Siemens Synco OZW772 Series Commissioning Instructions page 155

Web server v6.0 for synco system
Hide thumbs Also See for Synco OZW772 Series:
Table of Contents

Advertisement

Update transmitted
project data in OZW
Siemens
Building Technologies
The device stats of changed devices is no longer up-to-date after transmitted
project data from ETS to the OZW.
OZW must be selected and updated with "Generate". Administrator or service user
rights are required.
Confirm with "OK".
OZW is now updated.
The changes can now be viewed in the menu tree.
The following changes are recognized and displayed on the device list as "Not
updated":
· Writing and entire project
· Write a project without changes
· Add / delete /rename KNX pages.
· Add /Delete /Change type/Rename data points.
Web server OZW772... V6.0
KNX S-Mode
155 / 176
CE1C5701en
2015-10-12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents