Operating Page "Faults Current; Operating Page "Settings; Web Server; Time Of Day/Date - Siemens Synco OZW772 Series Commissioning Instructions

Web server v6.0 for synco system
Hide thumbs Also See for Synco OZW772 Series:
Table of Contents

Advertisement

Language and
code number
Time zone
24 / 176
Siemens
Building Technologies
2.5.2

Operating page "Faults current"

Local faults and faults in system are displayed under "Faults current".
Path: Home > 0.5 OZW672... > Faults current
A description of faults is available in Section 4.3,"Faults"
2.5.3

Operating page "Settings"

2.5.3.1

Web Server

Path: Home > 0.2.150 OZW772.xx > Settings > Web Server
Data point
Language
Default val: English
Setting val: see example
Code
Default val: 01
Setting val: max. 20 charact.
Reset admin password *
Default val: No
Setting val: Yes
* with PC software ACS790 only.
2.5.3.2

Time of day/date

Path: Home > 0.2.150 OZW772.xx > Settings > Time of day/date
Data point
Time zone
Default val: GMT +01:00
Berlin, Rome
Setting val: misc. Time zones
Web server OZW772... V6.0
Commissioning
Explanation, example
Web Server language: Is used for Web Server
fault texts, message history, messages and
system reports.
Access code for PC Software ACS790.
If you do not know the administrator password
for the Web Server, setting value "Yes" again
provides access to the Web Server via the
administrator password "Password".
"Password or Password.1" is possible again
(Administrator password for delivery of
devices to Version 5.2 = "Password", for
devices as of Version 6.0 = "Password.1").
Setting value "Yes" is a temporary state, i.e.
the setting value automatically goes to "No"
after ca. 2 seconds.
Explanation, example
The time zone setting value is based on UTC
(GMT). The time zone also defines daylight
saving time / standard time changeover.
*
*
CE1C5701en
2015-10-12