Port forwarding (PAT)
Notes
112 / 176
Siemens
Building Technologies
· Port Forwarding is used to determine which local IP addresses/ports the router
translates to which public IP addresses/ports.
· Web operating pages are preset on the Web Server via Port 80 (HTTP) or port
443 (HTTPS). As a result, queries from the Internet must be translated using
the public IP address/port to the private IP address/port 80 or 443 for the Web
Server.
· If the connection of the software ETS Tool is via the Internet, Port 3671
(reserved for ETS) must be translated by public as well as private IP addresses.
· When using PC software ACS790 for remote operation, you must also change
Port 21 (FTP) and Port 50005 (ACS private) from the public to a private IP
address.
· The port IP address is appended to the web browser address line: <IP
address>:<Port>, e.g.
· The web browser always uses port 80 unless another port is entered. As a
result, the information in the address line for the web browser is always: <IP
address>:80 and <IP address>, or
· Ports not equal to 80 are considered more robust against hackers.
· We recommend using Port Forwarding from the private range for ports (see
Section 11.3.1).
In the example, queries from the Internet to a public IP address (Internet
connection)/port 80 are forwarded to local IP address
Server)/Port 80. Port 21 is also enabled for file transfer.
Web server OZW772... V6.0
Communications
122.104.2.10:8080.
122.104.2.10:80
and
122.104.2.10.
192.168.2.10