04)
71 (05)
69 (06)
0 to 100
92 (04)
84 (05 & 06)
0 to 100
%
50
0 to 999
volts
230
460
575
0 to 999
amps
See VFD Motor Parameters
(Table 26 )
10 to 500
60
50 to 30000
1725
0 to 500
See VFD Motor Parameters
(Table 26 )
0 to 999
amps
See VFD Motor Parameters
(Table 26 )
0=FORWARD
0
1=REVERSE
0 to 1800
secs
30
0 to 1800
secs
10
0 to 3
1
CCN TABLE/
DEFAULT
Sub--- TABLE
SERVICE
CONFIGURATION
DISPLAY
(display only, not in table)
UNIT
AFAN_CFG
71
PAGE
CCN POINT
NO.
DISPUNIT
12
LANGUAGE
12
PASS_EBL
12
PASSWORD
12
DISPTEST
12
STARTDLY
12
CTL_TYPE
12
STATTYPE
12
FANSTCFG
12
FILSTCFG
12
SHTDNCFG
12
REMOCCFG
12
SAT_SET
12
RAT_SENS
12
RH_OAQ
12
HUMSTCFG
12
TCSTCOOL
13
TCSTHEAT
13
FAN_TYPE
14
NUM_SPDS
14
SMARTFAN
15
OCC_FAN
15
FATALFAN
15
SPEEDMAX
15
SPEED1
15
SPEED2
15
SPEED3
15
FSPDVENT
15
15
VFD1NVLT
57
VFD1NAMP
57
VFD1NFRQ
57
VFD1NRPM
57
VFD1NPWR
57
VFD1MAXA
57
VFD1MDIR
57
VFD1ACCL
57
VFD1DECL
57
VFD1SWFQ
57