Default KNX subtype
158 / 176
Siemens
Building Technologies
Data points can be defined in ETS that are not explicitly supported by OZW.
OZW converts any such data points received from ETS into its default subtypes.
KNX main
Default KNX
type
subtype
1.*
1.001
2.*
2.001
5.*
5.001
6.*
6.001
7.*
7.001
8.*
8.001
9.*
9.001
12.*
12.001
13.*
13.001
14.*
14.019
18.*
18.001
20.*
20.002
* = unsupported subtype from this main type group
Web server OZW772... V6.0
KNX S-Mode
Name and decoding
Switching (Off/On)
Prio. switching (Off/On controlled)
Percent (0...100%)
Percent (-128...127%)
Value (0...65535)
Value (-32768...32767)
Temperature (-273...670 760 °C)
Value (unsigned 0...4 294 967 295)
Value (signed
-2 147 483 648...2 147 483 647)
Current (A).
(
Scene control
Scene control: Call up/memorize
scene number)
Building mode (building operating mode:
Building used, building not used, building
protection)
CE1C5701en
2015-10-12