Decommissioning And Disassembly; Decommissioning; Removing The Actuator From The Valve; Force-Locking Attachment - Samson TROVIS 5724-8 Mounting And Operating Instructions

Electric actuators with process controller for heating and cooling applications
Table of Contents

Advertisement

9 Decommissioning and disas-
sembly
DANGER
DANGER
!
!
Risk of electric shock.
− Before performing any work on the device
and before opening the device, disconnect
the supply voltage and protect it against
unintentional reconnection.
− Only use power interruption devices that
are protected against unintentional recon-
nection of the supply voltage.
DANGER
DANGER
!
!
Risk of bursting in control valve components
due to incorrect opening.
− Before starting any work on the control
valve, depressurize all plant sections con-
cerned and the valve.
− Drain the process medium from all the
plant sections concerned as well as the
valve.
− Wear recommended personal protective
equipment. See associated valve documen-
tation.

9.1 Decommissioning

To decommission the electric actuator for
maintenance work or disassembly, proceed
as follows:
1. Close the shut-off valves upstream and
downstream of the control valve to stop
the process medium from flowing
through the valve.
EB 5724-8 EN

Decommissioning and disassembly

2. Completely drain the pipelines and
valve.
3. Disconnect and lock the supply voltage.
4. If necessary, allow the pipeline and valve
components to cool down.
5. Remove the valve from the pipeline. See
associated valve documentation.
9.2 Removing the actuator
from the valve
9.2.1
Force-locking attach-
ment
1. Undo the coupling nut (4) and remove
the actuator from the valve connection.
9.2.2

Form-fit attachment

1. Pull plug stem until it reaches the actua-
tor stem or extend actuator stem using
the handwheel.
2. Unscrew the stem connector clamps (16)
between the actuator stem and the plug
stem.
3. Undo the nut (17) and remove the rod-
type yoke (15) together with the actuator
from the valve.
4. Undo the coupling nut (4) and remove
the actuator from the rod-type yoke (15).
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Trovis 5725-8

Table of Contents