Consumption Data File; Main Areas For Consumption Data File - Siemens Synco OZW772 Series Commissioning Instructions

Web server v6.0 for synco system
Hide thumbs Also See for Synco OZW772 Series:
Table of Contents

Advertisement

Notes
Note
User defined texts
Web Server data
74 / 176
Siemens
Building Technologies
· Compatible M-bus meters are listed in data sheet N2735 on the consumption
data interface WRI982.
· The QAX9.... documentation includes additional information on meter
integration and consumption data acquisition up to QAX9...
· Information on pulse processing for Synco 700 controllers is available in the
corresponding documentation on basic.
· Information on KNX S-Mode products is available in the manufacturer's product
documentation.
6.1

Consumption data file

You can view the consumption data file via web operation (local or remote)
(Section 4.4) or sent via e-mail (Section 6.3).
The consumption data file displays meters for those KNX devices with device
pages generated on the Web Server.
The device web pages must be re-generated after commissioning and changes
to the plant (see Section 2.4).
Static metering information is available immediately after generation. The current
values for operational meters are available in the consumption data file at the latest
after 24 hours.
6.1.1

Main areas for consumption data file

Header, Information line 1...10 and Footer are user defined settings that can be
entered in the web operation for the Web Server (see Section 2.5.3.6,
"Consumption data").
Plant information relies on the Web Server and is mapped "ad hoc" when querying
and sending the consumption data file.
Web server OZW772... V6.0
Record consumption data
CE1C5701en
2015-10-12

Hide quick links: