YASKAWA VS mini J7 Series Instruction Manual page 47

Compact general-purpose inverter
Hide thumbs Also See for VS mini J7 Series:
Table of Contents

Advertisement

Typical Setting of the V/f Pattern
Set the V/f pattern according to the application as described below. For
400-V Class Inverters, the voltage values (n10, n13, and n15) should be
doubled. When running at a frequency exceeding 50/60 Hz, change the
Maximum Output Frequency (n09).
Note: Always set the maximum output frequency according to the motor char-
acteristics.
1. For General-purpose Applications
Motor Specification: 60 Hz
(Factory setting)
V
200
12
1.5
2. For Fans/Pumps
Motor Specification: 60 Hz
V
200
50
10
1.5
3. For Applications Requiring High Starting Torque
Motor Specification: 60 Hz
V
200
24
18
1.5
3
Increasing the voltage of the V/f pattern increases motor torque, but
an excessive increase may cause motor overexcitation, motor over-
heating, or vibration.
46
Constant
n09
n10
n11
n12
n13
n14
n15
60 f
Constant
n09
n10
n11
n12
n13
n14
n15
30
60
f
Constant
n09
n10
n11
n12
n13
n14
n15
60
f
Motor Specification: 50 Hz
V
Setting
200
60.0
200.0
60.0
1.5
12
1.5
12
12
1.3
Motor Specification: 50 Hz
V
Setting
200
60.0
200.0
60.0
30.0
50
50
1.5
10
10
Motor Specification: 50 Hz
V
Setting
200
60.0
200.0
60.0
3.0
24
24
18
1.5
18
1.3
Constant
n09
n10
n11
n12
n13
n14
n15
50 f
Constant Setting
n09
n10
n11
n12
n13
n14
n15
1.3
25
50
f
Constant Setting
n09
n10
n11
n12
n13
n14
n15
2.5
50
f
Setting
50.0
200.0
50.0
1.3
12
1.3
12
50.0
200.0
50.0
25.0
50
1.3
10
50.0
200.0
50.0
2.5
24
1.3
18

Hide quick links: