Installer-Supplied Components; Not Available For Fwd30 And Fwd45 - Trane Sintesis Advantage CGAF Series Installation Operation & Maintenance

Air-cooled scroll chillers and heat pumps 260-670 kw
Hide thumbs Also See for Sintesis Advantage CGAF Series:
Table of Contents

Advertisement

Installer-Supplied Components

Customer wiring interface connections are shown in
the electrical schematics and connection diagrams that
are shipped with the unit. The installer must provide the
following components if not ordered with the unit:
FWD
• Power supply wiring (in conduit) for all field-
Power supply
wired connections
Capacities
Cooling capacity on water (1)
• All control (interconnecting) wiring (in conduit)
Heating capacity on water (2)
for field supplied devices
Fan motor
Fan power input (3)
• Fused-disconnect switches
Current amps (3)
Start-up amps
Air flow
Power Supply Wiring
minimum
nominal
All power supply wiring must be sized and selected
maximum
accordingly by the project engineer in accordance
Main coil
Water entering/leaving connections
with standard IEC 60364. All wiring must comply with
local codes. The installing (or electrical) contractor
Electric heater (accessory for blower only)
must provide and install the system interconnecting
Electric power supply
wiring, as well as-the power supply wiring. It must be
Heating capacity
Hot water coil (accessory for blower only)
properly sized and equipped with the appropriate fuse-
Heating capacity (4)
disconnect switches. The type and installation location(s)
G2 filter (filter box accessory)
of the fused-disconnect switches must comply with all
Quantity
applicable codes.
Dimensions ( LxWxth)
G4 filter (filter box accessory)
Quantity
Cut holes into the sides of the control panel for the
Dimensions ( LxWxth)
appropriately-sized power wiring conduits. The wiring
Condensate pump (accessory)
Water flow - lift height
is passed through these conduits and connected to the

Not available for FWD30 and FWD45

terminal blocks.
Sound level (L/M/H speed)
Sound pressure level (5)
To provide proper phasing of 3 phase input, make
Sound power level (5)
Unit dimensions
connections as shown in field wiring diagrams and as
Width x Depth
stated on the yellow WARNING label in the starter panel.
Height
Proper equipment grounds must be provided to each
Shipped unit dimensions
Width x Depth
ground connection in the panel.
Height
Weight
CAUTION! Customer wiring interface connections are
Colour
Recommended fuse size
shown in the electrical schematics and connection
Unit alone (aM/gI)
diagrams that are shipped with the unit. The installer
Unit with electric heater (gI)
must provide the following components if not ordered
with the unit.
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
WARNING! To prevent injury or death, disconnect all
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
electrical power sources before completing wiring
connections to the unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
CAUTION! The use of copper mono-conductors is the
*absolute service pressure: min 1 bar/max 11 bars
preferred solution to avoid corrosion and overheating
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
at terminal connections.
*absolute service pressure: min 1 bar/max 11 bars
Control Power Supply
Chiller is provided with control power transformer, it
is not necessary to provide additional control power
voltage to the unit.
Heater Power Supply
The evaporator shell is insulated from ambient air and
protected from freezing for temperature down to -20°C
by two thermostatically-controlled immersion heaters
combined with evaporator pumps activation through
Tracer UC800. Whenever the ambient temperature
drops below 0°C the thermostat energizes the heaters
and the Tracer UC800 activates the pumps. If ambient
4
42
Technical Data
temperatures below -20°C are expected, contact your
Trane local office.
CAUTION! The control panel main processor does
not check for loss of power to the heat tape nor does
08
it verify thermostat operation. A qualified technician
(V/Ph/Hz)
must frequently verify power to the heat tape and
(kW)
5,2
confirm operation of the heat tape thermostat, to avoid
(kW)
6,3
catastrophic damage to the evaporator.
(type)
(kW)
0,23
(A)
1,1
CAUTION! With factory-fitted disconnect switch, trace
(A)
3,2
heating is taken from the live side of the isolator so
power remains on. Supply voltage to the heating tapes
(m
/h)
490
3
(m
/h)
820
is 400V.
3
(m
/h)
980
3
Don't energize heaters without water. In case of winter
(type)
water drainage for freeze protection, it is compulsory to
(Dia)
3/4"
disconnect the evaporator heaters to protect them from
(V/Ph/Hz)
230/1/50
burning due to overheat.
(kW)
2/4
Water Pump Power Supply
(kW)
6,3
2
Provide power-supply wiring with fused disconnect
(mm)
386x221x8
switch(es) for the chilled water pump(s).
-
Interconnecting Wiring
(mm)
-
(type)
Chilled-Water Flow (Pump) Interlock
(l/h - mm)
CGAF/CXAF requires a field-supplied, control-voltage
contact input through a flow proving switch (6S51) and
(dB(A))
36/40/43
an auxiliary contact (6K51). Connect the proving switch
(dB(A))
46/50/53
and auxiliary contact to terminal 2 connector J2 cards
(mm)
890 x 600
(1A11). Refer to the field wiring diagram for details.
(mm)
250
(mm)
933 x 644
Chilled-Water Pump Control
(mm)
260
An evaporator water-pump output relay closes when
(kg)
32
the chiller is given a signal to go into the AUTO mode
of operation from any source. The contact is opened to
(A)
8/16
turn off the pump in the event of most machine-level
(A)
16 (2kW),25 (4kW)
diagnostics, to prevent the buildup of pump heat.
CAUTION! The evaporator water pump output relay
must be used to control the chilled water pump and to
benefit from the water pump timer function at startup
and shutdown of the chiller. This is required when
the chiller is in operation under freezing conditions,
especially if the chilled water loop does not contain
glycol.
CAUTION! Refer to Freeze Protection section for
information about the evaporator circulating pump.
Alarm and Status Relay Outputs
(Programmable Relays)
See CGAF / CXAF User Guide for alarm and status relay
outputs.
EDLS and ECWS Analog Input Signal
Wiring Details
See CGAF / CXAF User Guide for EDLS and ECWS.
12
20
230/1/50
8,3
15
11,9
18,9
2 x direct drive centrifugal
0,46
0,65
2,2
3,1
5,5
9,3
980
1400
1650
2300
1970
2600
ISO R7 rotating female
3/4"
1 1/2"
230/1/50 or 400/3/50
400/3/50
8
10
12
17,4
2
2
486x271x8
586x321x8
2
2
486x264x48
586x314x48
Centrifugal
24 - 500
38/41/44
46/50/53
48/51/54
56/60/63
1090 x 710
1290 x 820
300
350
1133 x 754
1333 x 864
310
360
46
61
galvanised steel
8/16
8/16
40 (230V),3*16 (400V)
3*20
30
45
18,8
30,1
20,9
38,2
1,04
1,51
4,7
5,5
14,1
16,5
1800
2700
3000
4500
3600
5400
1 1/2"
1 1/2"
400/3/50
400/3/50
12
12
22,4
34,5
2
2
586*421*8
586*621*8
2
2
586*414*48
586*614*48
47/52/57
47/52/58
57/62/67
57/62/68
1290 x 970
1290 x 1090
450
650
1333 x 1008
1333*1133
460
660
76
118
8/25
8/25
3*25
3*25
CG-SVX039B-GB
UNT-PRC002-GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents