Maintenance

8.3 Replacing the connectivity module

Function
Offboarding
Reset user credentials Resets the user name and the connectivity module password to the factory settings.
Factory settings
8.3
Replacing the connectivity module
Connectivity module as replacement part
You can order the connectivity module as replacement part (Page 43). The battery is not
connected and it has no motor parameters. You must configure the device from new.
Procedure
1. At the front cover release the two central fastening screws.
Do not completely turn the screws from the cover so that the screws are not lost.
2. Remove the front cover.
3. Withdraw the battery connector.
4. Release the 4 fastening screws that fix the connectivity module to the holder.
5. Remove the connectivity module from the mounting bracket.
6. Place the new connectivity module in the mounting bracket.
7. Retighten the 4 fastening screws.
8. Insert the battery connector.
9. Reattach the front cover. Ensure that the cover fits precisely.
10.Tighten the 2 central fastening screws at the front cover by hand.
11.Configure the connectivity module from new.
38
Description
Deletes all onboarding information in the connectivity module. After offboarding, it is no longer
possible to transfer measurement data to SIDRIVE IQ. To transfer data, start a new onboarding
process.
Offboarding is a precondition for a new onboarding process to SIDRIVE IQ.
Resets the connectivity module to the factory settings. The user data are reset to the factory settings.
All of the saved motor data and onboard information are lost.