Carrier 48LC 04 Controls, Start-Up, Operation And Troubleshooting page 69

Single package rooftop units with comfortlink controls version 1.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

APPENDIX — LOCAL DISPLAY AND CCN TABLES
ITEM
SERVICE TEST
TEST
Field Service Test Mode
INDP
Test Independent Outputs
ECON
Economizer Position Test
E.CAL
Calibrate Economizer
PE.1
Power Exhaust 1 Test
PE.2
Power Exhaust 2 Test
ALRM
Alarm Relay Test
FANS
Test Fans
F.SPD
Indoor Fan Speed Test
F.MOD
IDF Fan Mode
IDF1
Indoor Fan Test 1
IDF2
Indoor Fan Test 2
IDF3
Indoor Fan Test 3
COOL
Test Cooling
CMP .A
Cool A Test
LDR_A
Cir A Loader Test
F.SPD
Reduced Cool Fan Speed
L.ODF
Low Amb ODF Test
HEAT
Test Heating
HT.1
Heat Stage 1 Test
HT.2
Heat Stage 2 Test
F.SPD
Reduced Heat Fan Speed
ITEM
EXPANSION
TEMPERATURES
AIR.T
Air Temperatures
SAT
Supply Air Temperature
OAT
Outdoor Air Temperature
SPT
Space Temperature
SPTO
Space Temperature Offset
RAT
Return Air Temperature
REF.T
Refrigerant Temperatures
SST.A
Sat. Suction Temp A
SCT.A
Sat. Condenser Temp A
PRESSURES
SSP .A
Suction Pressure A
SCP .A
Condenser Pressure A
ITEM
SETPOINTS
OCSP
Occupied Cool Setpoint
UCSP
Unoccupied Cool Setpoint
OHSP
Occupied Heat Setpoint
UHSP
Unoccupied Heat Setpoint
GAP
Heat--- Cool Setpoint Gap
STO.R
SPT Offset Range (+/--- )
RH.SP
Space RH Occupied SP
RH.UN
Space RH Unoccupied SP
RH.DB
Space RH Deadband
RH.HB
Dehum Heat SP Deadband
LCSP
Low Cool SAT Setpoint
HCSP
High Cool SAT Setpoint
CCSP
Comfort SAT Setpoint
MODE — SERVICE TEST
EXPANSION
RANGE
Off/On
0 to 100
Off/On
Off/On
Off/On
Off/On
0 to 100
0 to 7
Off/On
Off/On
Off/On
Off/On
Off/On
0 to 100
Off/On
Off/On
Off/On
0 to 100
MODE — TEMPERATURES & PRESSURES
RANGE
xxx.x
° F
xxx.x
° F
xxx.x
° F
xxx.x
^F
xxx.x
° F
xxx.x
° F
xxx.x
° F
xxx.x
° F
xxx.x
psig
xxx.x
psig
MODE — SETPOINTS
EXPANSION
RANGE
55 to 80
65 to 95
55 to 80
40 to 80
2 to 10
0 to 5
30 to 100
30 to 100
2 to 20
--- 5 to 5
55 to 75
50 to 70
40 to 70
UNITS
CCN TABLE/Sub--- TABLE
(TEST = display only)
TESTINDP
%
TESTFANS
%
TESTCOOL
%
TESTHEAT
%
CCN TABLE/
UNITS
CCN POINT
Sub--- TABLE
STATUS DISPLAY
UINPUT
SAT_DISP
OA_TEMP
SPACE_T
SPTO
RETURN_T
SST_A
SCT_A
SSP_A
SCP_A
UNITS
DEFAULT
SETPOINT CONFIGURATION
° F
78
SET_PNT
° F
85
° F
68
° F
60
^F
5
^F
5
%
50
%
80
%
8
^F
2
° F
60
° F
55
° F
55
69
CCN POINT
S_ECONO
S_ECOCAL
S_PE_1
S_PE_2
S_ALMOUT
S_FANSPD
S_IDFMOD
S_IDF_1
S_IDF_2
S_IDF_3
S_COMP_A
S_LOADER
S_FSPDCL
S_LAODF
S_HEAT_1
S_HEAT_2
S_FSPDHT
CCN WRITE
DISPLAY WRITE
STATUS
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
CCN TABLE/Sub--- TABLE
CCN POINT
OCSP
UCSP
OHSP
UHSP
HCSP_GAP
SPTO_RNG
SPRH_SP
SPRH_USP
SPRH_DB
RH_HSPDB
LCSASP
HCSASP
CFSASP
STATUS