Refrigerant Charging; Saturation Curve - York CodePak YK L1 L1 G4 Operation Manual

Centrifugal liquid chillers styles a & b with microcomputer control center part 371-01200-004 for electro-mechanical starter & solid state starter
Table of Contents

Advertisement

FIG. 22 – SATURATION CURVE
medium for carrying this residual moisture to the
vacuum pump, nitrogen should be introduced into the
system to bring it to atmospheric pressure and the
indicator temperature will return to approximately am-
To avoid the possibility if freezing liquid within the cooler
tubes when charging an evacuated system, only re-
frigerant vapor from the top of the drum or cylinder
must be admitted to the system pressure until the sys-
tem pressure is raised above the point corresponding
to the freezing point of the cooler liquid. For water, the
pressure corresponding to the freezing point is 57.5
PSIG (396.5 kPa) for R-22 or 8.54 PSIG (58.9 kPa) for
R-134a (at sea level).
While charging, every precaution must be taken to pre-
vent moisture laden air from entering the system. Make
up a suitable charging connection from new copper
tubing to fit between the system charging valve and
the fitting on the charging drum. This connection should
be as short as possible but long enough to permit suf-
ficient flexibility for changing drums. The charging con-
nection should be purged each time a full container of
refrigerant is connected and changing containers should
be done as quickly as possible to minimize the loss of
refrigerant.
Refrigerant may be furnished in drums containing ei-
ther 30, 50, 125 or 1750 lbs. (13.6, 22.7, 56.7 or 793.8
kg) of refrigerant. These drums are not returnable and
they should be stored for future use if it should ever
become necessary to remove refrigeration from the
system.
YORK INTERNATIONAL
bient temperature. Close off the system again, and start
the second evacuation.
The relatively small amount of moisture left will be car-
ried out through the vacuum pump and the tempera-
ture or pressure shown by the indicator should drop
uniformly until it reaches a temperature of 35°F (1.7°C)
or a pressure of 5 mm Hg.
When the vacuum indicator registers this temperature
or pressure, it is a positive sign that the system is
evacuated and dehydrated to the recommended limit.
If this level cannot be reached, it is evident that there
is a leak somewhere in the system. Any leaks must be
corrected before the indicator can be pulled down to
LD01084
35°F (1.7°C) or 5 mm Hg. in the primary evacuation.
During the primary pulldown, keep a careful watch on
the wet bulb indicator temperature, and do not let it fall
below 35°F (1.7°C). If the temperature is allowed to fall
to 32°F (0°C), the water in the test tube will freeze,
and the result will be a faulty temperature reading.

REFRIGERANT CHARGING

TABLE 4 – REFRIGERANT CHARGE
Cooler
SHELL CODES
R-22 R-134a R-22 R-134a
Con-
(Lbs.)
denser
L
L
1350
L
M
1475
M
L
1525
M
M
1625
M
N
1850
N
M
1900
N
N
2125
N
P
2125
P
N
2175
P
P
2175
P
Q
2500
Q
P
2550
Q
Q
2925
Q
R
3250
R
Q
3500
R
R
3850
FORM 160.49-O1
(Kg.)
1340
612
608
1465
669
665
1525
691
691
1625
737
737
1840
839
835
1905
861
864
2125
964
964
2125
964
964
2185
987
991
2185
987
991
2530
1134
1147
2560
1157
1161
2905
1327
1318
3250
1474
1465
3500
1588
1588
3840
1746
1742
49

Advertisement

Table of Contents
loading

This manual is also suitable for:

Codepak yk s2 s2 j4Codepak yk se sc j2

Table of Contents