Troubleshooting; Section 6 - Trouble Shooting - York CodePak YK L1 L1 G4 Operation Manual

Centrifugal liquid chillers styles a & b with microcomputer control center part 371-01200-004 for electro-mechanical starter & solid state starter
Table of Contents

Advertisement

TABLE 1 – CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE MICROCOMPUTER CONTROL, CENTER DISPLAY
SHUTDOWN CAUSE
CONTROL CENTER DISPLAY
DAY OF
TIME OF
CAUSE OF
WEEK
DAY
SHUTDOWN
MON.
10:00 AM
Low Water
Temp.
MON.
10:00 AM
Flow Switch
MON.
10:00 AM
System
Cycling
MON.
10:00 AM
Multi-Unit
MON.
10:00 AM
Internal
Clock
MON.
10:00 AM
AC under-
voltage
MON.
10:00 AM
Power Fault
Remote Stop
MON.
Anti-Recycle,
20 Min. Left
MON.
10:00 AM
Low Evap.
Pressure
(Continued on Page 42)
GOVERNING CONTROL FUNCTION
OPERATING
METHOD OF
DESCRIPTION
RESTART
ON
RISE
Autostart
Low Water
Chilled
(LWT)
water
setpoint
Autostart
Flow Switch
Autostart
A remote com-
mand (computer
relay contact or
manual switch)
Autostart
(Optional) Lead-
Lag Sequence
Control
Autostart
Internal Clock
Autostart
<15% FLA for
25 continuous
seconds
Autostart
CM-2 Current
Module or
Solid State
Starter
Energy manage-
ment System
Anti-Recycle
timer
Low Evap.
54..3 PSIG 54.4 PSIG
Pressure
(374.4 kPa)
Transducer
(R-22)
(LEP)
25 PSIG
(172.4 kPa)
(R-134a)
PROGRAMMED
SETPOINTS
POINT
BY OPERATOR
ON
FALL
4°F (2.2°C)
4°F (2.2°C) be-
below
low chilled water
chiller
setpoint (If set
water
to 40°F (4.4°C)
setpoint
would be 36°F
(2.2°C)) (36°F
(2.2°C) mini-
mum)
Daily Schedule
Programmed to
Shutdown Unit
Will not start
until 30 Min.
timer is timed
(375 kPa)
(R-22)
25.1 PSIG
(173 kPa)
(R-134a)
START-UP OF
PROBABLE CAUSE
SYSTEM AFTER
AND SERVICE
SHUTDOWN
REQUIRED
Automatic Restart
System load is less
when water reaches
than minimum capacity
setpoint; if system is
running and setpoint
is increased 4°F, sys-
tem will continue to
run, as LWT cutout
shifts to a fixed 36°F
for 10 minutes.
Automatic Restart
Lack of water flow.
when water flow is
Check operation of
Restored to close
chilled water pump
flow switch.
Automatic Restart
Contact-connected to
upon remote
the Remote/Local
command.
cycling input of the
Digital input board
Automatic Restart
Contact-connected to
upon remote
the Multi-Unit cycling
command.
input of the Digital
input board
Will automatically
Pressing Compressor
restart when pro-
Start Switch over-
grammed schedule
rides the program
permits
Cycling shutdown occurs
when motor current is
>15% FLA for 25 seconds
during chiller operation
Will start automatic-
Motor Controller contacts
tically following
opening and closing in
coastdown
less than 3 seconds due to
a power fault condition
Start up by start
Remote Stop Contact
signal from remote
Closure
start switch
Will restart when
Min. Time between
time left = 00 Min.
successive compres-
sor starts is 30 min.
To restart press com-
See OPERATION
pressor switch from
ANALYSIS TABLE 2
STOP/RESET to
Symptom 2.
START position.