Proline Promass F 300 Coriolis Flowmeter
EtherNet/IP
Operating Instructions Manual
BA01807O/06/EN/01.17
Valid as of version 01.00 zz (Device firmware)
71382409
MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Proline Promass F 300

  • Page 1 MANUAL Proline Promass F 300 Coriolis Flowmeter EtherNet/IP Operating Instructions Manual BA01807O/06/EN/01.17 Valid as of version 01.00 zz (Device firmware) 71382409...
  • Page 2 • The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser Sales Center will supply you with current information and updates to these instructions. Important All information and technical specifications in this documentation have been carefully checked and compiled by the author.
  • Page 3: Table Of Contents

    Proline Promass F 300 EtherNet/IP Table of contents Table of contents 5.2.2 Measuring devices with lifting lugs . . About this document ....6 5.2.3 Transporting with a fork lift .
  • Page 4 Table of contents Proline Promass F 300 EtherNet/IP Access to the operating menu via the local 10.5.4 Selecting and setting the medium . . display ......
  • Page 5 13.2 Measuring and test equipment ... 216 13.3 Endress+Hauser services ....216 Repairs ......217 14.1 General notes .
  • Page 6: About This Document

    About this document Proline Promass F 300 EtherNet/IP About this document Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
  • Page 7: Communication Symbols

    Proline Promass F 300 EtherNet/IP About this document 1.2.3 Communication symbols Symbol Meaning Wireless Local Area Network (WLAN) Communication via a wireless, local network. Light emitting diode is off. Light emitting diode is on. Light emitting diode is flashing. 1.2.4...
  • Page 8: Symbols In Graphics

    • The W@M Device Viewer : Enter the serial number from the nameplate (www.endress.com/deviceviewer) • The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2-D matrix code (QR code) on the nameplate. For a detailed list of the individual documents along with the documentation code →...
  • Page 9: Supplementary Device-Dependent Documentation

    Proline Promass F 300 EtherNet/IP About this document Document type Purpose and content of the document Transmitter Brief Operating Guides you quickly to the 1st measured value - Part 2 Instructions The Transmitter Brief Operating Instructions are aimed at specialists with responsibility for commissioning, configuring and parameterizing the measuring device (until the first measured value).
  • Page 10: Basic Safety Instructions

    Basic safety instructions Proline Promass F 300 EtherNet/IP Basic safety instructions Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
  • Page 11: Workplace Safety

    Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
  • Page 12: Product Safety

    It meets general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device.
  • Page 13: Protecting Access Via A Password

    Proline Promass F 300 EtherNet/IP Basic safety instructions the motherboard). When hardware write protection is enabled, only read access to the parameters is possible. Hardware write protection is disabled when the device is delivered →  169. 2.7.2 Protecting access via a password Different passwords are available to protect write access to the device parameters or access to the device via the WLAN interface.
  • Page 14: Access Via Web Server

    Basic safety instructions Proline Promass F 300 EtherNet/IP 2.7.4 Access via Web server The device can be operated and configured via a Web browser with the integrated Web server (→  66). The connection is via the service interface (CDI-RJ45), the connection for EtherNet/IP signal transmission (RJ45 connector) or the WLAN interface.
  • Page 15: Product Description

    Proline Promass F 300 EtherNet/IP Product description Product description The device consists of a transmitter and a sensor. The device is available as a compact version: The transmitter and sensor form a mechanical unit. Product design N ic te r e rg ö...
  • Page 16: Incoming Acceptance And Product

    A0028673 and documents present? • If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center. • Depending on the device version, the CD-ROM might not be part of the delivery! The Technical Documentation is available via the Internet or via the Endress+Hauser...
  • Page 17: Product Identification

    • Enter the serial number from the nameplates into the Endress+Hauser Operations App or scan the 2-D matrix code (QR code) on the nameplate with the Endress+Hauser Operations App: all the information for the measuring device is displayed. For an overview of the scope of the associated Technical Documentation, refer to the following: •...
  • Page 18: Transmitter Nameplate

    Incoming acceptance and product identification Proline Promass F 300 EtherNet/IP 4.2.1 Transmitter nameplate 3 4 5 Order code: Ser. no.: Ext. ord. cd.: Date: A0029192  2 Example of a transmitter nameplate Manufacturing location Name of the transmitter Order code Serial number (ser.
  • Page 19: Sensor Nameplate

    Proline Promass F 300 EtherNet/IP Incoming acceptance and product identification 4.2.2 Sensor nameplate Order code: Ser. no.: Ext. ord. cd.: Date: A0029199  3 Example of a sensor nameplate Name of the sensor Manufacturing location Order code Serial number (ser. no.) Extended order code (Ext.
  • Page 20 Incoming acceptance and product identification Proline Promass F 300 EtherNet/IP 4.2.3 Symbols on measuring device Symbol Meaning WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury. Reference to documentation Refers to the corresponding device documentation.
  • Page 21: Storage And Transport

    Proline Promass F 300 EtherNet/IP Storage and transport Storage and transport Storage conditions Observe the following notes for storage: ‣ Store in the original packaging to ensure protection from shock. ‣ Do not remove protective covers or protective caps installed on process connections.
  • Page 22: Measuring Devices With Lifting Lugs

    Storage and transport Proline Promass F 300 EtherNet/IP A0029214 5.2.2 Measuring devices with lifting lugs CAUTION Special transportation instructions for devices with lifting lugs ‣ Only use the lifting lugs fitted on the device or flanges to transport the device.
  • Page 23: Installation

    Proline Promass F 300 EtherNet/IP Installation Installation Installation conditions No special measures such as supports are necessary. External forces are absorbed by the construction of the device. 6.1.1 Mounting position Mounting location A0028772 To prevent measuring errors arising from accumulation of gas bubbles in the measuring tube, avoid the following mounting locations in the pipe: •...
  • Page 24 Installation Proline Promass F 300 EtherNet/IP A0028773  4 Installation in a down pipe (e.g. for batching applications) Supply tank Sensor Orifice plate, pipe restriction Valve Batching tank Ø orifice plate, pipe restriction [mm] [in] [mm] [in] ³⁄₈ 0.24 ½...
  • Page 25 Proline Promass F 300 EtherNet/IP Installation Orientation Recommendation Horizontal orientation, transmitter at bottom Exceptions: →  5,  25 A0015590 Horizontal orientation, transmitter at side A0015592 Applications with low process temperatures may decrease the ambient temperature. To maintain the minimum ambient temperature for the transmitter, this orientation is recommended.
  • Page 26: Requirements From Environment And Process

