Carrier 48LC 04 Controls, Start-Up, Operation And Troubleshooting page 81

Single package rooftop units with comfortlink controls version 1.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

ITEM
EXPANSION
I.FAN
INDOOR FAN CONFIG
FTYP
Indoor Fan Type
NSPD
Number of Speeds
SMT.F
Smart Fan Control
OC.FN
Fan On When Occupied
IDF.F
Shut Down on IDF Failure
FS.MX
Supply Fan Maximum Speed
F.SP1
Supply Fan Speed 1
F.SP2
Supply Fan Speed 2
F.SP3
Supply Fan Speed 3
FS.VN
Fan Speed --- Ventilation
S.VFD
SUPPLY FAN VFD CONFIG
N.VLT
VFD1 Nominal Motor Volts
N.AMP
VFD1 Nominal Motor Amps
N.FRQ
VFD1 Nominal Motor Freq
N.RPM
VFD1 Nominal Motor RPM
N.PWR
VFD1 Nominal Motor HPwr
MAX.A
VFD1 Maximum Amps
M.DIR
VFD1 Motor Direction
ACCL
VFD1 Acceleration Time
DECL
VFD1 Deceleration Time
SW.FQ
VFD1 Switching Frequency
COOL
Cooling Configuration
N.STG
Number of Stages
MRT.C
Compressor Min On Time
MOT.C
Compressor Min Off Time
RST.C
Runtime to Reset Strikes
C.DEC
Cool Stage Decrease Time
C.INC
Cool Stage Increase Time
FOD.C
Fan--- off Delay, Mech Cool
FTT
Fan Transition Time
ALM.N
Alert Each Strike
CA.LO
Circuit A Lockout Temp
LA.SP
Low Ambient ODF
Setpoint
D.CMP
Diagnose Comp Safety
MX.SA
Max Suction Change CirA
CS.A1
Current Sensing A1
DHUM
Dehum Control Type
SAT
Supply Air Temperature
SA.PD
SAT Cool Demand (+)
Level
SA.ND
SAT Cool Demand (--- )
Level
SAT.U
Minimum SAT Upper Level
SAT.L
Minimum SAT Lower Level
SPT
Space Temperature
CL.PD
SPT Cool Demand (+)
Level
CL.ND
SPT Cool Demand (--- )
Level
C.LAG
Cool Thermal Lag Factor
SST
Low Suction Control
SST.O
Suction OK Temperature
SST.1
Low Suction --- Level 1
SST.2
Low Suction --- Level 2
SST.3
Low Suction --- Level 3
CK.DL
Delay On Low SST Check
FLSU
Fan Low Suction Temp
MODE — CONFIGURATION (cont)
RANGE
UNITS
1=LEN VFD
1
2=ECM
2: Direct Drive Fan
2 or 3
0
No/Yes
Yes
No (Direct Drive Fan)
No/Yes
Yes
No/Yes
Yes
80 to 100
100
0 to 100
70 (04)
57 (05 & 06)
0 to 100
87 (04)
71 (05)
69 (06)
0 to 100
92 (04)
84 (05 & 06)
0 to 100
%
50
0 to 999
volts
230
460
575
0 to 999
amps
See VFD Motor Parameters
(Table 26 )
10 to 500
60
50 to 30000
1725
0 to 500
See VFD Motor Parameters
(Table 26 )
0 to 999
amps
See VFD Motor Parameters
(Table 26 )
0=FORWARD
0
1=REVERSE
0 to 1800
secs
30
0 to 1800
secs
10
0 to 3
1
1 to 2
2
120 to 999
sec
180
300 to 999
sec
300
120 to 999
sec
300
120 to 999
sec
300
120 to 999
sec
450
0 to 600
sec
75
60 to 600
sec
480
No/Yes
Yes
0 to 100F
° F
0
0 to 80
° F
40
No/Yes
Yes
0 to 100
PSIG
4
Disable/Enable
Disable
0=No Control
0
1=Max Dehum
2=Max Comfort
0.5 to 10
^F
1
--- 10 to --- 0.5
^F
--- 1
35.0 to 65.0
° F
52
35.0 to 65.0
° F
40
0.5 to 5
^F
1
--- 5 to --- 0.5
^F
--- 1
0 to 5
1
10 to 50
° F
18
10 to 50
° F
20
5 to 50
° F
15
0 to 50
° F
10
0 to 300
sec
0
28 to 50
° F
32
81
CCN TABLE/
DEFAULT
Sub--- TABLE
AFAN_CFG
COOL_CFG
CCN
ENTRY
POINT
FAN_TYPE
NUM_SPDS
SMARTFAN
OCC_FAN
FATALFAN
SPEEDMAX
SPEED1
SPEED2
SPEED3
FSPDVENT
VFD1NVLT
VFD1NAMP
VFD1NFRQ
VFD1NRPM
VFD1NPWR
VFD1MAXA
VFD1MDIR
VFD1ACCL
VFD1DECL
VFD1SWFQ
NUM_STAG
MIN_ON
MIN_OFF
MIN_ON_S
STAGEDEC
STAGEINC
COOL_FOD
FANTRANT
ALM_NOW
OATLCMPA
LAODF_SP
DIAGCOMP
MAXDSSPA
A1_SENSE
DEHUMCTL
SAT_POS
SAT_NEG
SATMIN_H
SATMIN_L
DEM_POS
DEM_NEG
COOL_LAG
SSTOK
SSTLEV1
SSTLEV2
SSTLEV3
SSTCKDLY
FANLOSUC

Advertisement

Table of Contents
loading

This manual is also suitable for:

48lc 0550lc 0550lc 0648lc 0650lc 04

Table of Contents