Start closed-loop operation
Start closed-loop operation.
Readings:
'on' during start-up time. Afterwards,
the value resulting from the A3.1 con-
figuration item.
Note
The duration of start-up time is set in the
A1.T.ON parameter in TROVIS-VIEW.
During the start-up time, the actuator stem
moves to the defined positioning value A1.
YP.ON (see section 10.2).
End closed-loop operation
End closed-loop operation.
Readings:
'-' blinks in alternating sequence on
the left and right while the lag time
is running
'--' while closed-loop operation is in-
terrupted
Note
The duration of lag time is set in the
A1.T.OFF parameter in TROVIS-VIEW.
During the lag time, the actuator stem moves
to the defined positioning value A1.YP.OFF
(see section 10.2).
EB 5724-8 EN
6.3 Increasing/decreasing set
point
Necessary configuration (see section 10.2)
− A1.1 = 2 and A1.5 = 0 or
− A1.1 = 2 and A1.5 = 1 or
− A1.1 = 2 and A1.5 = 2 or
− A1.1 = 2 and A1.5 = 3 or
− A1.1 = 2 and A1.5 = 4
Note
The setting A1.5 = 1, 2, 3 or 4 allows the
operating function to be controlled by the
digital input and over the [I]/[O] keys (auto-
matic level, 'Au' reading in the display).
Changing to the function level ('F u' reading)
is performed only using the [I]/[O] keys.
Press the [I] or [O] key once to change from
the automatic to the function level. To change
from the function to the automatic level, keep
the [O] key pressed for three seconds.
Control to set point
Control to set point.
Increase/decrease set point
Start set point increase/decrease.
Note
The set point increase/decrease is set in the
C1.SP.DIF parameter in TROVIS-VIEW. See
section 10.2.