SECTION 6 – MAINTENANCE

REFRIGERANT CHARGING

To avoid the possibility of freezing liquid within the
evaporator tubes when charging an evacuated system,
only refrigerant vapor from the top of the cylinder
must be admitted to the system pressure until the sys-
tem pressure is raised above the point corresponding to
the freezing point of the evaporator liquid. For water,
the pressure corresponding to the freezing point is 8.54
PSIG (58.9 kPa) for R-134a (at sea level).

TABLE 3 - REFRIGERANT CHARGE

R-134A
EVAPORATOR
CODE
BB
BC
BD
B2
B3
B4
CB
CC
CD
C2
C3
C4
DB
DC
DD
D2
D3
D4
EB
11162
EC
10496
ED
E2
11447
E3
10925
E4
10375
42
LBS.
KG'S
7132
3235
6554
2973
6000
2722
7144
3241
6680
3030
6275
2846
8871
4024
8446
3831
8050
3651
9622
4365
8949
4059
8450
3833
8999
4082
8453
3834
7925
3595
9327
4231
8900
4037
8450
3833
5063
4761
9850
4468
5192
4955
4706
While charging, every precaution must be taken to pre-
vent moisture laden air from entering the system.
The charging connection should be purged each time
a full cylinder of refrigerant is connected or changed.
Refrigerant may be furnished in cylinders contain-
ing either 30, 50, 125 or 1750 lbs. (207, 345, 862, or
12,066 kg) of refrigerant.
R-134A
EVAPORATOR
CODE
FB
11022
FC
10378
FD
F2
11411
F3
10857
F4
10250
GB
13485
GC
12698
GD
11900
G2
13970
G3
13292
G4
12550
HB
12292
HC
11674
HD
10875
H2
12711
H3
12089
H4
11400
KB
15057
KC
14301
KD
13325
K2
15553
K3
14793
K4
13950
FORM 160.69-O2
ISSUE DATE: 9/30/2020
LBS.
KG'S
5000
4707
9725
4411
5176
4925
4649
6117
5760
5398
6337
6029
5693
5576
5295
4933
5766
5484
5171
6830
6487
6044
7055
6710
6328