Selecting the Stopping Method

Stopping Method Selection (n04)

Select the stopping method suitable for the application.
Setting
0
1
Deceleration to a Stop
Example when acceleration/deceleration time 1 is selected
Acceleration
Output
Time 1
Frequency
(n16)
FWD (REV)
RUN
Command
* Changing the Frequency Reference while Running
Upon termination of a FWD (REV) RUN command, the motor deceler-
ates at the deceleration rate determined by the time set in Deceleration
Time 1 (n17) and DC injection braking is applied immediately before
stopping. DC injection braking is also applied when the motor deceler-
ates because the frequency reference is set lower than the Min. Output
Frequency (n14) when the FWD (REV) RUN command is ON. If the
deceleration time is short or the load inertia is large, an overvoltage
(OV) fault may occur at deceleration. In this case, increase the decelera-
tion time.
Description
Deceleration to a stop
Coast to a stop
Deceleration
Time 1
Deceleration
(n17)
Time 1 (n17)
Time
6. Programming Features
Min. OutputFrequency
(Frequency at
DC Injection Braking
Startup) n14
(Factory Setting: 1.5 Hz)
DC Injection Braking
Time at Stop (n53)
(Factory Setting: 0.5 s)
67