    If operating outdoors: Avoid direct sunlight, particularly in warm climatic regions. You can order a weather protection cover from Endress+Hauser : →  219 System pressure It is important that cavitation does not occur, or that gases entrained in the liquids do not outgas.
  • Page 27 Proline Promass F 300 EtherNet/IP Installation The following device versions are recommended for versions with thermal insulation: • Version with extended neck for insulation: Order code for "Sensor option", option CG with an extended neck length of 105 mm (4.13 in).
  • Page 28: Special Mounting Instructions

    Installation Proline Promass F 300 EtherNet/IP Heating options If a fluid requires that no heat loss should occur at the sensor, users can avail of the following heating options: • Electrical heating, e.g. with electric band heaters • Via pipes carrying hot water or steam •...
  • Page 29 Proline Promass F 300 EtherNet/IP Installation DN 8 ( ")...150 (6") DN 250 (10") ⁄ RUPTURE DISK A0028903 Rupture disk label Rupture disk with 1/2" NPT internal thread with 1" width across flat Transport protection Zero point adjustment All measuring devices are calibrated in accordance with state-of-the-art technology.
  • Page 30: Mounting The Measuring Device

    Installation Proline Promass F 300 EtherNet/IP Cover locking NOTICE Order code "Housing", option L "Cast, stainless": The covers of the transmitter housing are provided with a borehole to lock the cover. The cover can be locked using screws and a chain or cable provided by the customer.
  • Page 31: Turning The Transmitter Housing

    Proline Promass F 300 EtherNet/IP Installation 1. Ensure that the direction of the arrow on the nameplate of the sensor matches the flow direction of the fluid. 2. Install the measuring device or turn the transmitter housing so that the cable entries do not point upwards.
  • Page 32: Post-Installation Check

    Installation Proline Promass F 300 EtherNet/IP – – – 3 mm A0030035 1. Depending on the device version: Loosen the securing clamp of the connection compartment cover. 2. Unscrew the connection compartment cover. 3. Turn the display module to the desired position: max. 8 × 45° in each direction.
  • Page 33: Electrical Connection

    Proline Promass F 300 EtherNet/IP Electrical connection Electrical connection NOTICE The measuring device does not have an internal circuit breaker. ‣ For this reason, assign the measuring device a switch or power-circuit breaker so that the power supply line can be easily disconnected from the mains.
  • Page 34 Electrical connection Proline Promass F 300 EtherNet/IP Pulse/frequency/switch output Standard installation cable is sufficient. Relay output Standard installation cable is sufficient. Current input 0/4 to 20 mA Standard installation cable is sufficient. Status input Standard installation cable is sufficient. Cable diameter •...
  • Page 35 Proline Promass F 300 EtherNet/IP Electrical connection Capacitance: core/shield Maximum 1 000 nF for Zone 1, Class I, Division 1 Maximum 24 µH/Ω for Zone 1, Class I, Division 1 Cable length Maximum 300 m (1 000 ft), see the following table Max.
  • Page 36: Terminal Assignment

    Electrical connection Proline Promass F 300 EtherNet/IP 7.1.3 Terminal assignment Transmitter: supply voltage, input/outputs The terminal assignment of the inputs and outputs depends on the individual order version of the device. The device-specific terminal assignment is documented on an adhesive label in the terminal cover.
  • Page 37: Preparing The Measuring Device

    Proline Promass F 300 EtherNet/IP Electrical connection 7.1.6 Preparing the measuring device NOTICE Insufficient sealing of the housing! Operational reliability of the measuring device could be compromised. ‣ Use suitable cable glands corresponding to the degree of protection. 1. Remove dummy plug if present.
  • Page 38 Electrical connection Proline Promass F 300 EtherNet/IP Connecting the EtherNet/IP connector – – – 3 mm A0029813 1. Loosen the securing clamp of the connection compartment cover. 2. Unscrew the connection compartment cover. 3. Squeeze the tabs of the display module holder together.
  • Page 39 Proline Promass F 300 EtherNet/IP Electrical connection 22 mm 24 mm N ic t e r e r g ö f f iz e t e n s io r ir A0033722 7. Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry.
  • Page 40 Electrical connection Proline Promass F 300 EtherNet/IP 22 mm 24 mm – A0033984 4. Connect the cable in accordance with the terminal assignment .  Signal cable terminal assignment: The device-specific terminal assignment is documented on an adhesive label in the terminal cover.
  • Page 41: Integrating The Transmitter Into A Network

    Proline Promass F 300 EtherNet/IP Electrical connection 7.2.2 Integrating the transmitter into a network This section only presents the basic options for integrating the device into a network. For information on the procedure to follow to connect the transmitter correctly →  37.
  • Page 42 Electrical connection Proline Promass F 300 EtherNet/IP Integrating into a ring topology The device is integrated via the terminal connection for signal transmission (output 1) and the connection to the service interface (CDI-RJ45). Note the following when connecting: • Recommended cable: CAT5e, CAT6 or CAT7, with shielded connector •...
  • Page 43: Connecting The Remote Display And Operating Module Dkx001

    Proline Promass F 300 EtherNet/IP Electrical connection 7.2.3 Connecting the remote display and operating module DKX001 The remote display and operating module DKX001 is available as an optional extra →  219. • The remote display and operating module DKX001 is only available for the following housing versions, order code for "Housing":...
  • Page 44: Special Connection Instructions

    Electrical connection Proline Promass F 300 EtherNet/IP Special connection instructions 7.4.1 Connection examples EtherNet/IP A0028767  8 Connection example for EtherNet/IP Control system (e.g. PLC) Ethernet switch Observe cable specifications Device plug Transmitter EtherNet/IP: DLR (Device Level Ring) A0027544 Control system (e.g. PLC) Ethernet switch Observe cable specifications →...
  • Page 45 Proline Promass F 300 EtherNet/IP Electrical connection Current output 4-20 mA 4...20 mA A0028758  9 Connection example for 4-20 mA current output (active) Automation system with current input (e.g. PLC) Analog display unit: observe maximum load Transmitter 4...20 mA A0028759 ...
  • Page 46 Electrical connection Proline Promass F 300 EtherNet/IP Switch output A0028760  12 Connection example for switch output (passive) Automation system with switch input (e.g. PLC) Power supply Transmitter: Observe input values →  226 Relay output A0028760  13 Connection example for relay output (passive) Automation system with relay input (e.g.
  • Page 47: Hardware Settings

    Proline Promass F 300 EtherNet/IP Electrical connection Status input A0028764  15 Connection example for status input Automation system with status output (e.g. PLC) Power supply Transmitter: Observe input values Hardware settings 7.5.1 Setting the device address The IP address of the measuring device can be configured for the network via DIP switches.
  • Page 48: Activating The Default Ip Address

