Carrier 48LC 04 Controls, Start-Up, Operation And Troubleshooting page 5

Single package rooftop units with comfortlink controls version 1.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

RUN
SERVICE
TEMPERATURES
STATUS
TEST
Auto View
Service Test
of
Mode
Temperatures
Run Status
(TEST)
(VIEW)
Test Indepen-
Refrigerant
Software
dent
Temperatures
Version
Outputs
Numbers
(INDP)
(VERS)
Test Fans
Control
(FANS)
Modes
Test Cooling
(MODE)
(COOL)
Cooling
Test Heating
Status
(HEAT)
(COOL)
Heating
Status
(HEAT)
Economizer
Status
(ECON)
Component
Run Hours
(HRS)
Component
Starts
(STRT)
NAVIGATE/
EXIT
SCROLL
Fig. 3 - - System Pilott User Interface
Force Hierarchy
There is a hierarchy in CCN with regards to forcing a point.
Programs and devices write a force at different priority levels. A
higher level (smaller number, 1 being the highest) will override a
lower level force. The Scrolling Marquee uses a Control Force at
level 7. The Navigator writes a Service Force which is level 3.
System Pilots and Touch Pilots write Supervisor Forces at level 4.
Network programs can be set to write different level priority forces.
Table 2 – Scrolling Marquee Mode and Menu Display Structure
PRESSURES SETPOINTS
Air
(AIR.T)
(REF.T)
MODIFY/
SELECT
+
PAGE
-
C06322
INPUTS
OUTPUTS CONFIGURATION
Thermostat
Fan
Display
Configuration
Inputs
Outputs
(DISP)
(STAT)
(FANS)
Unit
General
Cool
Configuration
Inputs
Outputs
(UNIT)
(GEN.I)
(COOL)
Indoor Fan
Air Quality
Heat
Configuration
Inputs
Outputs
(I.FAN)
(AIR.Q)
(HEAT)
Cooling
Economiz-
Configuration
er
(COOL)
Outputs
(ECON)
Heating
Configuration
Alarm
(HEAT)
Relay
(ALRM)
Economizer
Configuration
(ECON)
Air Quality
Cfg.
(AIR.Q)
Alarm Relay
Config.
(ALM.O)
Sensor
Calibration
(TRIM)
CCN
Configuration
Generic Status Display Table
The GENERIC points table allows the service/installer the ability
to create a custom table in which up to 20 points from the 5 CCN
categories (Points, Config, Service- -Config, Set Point, and
Maintenance) may be collected and displayed.
In the Service- -Config table section, there is a table named
"GENERICS." This table contains placeholders for up to 20 CCN
point names and allows the user to decide which points are
displayed in the GENERIC points sub- -table under the status
display table. Each one of these placeholders allows the input of an
8- -character ASCII string. Using a CCN interface, enter the Edit
mode for the Service- -Config table "GENERICS" and enter the
CCN name for each point to be displayed in the custom points
table in the order they will be displayed. When done entering point
names, download the table to the rooftop unit control.
IMPORTANT: The computer system software (ComfortVIEWt,
Service Tool, etc.) that is used to interact with CCN controls,
always saves a template of items it considers as static (e.g., limits,
units, forcibility, 24- -character text strings, and point names) after
the software uploads the tables from a control. Thereafter, the
software is only concerned with run time data like value and
hardware/force status. With this in mind, it is important that
anytime a change is made to the Service- -Config table
"GENERICS" (which in turn changes the points contained in the
GENERIC point table), that a complete new upload be performed.
This requires that any previous table database be completely
removed first. Failure to do this will not allow the user to display
the new points that have been created and the CCN interface will
have a different table database than the unit control.
5
TIME
OPERATING
ALARMS
CLOCK
MODES
Time of
Control
Reset All
Day
Modes
Current
(TIME)
(MODE)
Alarms
(R.CURR)
Month,
Cool Mode
Date
Diagnostic
Reset
Day and
(COOL)
Alarm
Year
History
Heat Mode
(DATE)
(R.HIST)
Diagnostic
Daylight
(HEAT)
Currently
Savings
Active
Economizer
Time
Alarms
Diagnostic
(DST)
(CURR)
(ECON)
Local Time
Alarm
Schedule
Demand
HIstory
(SCH.L)
Listing
(HIST)
(DMD.L)
Local
Holiday
Schedules
(HOL.L)