• Selecting Stopping Method

Selecting stopping method (n04)
Selects the stopping method when the run command is removed.
Setting
Description
0
Deceleration to stop
1
Coast to stop
• Deceleration to stop (n04 =0)
* When frequency reference is changed during running.
Upon removal of the FWD (REV) run command, the motor decelerates at the decel rate
determined by the time set to decel time 1 (n17) and DC injection braking is applied
immediately before stop. DC injection braking is also applied when the motor
decelerates by setting the frequency reference lower than minimum output frequency
while the(n14) with FWD (REV) run command remains ON.
If the decel time is short or the load inertia is large, an over voltage (OV) fault may
occur during deceleration. In this case, increase the decel time.