    Electrical connection Proline Promass F 300 EtherNet/IP A0029635 1. Depending on the housing version, loosen the securing clamp or fixing screw of the housing cover. 2. Depending on the housing version, unscrew or open the housing cover and disconnect the local display from the main electronics module where necessary.
  • Page 49: Ensuring The Degree Of Protection

    Proline Promass F 300 EtherNet/IP Electrical connection Ensuring the degree of protection The measuring device fulfills all the requirements for the IP66/67 degree of protection, Type 4X enclosure. To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps after the electrical connection: 1.
  • Page 50: Operation Options

    Operation options Proline Promass F 300 EtherNet/IP Operation options Overview of operation options A0034513 Local operation via display module Computer with Web browser (e.g. Internet Explorer) or with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX350 or SFX370 Mobile handheld terminal Control system (e.g.
  • Page 51: Structure And Function Of The Operating Menu

    Proline Promass F 300 EtherNet/IP Operation options Structure and function of the operating menu 8.2.1 Structure of the operating menu For an overview of the operating menu for experts: "Description of Device Parameters" document supplied with the device→  255...
  • Page 52 Operation options Proline Promass F 300 EtherNet/IP Operating menu for operators and maintenances Language Operatation Language Parameter 1 Parameter n Submenu 1 Submenu n Setup Device tag Wizard 1 / Parameter 1 Wizard n / Parameter n Advanced setup Enter access code...
  • Page 53: Operating Philosophy

    Proline Promass F 300 EtherNet/IP Operation options 8.2.2 Operating philosophy The individual parts of the operating menu are assigned to certain user roles (operator, maintenance etc.). Each user role contains typical tasks within the device lifecycle. For custody transfer, once the device has been put into circulation or sealed, its operation is restricted.
  • Page 54: Access To The Operating Menu Via The Local Display

    Operation options Proline Promass F 300 EtherNet/IP Menu/parameter User role and tasks Content/meaning Expert function-oriented Tasks that require detailed Contains all the parameters of the device and makes it possible to access knowledge of the function of the these parameters directly using an access code. The structure of this menu is...
  • Page 55 Proline Promass F 300 EtherNet/IP Operation options Status area The following symbols appear in the status area of the operational display at the top right: • Status signals→  189 – F: Failure – C: Function check – S: Out of specification –...
  • Page 56: Navigation View

    Operation options Proline Promass F 300 EtherNet/IP Measurement channel numbers Symbol Meaning Measurement channel 1 to 4 The measurement channel number is displayed only if more than one channel is present for the same measured variable type (e.g. Totalizer 1 to 3).
  • Page 57 Proline Promass F 300 EtherNet/IP Operation options For more information about the icons in the menu, refer to the "Display area" section →  57 Status area The following appears in the status area of the navigation view in the top right corner: •...
  • Page 58: Editing View

    Operation options Proline Promass F 300 EtherNet/IP Wizard operation Symbol Meaning Switches to the previous parameter. Confirms the parameter value and switches to the next parameter. Opens the editing view of the parameter. 8.3.3 Editing view Numeric editor +0.000 Xx –...
  • Page 59 Proline Promass F 300 EtherNet/IP Operation options Text editor Xxxxxxx A B C D E F G H I J K M N O P Q R S T U V W A0034114  18 For entering text in parameters (e.g. tag name)
  • Page 60: Operating Elements

    Operation options Proline Promass F 300 EtherNet/IP Controlling data entries Symbol Meaning Move entry position Reject entry Confirm entry Delete character immediately to the left of the entry position Delete character immediately to the right of the entry position Clear all the characters entered 8.3.4...
  • Page 61: Opening The Context Menu

    Proline Promass F 300 EtherNet/IP Operation options Operating key(s) Meaning Escape key combination (press keys simultaneously) In a menu, submenu • Pressing the key briefly: – Exits the current menu level and takes you to the next higher level. – If help text is open, closes the help text of the parameter.
  • Page 62: Navigating And Selecting From List

    Operation options Proline Promass F 300 EtherNet/IP 8.3.6 Navigating and selecting from list Different operating elements are used to navigate through the operating menu. The navigation path is displayed on the left in the header. Icons are displayed in front of the individual menus.
  • Page 63: Calling The Parameter Directly

    Proline Promass F 300 EtherNet/IP Operation options 8.3.7 Calling the parameter directly A parameter number is assigned to every parameter to be able to access a parameter directly via the onsite display. Entering this access code in the Direct access parameter calls up the desired parameter directly.
  • Page 64: Changing The Parameters

    Operation options Proline Promass F 300 EtherNet/IP 8.3.9 Changing the parameters Parameters can be changed via the numeric editor or text editor. • Numeric editor: Change values in a parameter, e.g. specifications for limit values. • Text editor: Enter text in a parameter, e.g. tag name.
  • Page 65: Disabling Write Protection Via Access

    Proline Promass F 300 EtherNet/IP Operation options 8.3.11 Disabling write protection via access code If the -symbol appears on the local display in front of a parameter, the parameter is write-protected by a user-specific access code and its value cannot be changed at the moment using local operation →...
  • Page 66: Access To The Operating Menu Via The Web Browser

    Operation options Proline Promass F 300 EtherNet/IP Access to the operating menu via the Web browser 8.4.1 Function range Thanks to the integrated Web server, the device can be operated and configured via a Web browser and via a service interface (CDI-RJ45) or via a WLAN interface. The structure of the operating menu is the same as for the local display.
  • Page 67 Proline Promass F 300 EtherNet/IP Operation options Computer settings Settings Interface CDI-RJ45 WLAN User rights Appropriate user rights (e.g. administrator rights) for TCP/IP and proxy server settings are necessary (for adjusting the IP address, subnet mask etc.). Proxy server settings of the...
  • Page 68: Establishing A Connection

    Operation options Proline Promass F 300 EtherNet/IP Device WLAN interface IP address If the IP address of the device is not known: • The IP address can be read out via local operation: Diagnostics → Device information → IP address •...
  • Page 69 Proline Promass F 300 EtherNet/IP Operation options 4. If a 2nd network card is not used, close all the applications on the notebook.  Applications requiring Internet or a network, such as e-mail, SAP applications, Internet or Windows Explorer. 5. Close any open Internet browsers.
  • Page 70: Logging On

    Operation options Proline Promass F 300 EtherNet/IP Starting the Web browser 1. Start the Web browser on the computer. 2. Enter the IP address of the Web server in the address line of the Web browser: 192.168.1.212  The login page appears.
  • Page 71: User Interface

    Proline Promass F 300 EtherNet/IP Operation options 8.4.5 User interface A0029418 Function row Local display language Navigation area Header The following information appears in the header: • Device name • Device tag • Device status with status signal →  192 •...
  • Page 72: Disabling The Web Server

    Operation options Proline Promass F 300 EtherNet/IP Navigation area If a function is selected in the function bar, the submenus of the function open in the navigation area. The user can now navigate through the menu structure. Working area Depending on the selected function and the related submenus, various actions can be performed in this area: •...
  • Page 73: Access To The Operating Menu Via The Operating Tool

    Proline Promass F 300 EtherNet/IP Operation options 2. Close the Web browser. 3. If no longer needed: Reset modified properties of the Internet protocol (TCP/IP) →  68. If communication with the Web server was established via the default IP address 192.168.1.212, DIP switch No.
  • Page 74 Operation options Proline Promass F 300 EtherNet/IP A0033725  21 Options for remote operation via EtherNet/IP network: ring topology Automation system, e.g. "RSLogix" (Rockwell Automation) Workstation for measuring device operation: with Custom Add-On Profile for "RSLogix 5000" (Rockwell Automation) or with Electronic Data Sheet (EDS) Computer with Web browser (e.g.
  • Page 75 Proline Promass F 300 EtherNet/IP Operation options A0027563  22 Connection via service interface (CDI-RJ45) Computer with Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for accessing the integrated device Web server or with "FieldCare", "DeviceCare" operating tool with COM DTM "CDI Communication TCP/IP"...
  • Page 76 Operation options Proline Promass F 300 EtherNet/IP Degree of protection IP67 Available antennas • Internal antenna • External antenna (optional) In the event of poor transmission/reception conditions at the place of installation.  Only one antenna active in each case! Max.
  • Page 77: Fieldcare

    FieldCare Function scope FDT-based plant asset management tool from Endress+Hauser. It can configure all smart field devices in a system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition.
  • Page 78: Devicecare

    DeviceCare Function scope Tool to connect and configure Endress+Hauser field devices. The fastest way to configure Endress+Hauser field devices is with the dedicated "DeviceCare" tool. Together with the device type managers (DTMs) it presents a convenient, comprehensive solution. For details, see Innovation Brochure IN01047S Source for device description files See information →...
  • Page 79: System Integration

    Proline Promass F 300 EtherNet/IP System integration System integration Overview of device description files 9.1.1 Current version data for the device Firmware version 01.00.zz • On the title page of the Operating Instructions • On the transmitter nameplate • Firmware version Diagnostics →...
  • Page 80: Overview Of System Files

    System integration Proline Promass F 300 EtherNet/IP Overview of system files System files Version Description How to acquire Electronic Data Certified in accordance with the • www.endress.com → Download- Sheet (EDS following ODVA guidelines: Area system file) • Conformance test •...
  • Page 81 Proline Promass F 300 EtherNet/IP System integration Heartbeat monitoring Permanently assigned → fixed input assembly →  86 input group (Assem112) 96 byte Input assembly custom Configurable → →  86 (Assem101) 88 byte input group Output assembly fix Permanently assigned ←...
  • Page 82: Input And Output Groups

    System integration Proline Promass F 300 EtherNet/IP 9.4.2 Input and output groups Possible configurations Configuration 1: Exclusive Owner Multicast Input Assembly Fix Instance Size (byte) Min. RPI (ms) Input Assembly Configurable Configuration 0 x 64 – Output Assembly Fix O → T Configuration...
  • Page 83 Proline Promass F 300 EtherNet/IP System integration Configuration 7: Exclusive Owner Multicast Input Assembly Configurable Instance Size (byte) Min. RPI (ms) Input Assembly Configurable Configuration 0 x 69 – – Output Assembly Fix O → T Configuration 0 x 66 Input Assembly Fix T →...
  • Page 84 System integration Proline Promass F 300 EtherNet/IP Description Byte Reference density 29-32 Totalizer 1 33-36 Totalizer 2 37-40 Totalizer 3 41-44 Diagnostic information via EtherNet/IP →  93 Mass flow fixed input assembly (Assem106), 32 byte Description Byte 1. File header (not visible) 2.
  • Page 85 Proline Promass F 300 EtherNet/IP System integration Description Byte 3. Carrier mass flow 37-40 4. Target volume flow 41-44 5. Carrier volume flow 45-48 6. Target corrected volume flow 49-52 7. Carrier corrected volume flow 53-56 8. Concentration 57-60 9. Volume flow unit 61-62 10.
  • Page 86 System integration Proline Promass F 300 EtherNet/IP Description Byte 13. Oil density unit 73-74 14. Water density unit 75-76 Only available with the Petroleum application package Heartbeat monitoring fixed input assembly (Assem112), 100 byte Description Byte 1. Mass flow fixed input assembly 1-32 2.
  • Page 87 Proline Promass F 300 EtherNet/IP System integration Possible input values Possible input values 1 to 10: • Off • Temperature • Exciter current 0 • Mass flow • Carrier tube temperature • Exciter current 1 • Volume flow • Electronic temperature •...
  • Page 88 System integration Proline Promass F 300 EtherNet/IP Description (format) Byte Value 17. Not used – 18. Control totalizer 1 (integer) • 32226 (0): Add • 32490 (1): Reset and stop 19. Control totalizer 2 (integer) • 32228 (2): Default value and stop •...
  • Page 89 Proline Promass F 300 EtherNet/IP System integration Description (format) Byte Value 28. External reference density unit (integer) 29-30 • 32840 (240): kg/Nm • 32841 (240): kg/Nl • 32842 (240): g/Scm • 32843 (240): kg/Scm • 32844 (240): lb/Sft 29. Not used 31-32 –...
  • Page 90 System integration Proline Promass F 300 EtherNet/IP Description (format) Bits Byte Offset Parameter 84 System units Dynamic viscosity unit Parameter 78 System units Concentration unit Parameter 82 System units Oil density unit Parameter 83 System units Water density unit Parameter 90...
  • Page 91 Proline Promass F 300 EtherNet/IP System integration Description (format) Bits Byte Offset Parameter 22 Configurable input assembly Input assembly position 15 Parameter 23 Configurable input assembly Input assembly position 16 Parameter 24 Configurable input assembly Input assembly position 17 Parameter 25...
  • Page 92 System integration Proline Promass F 300 EtherNet/IP Description (format) Bits Byte Offset Parameter 61 Diagnostic behavior Assign behavior for diagnostic information 302 None Parameter 74 Diagnostic behavior Assign behavior for diagnostic information 441 Parameter 75 Diagnostic behavior Assign behavior for diagnostic...
  • Page 93: Diagnostic Information Via Ethernet/Ip

