Deliming Cycle Status (Led Indicators) - Vulcan-Hart C24EA Series Service Manual

Electric convection steamers
Hide thumbs Also See for C24EA Series:
Table of Contents

Advertisement

C24EA SERIES ELECTRIC CONVECTION STEAMERS - CONTROL BOARD
Drain Cycle Ends
LED's 1, 9, 12 and 13 remain lit.
All other LED's are off.
Steamer is off.

DELIMING CYCLE STATUS (LED INDICATORS)

Conditions same as listed under STARTING CONDITIONS.
Delime time delay relay 2 (TDR) and drain time delay relay (TDR) jumpers on the control board are set at their
default times as shown on the schematic.
Delime valve closed.
Delime solution added to steam generator.
NOTE: Heat exchanger elements are not energized during delime cycle.
Delime Switch On
Delime switch pressed to DELIME position (momentary on - hold 2 sec).
Power light (3LT) (amber) on.
Delime light (4LT) (red) on.
HL Led is on. Water level control powered.
Water fills steam generator at fast fill rate.
STATUS
LED
ON
OFF
1
X
12
X
13
X
14
X
F35453 Rev. A (0119)
COMPONENT
Same as starting conditions
Same as starting conditions
Power to delime 1 (TDR)
Delime Relay (K4) energized.
Relay timed out, no output to delime circuit. LED
remains lit as in Turning Steamer Off.
Delime 2 (TDR) powered thru K4-6/4 closed contacts
(N.O.). 120VAC output from delime 2 (TDR) load
terminal for 60 minutes.
Power to heating circuit, power light (3LT) and WLC
thru K4-5/3 closed contacts (N.O.).
Page 44 of 75
DESCRIPTION