Siemens Synco OZW772 Series Commissioning Instructions page 29

Web server v6.0 for synco system
Hide thumbs Also See for Synco OZW772 Series:
Table of Contents

Advertisement

Send messages
Notes
Siemens
Building Technologies
Data point
Message receiver 1...4
Def' value: (message receiver x)
Setting values: max. 20
characters
Receiver type
Default value: ---
Setting values: --, E-mail
Fault priority
Default value: All
Setting values: All,
Only urgent ones
Email address
Default value: message receiver
@example.com
Setting values:max. 49characters
Number of messages for
send
The number of messages pending is available under "Number of messages for
sending".
A time frame can be defined during which messages can be sent for each receiver.
· The following settings are optional when restricting the time for sending
messages (default settings: No restriction).
· In general: Messages occurring outside the send periods are sent afterwards if
still pending during the send period.
Path: Home > 0.2.150 OZW772.xx > Message receiver > Message receiver 1...4
> Send messages
You can define time periods per weekday or special day when messages can be
sent to the message receivers.
Special days are defined via Holidays/special days.
Data point
Monday...Sunday,
Special day
Default val: Monday, 00:00
On ...
Special day,
00:00 On ...
Setting val: Monday - Sunday,
Special day
00:00 - 24:00 Off/on
Web server OZW772... V6.0
Commissioning
Explanation, example
Message receiver 1...4 is a name (text) and
is displayed in the web browser. You must
run "generate" to display the change (for the
workflow, see Section "Refresh device web
pages" in Section 2.4).
All Receiver types are available:
"---": No messages to this message receiver.
"E-mail": Configure message receiver for e-
mail.
The setting value "Only urgent ones" acts as
a filter for sending fault messages.
The setting value must match the e-mail
address of the message receiver.
Number of messages to be transmitted at
next send.
Explanation, example
Each message receiver is assigned a time
switch to program max. 3 transmission times
for each weekday, i.e. periods during which
the Web Server can send messages.
The default value sends messages
throughout the entire period.
— —
29 / 176
CE1C5701en
2015-10-12