    Proline Promass F 300 EtherNet/IP System integration Description (format) Bits Byte Offset 123. Parameter 162 Concentration Coefficient D1 124. Parameter 165 Concentration Coefficient D2 125. Parameter 168 Concentration Coefficient D3 126. Parameter 171 Concentration Coefficient D4 127. Parameter 55 Petroleum mode 128.
  • Page 94 System integration Proline Promass F 300 EtherNet/IP Status signal Short text Value Process temperature too high 16777413 Process temperature too low 16777414 Main electronic failure 16777428 Sensor temperature 16777429 Sensor temperature 16777430 Sensor connection 16777435 Sensor connection 16777436 Electronic failure...
  • Page 95 Proline Promass F 300 EtherNet/IP System integration Status signal Short text Value Process temperature too high 33554629 Process temperature too low 33554630 Special event 13 33554719 Special event 10 33554768 Special event 11 33554769 Special event 12 33554770 Simulation diagnostic event...
  • Page 96 System integration Proline Promass F 300 EtherNet/IP Status signal Short text Value Special event 11 134218065 Special event 12 134218066 Inhomogeneous 134218082 Tube damping too high 134218088 Monitoring failed 134218182 1089 Power on 268435545 1090 Configuration reset 268435546 1091 Configuration changed...
  • Page 97 Proline Promass F 300 EtherNet/IP System integration Status signal Short text Value 1461 Failed: Sensor verification 268435917 1462 Failed: Sensor electronic module verific. 268435918...
  • Page 98: Commissioning

    Commissioning Proline Promass F 300 EtherNet/IP Commissioning 10.1 Function check Before commissioning the measuring device: ‣ Make sure that the post-installation and post-connection checks have been performed. • "Post-installation check" checklist→  32 • "Post-connection check" checklist →  49 10.2...
  • Page 99: Configuring The Measuring Device

    Proline Promass F 300 EtherNet/IP Commissioning X X X X X X X 20.50 Main menu 0104-1 Display language English Operation Setup Display language 0104-1 English à Deutsch Español Français Display language 0104-1 à English Deutsch Español Français Hauptmenü 0104-1...
  • Page 100 Commissioning Proline Promass F 300 EtherNet/IP X X X X X X X 20.50 Main menu 0104-1 Display language English Display/operat. Setup Main menu Display/operat. Setup Diagnostic / ../Setup Medium selection XXXXXXXXX XXXXXXXXX A0032222-EN  24 Taking the example of the local display Depending on the device version, not all submenus and parameters are available in every device.
  • Page 101: Defining The Tag Name

    Proline Promass F 300 EtherNet/IP Commissioning ‣ Low flow cut off →  139 ‣ Partially filled pipe detection →  140 ‣ Advanced setup →  141 10.5.1 Defining the tag name To enable fast identification of the measuring point within the system, you can enter a unique designation using the Device tag parameter and thus change the factory setting.
  • Page 102 Commissioning Proline Promass F 300 EtherNet/IP Volume flow unit →  102 Volume unit →  102 Corrected volume flow unit →  102 Corrected volume unit →  102 Density unit →  103 Reference density unit →  103 →...
  • Page 103: Configuring The Communication

    Proline Promass F 300 EtherNet/IP Commissioning Parameter Description Selection Factory setting Density unit Select density unit. Unit choose list Country-specific: • kg/l Result • lb/ft³ The selected unit applies for: • Output • Simulation process variable • Density adjustment (Expert menu) Reference density unit Select reference density unit.
  • Page 104 Commissioning Proline Promass F 300 EtherNet/IP Subnet mask →  104 Default gateway →  104 Parameter overview with brief description Parameter Description User interface / Selection /  Factory setting User entry MAC address Displays the MAC address of the measuring Unique 12-digit character Each measuring device is given device.
  • Page 105 Proline Promass F 300 EtherNet/IP Commissioning 10.5.4 Selecting and setting the medium The Select medium wizard submenu contains parameters that must be configured in order to select and set the medium. Navigation "Setup" menu → Select medium ‣ Medium selection Select medium →...
  • Page 106: Interface

    Commissioning Proline Promass F 300 EtherNet/IP Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Select medium – Select medium type. • Liquid Liquid • Gas Select gas type The Gas option is selected in Select measured gas type.
  • Page 107: Displaying The I/O Configuration

    Proline Promass F 300 EtherNet/IP Commissioning 10.5.5 Displaying the I/O configuration The I/O configuration submenu guides the user systematically through all the parameters in which the configuration of the I/O modules is displayed. Navigation "Setup" menu → I/O configuration ‣...
  • Page 108 Commissioning Proline Promass F 300 EtherNet/IP Navigation "Setup" menu → Current input ‣ Current input 1 to n Terminal number →  108 →  108 Signal mode 0/4 mA value →  108 20 mA value →  108 Current span →...
  • Page 109: Configuring The Status Input

    Proline Promass F 300 EtherNet/IP Commissioning 10.5.7 Configuring the status input The Status input submenu guides the user systematically through all the parameters that have to be set for configuring the status input. Navigation "Setup" menu → Status input ‣...
  • Page 110 Commissioning Proline Promass F 300 EtherNet/IP Navigation "Setup" menu → Current output ‣ Current output 1 to n Terminal number →  110 →  110 Signal mode Assign current output 1 to n →  111 Current span →  112 0/4 mA value →...
  • Page 111 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description User interface /  Factory setting Selection / User entry Assign current output 1 to n – Select process variable for • Off Mass flow current output. • Mass flow • Volume flow • Corrected volume flow •...
  • Page 112 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description User interface /  Factory setting Selection / User entry Current span – Select current range for • 4...20 mA NAMUR Country-specific: process value output and • 4...20 mA US • 4...20 mA NAMUR upper/lower level for alarm •...
  • Page 113 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description User interface /  Factory setting Selection / User entry Failure mode One of the following options is Define output behavior in • Min. Max. selected in the Assign current alarm condition. • Max. output parameter (→  111): •...
  • Page 114: Configuring The Pulse/Frequency

