Carrier 48LC 04 Controls, Start-Up, Operation And Troubleshooting page 75

Single package rooftop units with comfortlink controls version 1.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

APPENDIX — LOCAL DISPLAY AND CCN TABLES
ITEM
EXPANSION
SCH.O
CCN Schedule Overrides
SCH.N
Schedule Number
HOL.G
Accept Global Holidays
OV.TL
Override Time Limit
OV.EX
Timed Override Hours
OV.SP
SPT Override Enabled
LDSH
CCN LOADSHED CONFIG.
S.GRP
Loadshed Group Number
R.MXC
Redline Max Cool Stages
S.MXC
Loadshed Max Cool Stages 0 to 3
R.MXH
Redline Max Heat Stages
S.MXH
Loadshed Max Heat
Stages
MODE — CONFIGURATION (cont)
RANGE
UNITS
0 = Always Occupied
0
1---64 = Local Schedule
65---99 = Global Schedule
No/Yes
No
0 to 4
hours
4
0 to 4
hours
---
No/Yes
Yes
0 to 16
0
0 to 3
2
2
0 to 2
2
0 to 2
2
75
CCN TABLE/
DEFAULT
Sub--- TABLE
SCHEDOVR
LOADSHED
PAGE
CCN POINT
NO.
SCHEDNUM
25
HOLIDAYT
25
OTL
25
OVR_EXT
25
TIMEOVER
26
SHED_NUM
26
MAXCREDL
26
MAXCSHED
26
MAXHREDL
26
MAXHSHED
26