5.6.3
Configuration of the
electric actuator
Î Connect the USB-RS485 adapter R3 to
the electric actuator and computer.
Î Perform configuration as required in
TROVIS-VIEW.

5.7 Quick check

To test the electric actuator's ability to func-
tion, the following quick checks can be per-
formed:
Î Apply the maximum and minimum con-
trol signals (e.g. over the manual level in
TROVIS-VIEW).
Î Check the end positions of the valve.
Î Check the travel indication on the scale.
Î Check the display reading.
Î Check bus connection, if applicable.
TROVIS 5725-8
Î Disconnect the supply voltage and check
whether the valve moves to the fail-safe
position.