    Commissioning Proline Promass F 300 EtherNet/IP 10.5.9 Configuring the pulse/frequency/switch output The Pulse/frequency/switch output wizard guides you systematically through all the parameters that can be set for configuring the selected output type. Navigation "Setup" menu → Advanced setup → Pulse/frequency/switch output ‣...
  • Page 115 Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Operating mode – Define the output as a pulse, • Pulse Pulse frequency or switch output. • Frequency • Switch Terminal number –...
  • Page 116 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Pulse width In the Operating mode Define time width of the 0.05 to 2 000 ms 100 ms parameter, the Pulse option is output pulse. selected, and one of the...
  • Page 117 Proline Promass F 300 EtherNet/IP Commissioning Measuring value at maximum →  120 frequency →  121 Failure mode Failure frequency →  121 Invert output signal →  121 Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User...
  • Page 118 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Assign frequency output The Frequency option is Select process variable for • Off selected in the Operating frequency output. • Mass flow mode parameter (→  114).
  • Page 119 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Minimum frequency value In the Operating mode Enter minimum frequency. 0.0 to 10 000.0 Hz 0.0 Hz parameter, the Frequency option is selected, and one of...
  • Page 120 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Measuring value at minimum In the Operating mode Enter measured value for Signed floating-point Depends on country frequency parameter, the Frequency minmum frequency. number and nominal...
  • Page 121 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Failure mode In the Operating mode Define output behavior in • Actual value 0 Hz parameter, the Frequency alarm condition. • Defined value option is selected, and one of •...
  • Page 122 Commissioning Proline Promass F 300 EtherNet/IP Configuring the switch output Navigation "Setup" menu → Pulse/frequency/switch output ‣ Pulse/frequency/switch output 1 to n Operating mode →  122 →  122 Terminal number Signal mode →  123 Switch output function →...
  • Page 123 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Signal mode – Select the signal mode for the • Passive Passive PFS output. • Active Switch output function The Switch option is selected Select function for switch •...
  • Page 124 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Assign limit • The Switch option is Select process variable for limit • Mass flow Mass flow selected in the Operating function. • Volume flow mode parameter.
  • Page 125: 10.5.10 Configuring The Relay Output

    Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Switch-on value • In the Operating mode Enter measured value for the Signed floating-point Country-specific: parameter, the Switch switch-on point. number • 0 kg/h option is selected.
  • Page 126 Commissioning Proline Promass F 300 EtherNet/IP Assign status →  127 Switch-off value →  127 Switch-on value →  127 Failure mode →  128 Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Relay output function –...
  • Page 127 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Assign limit In the Relay output function Select process variable for limit • Mass flow Mass flow parameter, the Limit option is function. • Volume flow selected.
  • Page 128: 10.5.11 Configuring The Local Display

    Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting interface / User entry Switch-on delay In the Relay output function Define delay for the switch-on 0.0 to 100.0 s 0.0 s parameter, the Limit option is of status output.
  • Page 129 Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Format display A local display is provided. Select how measured values • 1 value, max. size 1 value, max. size are shown on the display.
  • Page 130 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 1 display A local display is provided. Select the measured value that • Mass flow Mass flow is shown on the local display. • Volume flow •...
  • Page 131 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Current output 1 • Current output 2 • Current output 3 • Pressure 0% bargraph value 1 A local display is provided. Enter 0% value for bar graph...
  • Page 132 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 2 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •...
  • Page 133 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation...
  • Page 134 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 3 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •...
  • Page 135 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation...
  • Page 136 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry 100% bargraph value 3 A selection was made in the Enter 100% value for bar Signed floating-point Value 3 display parameter. graph display. number...
  • Page 137 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry Value 4 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •...
  • Page 138 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation...
  • Page 139: 10.5.12 Configuring The Low Flow Cut Off

    Proline Promass F 300 EtherNet/IP Commissioning 10.5.12 Configuring the low flow cut off The Low flow cut off wizard systematically guides the user through all the parameters that must be set to configure low flow cut off. Navigation "Setup" menu → Low flow cut off ‣...
  • Page 140: 10.5.13 Configuring The Partial Filled Pipe

    Commissioning Proline Promass F 300 EtherNet/IP 10.5.13 Configuring the partial filled pipe detection The Partial filled pipe detection wizard guides you systematically through all parameters that have to be set for configuring the monitoring of the pipe filling. Navigation "Setup" menu → Partially filled pipe detection ‣...
  • Page 141: Advanced Settings

    Proline Promass F 300 EtherNet/IP Commissioning 10.6 Advanced settings The Advanced setup submenu together with its submenus contains parameters for specific settings. Navigation to the "Advanced setup" submenu X X X X X X X 20.50 0104-1 Main menu Display language English Display/operat.
  • Page 142: Using The Parameter To Enter The Access Code

    Commissioning Proline Promass F 300 EtherNet/IP ‣ Totalizer 1 to n →  144 ‣ Display →  147 ‣ WLAN settings →  158 ‣ Concentration ‣ Heartbeat setup ‣ Configuration backup →  160 ‣ →  161 Administration 10.6.1...
  • Page 143: Carrying Out A Sensor Adjustment

    Proline Promass F 300 EtherNet/IP Commissioning Linear expansion coefficient →  143 Square expansion coefficient →  143 Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Corrected volume flow calculation – Select reference density for •...
  • Page 144: Configuring The Totalizer

    Commissioning Proline Promass F 300 EtherNet/IP Navigation "Setup" menu → Advanced setup → Sensor adjustment ‣ Sensor adjustment Installation direction →  144 ‣ →  144 Zero point adjustment Parameter overview with brief description Parameter Description Selection Factory setting...
  • Page 145 Proline Promass F 300 EtherNet/IP Commissioning Navigation "Setup" menu → Advanced setup → Totalizer 1 to n ‣ Totalizer 1 to n Assign process variable →  145 →  145 Unit totalizer 1 to n Totalizer operation mode →  146 Failure mode →...
  • Page 146 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection Factory setting Totalizer operation mode One of the following options is Select totalizer calculation • Net flow total Net flow total selected in the Assign process mode. • Forward flow total variable parameter •...
  • Page 147: Carrying Out Additional Display Configurations

    Proline Promass F 300 EtherNet/IP Commissioning 10.6.5 Carrying out additional display configurations In the Display submenu you can set all the parameters associated with the configuration of the local display. Navigation "Setup" menu → Advanced setup → Display ‣ Display Format display →...
  • Page 148 Commissioning Proline Promass F 300 EtherNet/IP Separator →  158 Backlight →  158...
  • Page 149 Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Format display A local display is provided. Select how measured values • 1 value, max. size 1 value, max. size are shown on the display.
  • Page 150 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 1 display A local display is provided. Select the measured value that • Mass flow Mass flow is shown on the local display. • Volume flow •...
  • Page 151 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Current output 1 • Current output 2 • Current output 3 • Pressure 0% bargraph value 1 A local display is provided. Enter 0% value for bar graph...
  • Page 152 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 2 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •...
  • Page 153 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation...
  • Page 154 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 3 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •...
  • Page 155 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation...
  • Page 156 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Value 4 display A local display is provided. Select the measured value that • None None is shown on the local display. • Mass flow • Volume flow •...
  • Page 157 Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry • Oscillation amplitude 1 • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation...
  • Page 158: Wlan Configuration

    Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry Header A local display is provided. Select header contents on local • Device tag Device tag display. • Free text Header text In the Header parameter, the Enter display header text.
  • Page 159 Proline Promass F 300 EtherNet/IP Commissioning WLAN IP address →  159 WLAN passphrase →  159 Assign SSID name →  159 SSID name →  160 Connection state →  160 Received signal strength →  160 Parameter overview with brief description...
  • Page 160: Configuration Management

    Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry / User interface SSID name • The User-defined option is Enter the user-defined SSID Max. 32-digit EH_device selected in the Assign SSID name (max. 32 characters). character string designation_last 7 name parameter.
  • Page 161: Using Parameters For Device Administration

    Proline Promass F 300 EtherNet/IP Commissioning Parameter Description User interface / Selection Factory setting Configuration management Select action for managing the device data in • Cancel Cancel the HistoROM backup. • Execute backup • Restore • Compare • Clear backup data Backup state Shows the current status of data saving or •...
  • Page 162 Commissioning Proline Promass F 300 EtherNet/IP ‣ Reset access code →  162 Device reset →  163 Using the parameter to define the access code Navigation "Setup" menu → Advanced setup → Administration → Define access code ‣ Define access code Define access code →...
  • Page 163: Simulation

    Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Description User interface / User entry Factory setting Operating time Indicates how long the device has been in Days (d), hours (h), minutes – operation. (m) and seconds (s) Reset access code Reset access code to factory settings.
  • Page 164 Commissioning Proline Promass F 300 EtherNet/IP Value current input 1 to n →  166 Current output 1 to n simulation →  166 Value current output 1 to n →  166 Frequency output simulation 1 to n →  166 Frequency value 1 to n →...
  • Page 165 Proline Promass F 300 EtherNet/IP Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Assign simulation process variable – Select a process variable for • Off the simulation process that is • Mass flow activated.
  • Page 166 Commissioning Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry / User interface Status input simulation – Switch simulation of the status • Off input on and off. • On Input signal level In the Status input simulation Select the signal level for the •...
  • Page 167: Protecting Settings From Unauthorized

    Proline Promass F 300 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting entry / User interface Device alarm simulation – Switch the device alarm on and • Off off. • On Diagnostic event category – Select a diagnostic event • Sensor Process category.
  • Page 168 A reset code must be entered for this purpose. The user-specific access code can then be defined again afterwards. Via Web browser, FieldCare, DeviceCare (via CDI-RJ45 service interface), fieldbus For a reset code, contact your Endress+Hauser service organization. 1. Navigate to the Reset access code parameter (→  163).
  • Page 169: Write Protection Via Write Protection

    Proline Promass F 300 EtherNet/IP Commissioning 2. Enter the reset code.  The access code has been reset to the factory setting 0000. It can be redefined →  167. 10.8.2 Write protection via write protection switch Unlike parameter write protection via a user-specific access code, this allows write access to the entire operating menu - except for the "Contrast display"...
  • Page 170: Operation

    Operation Proline Promass F 300 EtherNet/IP Operation 11.1 Reading the device locking status Device active write protection: Locking status parameter Operation → Locking status Function scope of the "Locking status" parameter Options Description None The access status displayed in the Access status parameter applies →  64. Only appears on local display.
  • Page 171: Measured Variables" Submenu

    Proline Promass F 300 EtherNet/IP Operation ‣ Output values →  175 ‣ Totalizer →  173 11.4.1 "Measured variables" submenu The Measured variables submenu contains all the parameters needed to display the current measured values for each process variable.
  • Page 172 Operation Proline Promass F 300 EtherNet/IP Parameter overview with brief description Parameter Prerequisite Description User interface Mass flow – Displays the mass flow currently Signed floating-point measured. number Dependency The unit is taken from the Mass flow unit parameter (→  102).
  • Page 173: Totalizer" Submenu

    Proline Promass F 300 EtherNet/IP Operation Parameter Prerequisite Description User interface Target mass flow With the following conditions: Displays the target fluid mass flow Signed floating-point • Order code for "Application package", currently measured. number option ED "Concentration" Dependency • The WT-% option or the User conc.
  • Page 174 Operation Proline Promass F 300 EtherNet/IP Navigation "Diagnostics" menu → Measured values → Input values ‣ Input values ‣ Current input 1 to n →  174 ‣ →  174 Status input 1 to n Input values of current input The Current input 1 to n submenu contains all the parameters needed to display the current measured values for every current input.
  • Page 175: Output Values

    Proline Promass F 300 EtherNet/IP Operation Parameter overview with brief description Parameter Description User interface Value status input Shows the current input signal level. • High • Low 11.4.4 Output values The Output values submenu contains all the parameters needed to display the current measured values for every output.
  • Page 176 Operation Proline Promass F 300 EtherNet/IP Output values for pulse/frequency/switch output The Pulse/frequency/switch output 1 to n submenu contains all the parameters needed to display the current measured values for every pulse/frequency/switch output. Navigation "Diagnostics" menu → Measured values → Output values → Pulse/frequency/switch output 1 to n ‣...
  • Page 177: Adapting The Measuring Device To The Process

    Proline Promass F 300 EtherNet/IP Operation Parameter overview with brief description Parameter Description User interface Switch status Shows the current relay switch status. • Open • Closed Switch cycles Shows number of all performed switch cycles. Positive integer Max. switch cycles number Shows the maximal number of guaranteed switch cycles.
  • Page 178: Function Scope Of The "Control Totalizer" Parameter

    Operation Proline Promass F 300 EtherNet/IP Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Control Totalizer 1 to n One of the following options is Control totalizer value. • Totalize Totalize selected in the Assign process •...
  • Page 179: Showing Data Logging

    Proline Promass F 300 EtherNet/IP Operation 11.7 Showing data logging The Extended HistoROM application package must be enabled in the device (order option) for the Data logging submenu to appear. This contains all the parameters for the measured value history.
  • Page 180 Operation Proline Promass F 300 EtherNet/IP Logging delay →  183 Data logging control →  183 Data logging status →  183 Entire logging duration →  183 ‣ Display channel 1 ‣ Display channel 2 ‣ Display channel 3 ‣...
  • Page 181 Proline Promass F 300 EtherNet/IP Operation Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Assign channel 1 The Extended HistoROM Assign a process variable to • Off application package is logging channel. • Mass flow available.
  • Page 182 Operation Proline Promass F 300 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry / User interface • Frequency fluctuation 0 • Frequency fluctuation 1 • Oscillation damping 0 • Oscillation damping 1 • Oscillation damping fluctuation 0 • Oscillation damping fluctuation 1 •...
  • Page 183 Proline Promass F 300 EtherNet/IP Operation Parameter Prerequisite Description Selection / User Factory setting entry / User interface Logging delay In the Data logging Enter the time delay for 0 to 999 h parameter, the Not measured value logging. overwriting option is selected. Data logging control...
  • Page 184: Diagnostics And Troubleshooting

    Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.1 General troubleshooting For local display Error Possible causes Solution Local display dark and no output Supply voltage does not match the Apply the correct supply voltage . signals value indicated on the nameplate.
  • Page 185 Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting For output signals Error Possible causes Solution Signal output outside the valid Main electronics module is Order spare part →  217. range defective. Device shows correct value on local Configuration error...
  • Page 186 Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Error Possible causes Solution Apart from the active network • Make sure that no other network connection to the measuring device, connections are established by other network connections are also the computer (also no WLAN) being used.
  • Page 187: Diagnostic Information Via Light Emitting

    Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Error Possible causes Solution Operation with FieldCare or Firewall of computer or network is Depending on the settings of the DeviceCare via CDI-RJ45 service preventing communication firewall used on the computer or in...
  • Page 188 Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Color Meaning The EtherNet/IP address of the device has been assigned twice. Flashing red EtherNet/IP connection is in the "time out" mode. Flashing red/green The device restarts/self-test. Port 1 active: Not connected or no connection established.
  • Page 189: Diagnostic Information On Local Display

    Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.3 Diagnostic information on local display 12.3.1 Diagnostic message Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the operational display. Operational display in alarm condition...
  • Page 190 Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic behavior Symbol Meaning Alarm • Measurement is interrupted. • Signal outputs and totalizers assume the defined alarm condition. • A diagnostic message is generated. Warning Measurement is resumed. The signal outputs and totalizers are not affected. A diagnostic message is generated.
  • Page 191: Calling Up Remedial Measures

    Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.3.2 Calling up remedial measures X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2...
  • Page 192: Diagnostic Information In The Web Browser

    Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP 12.4 Diagnostic information in the Web browser 12.4.1 Diagnostic options Any faults detected by the measuring device are displayed in the Web browser on the home page once the user has logged on.
  • Page 193: Calling Up Remedy Information

    Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.4.2 Calling up remedy information Remedy information is provided for every diagnostic event to ensure that problems can be rectified quickly. These measures are displayed in red along with the diagnostic event and the related diagnostic information.
  • Page 194: Calling Up Remedy Information

    Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Diagnostic code Diagnostic Diagnostic Status signal Short text behavior number ↓ ↓ ↓ Example Process limit A0013962 A0013958 NAMUR 3-digit number NE 107 12.5.2 Calling up remedy information Remedy information is provided for every diagnostic event to ensure that problems can be rectified quickly: •...
  • Page 195: Adapting The Diagnostic Information

    Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.7 Adapting the diagnostic information 12.7.1 Adapting the diagnostic behavior Each item of diagnostic information is assigned a specific diagnostic behavior at the factory. The user can change this assignment for specific diagnostic information in the Diagnostic behavior submenu.
  • Page 196 Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 062 Sensor connection faulty 1. Check or replace sensor • 0x10000DB electronic module (ISEM) • 0x10000DC 2. If available: Check connection •...
  • Page 197: Diagnostic Of Electronic

    Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 144 Measuring error too high 1. Check or change sensor 0x10001C7 2. Check process conditions Status signal Diagnostic behavior [from the...
  • Page 198 Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 262 Sensor electronic connection faulty 1. Check or replace connection 0x1000149 cable between sensor electronic module (ISEM) and main Status signal...
  • Page 199 Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 276 I/O module 1 to n faulty 1. Restart device • 0x100007B 2. Change I/O module • 0x1000081 Status signal Diagnostic behavior...
  • Page 200 Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 372 Sensor electronic (ISEM) faulty 1. Restart device • 0x10000A1 2. Check if failure recurs • 0x10000C7 3. Replace sensor electronic module •...
  • Page 201: Diagnostic Of Configuration

    Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 383 Memory content 1. Restart device 0x100016E 2. Delete T-DAT via ' R eset device' parameter Status signal 3. Replace T-DAT...
  • Page 202 Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 412 Processing download Download active, please wait 0x2000204 Status signal Diagnostic behavior Warning Diagnostic information Remedy instructions Coding of diagnostic information (hex)
  • Page 203 Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 443 Pulse output 1 to n 1. Check process • 0x800008C 2. Check pulse output settings • 0x8000121 Status signal Diagnostic behavior...
  • Page 204 Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 491 Current output 1 to n simulation Deactivate simulation 0x200000E Status signal Diagnostic behavior Warning Diagnostic information Remedy instructions Coding of diagnostic...
  • Page 205: Diagnostic Of Process

    Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 520 I/O 1 to n hardware configuration invalid 1. Check I/O hardware 0x1000276 configuration 2. Replace wrong I/O module Status signal 3.
  • Page 206 Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 830 Sensor temperature too high Reduce ambient temp. around the 0x80000C0 sensor housing Status signal Diagnostic behavior [from the Warning factory] Diagnostic behavior can be changed.
  • Page 207 Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 834 Process temperature too high Reduce process temperature 0x80000C5 Status signal Diagnostic behavior [from the Warning factory] Diagnostic behavior can be changed.
  • Page 208 Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 910 Tubes not oscillating 1. Check electronic 0x1000050 2. Inspect sensor Status signal Diagnostic behavior Alarm Diagnostic information Remedy instructions Coding of diagnostic...
  • Page 209: Pending Diagnostic Events

    Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 943 API pressure out of specification 1. Check process pressure with 0x800037F selected API commodity group 2. Check API related parameters...
  • Page 210: 12.10 Diagnostic List

    Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP Operating time from restart →  210 Operating time →  210 Parameter overview with brief description Parameter Prerequisite Description User interface Actual diagnostics A diagnostic event has occurred. Shows the current occured diagnostic...
  • Page 211: 12.11 Event Logbook

    Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting 12.11 Event logbook 12.11.1 Reading out the event logbook A chronological overview of the event messages that have occurred is provided in the Events list submenu. Navigation path Diagnostics menu → Event logbook submenu → Event list / ../Eventlist...
  • Page 212: 12.11.3 Overview Of Information Events

    Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP 12.11.3 Overview of information events Unlike a diagnostic event, an information event is displayed in the event logbook only and not in the diagnostic list. Info number Info name I1000 --------(Device ok)
  • Page 213: 12.12 Resetting The Measuring Device

    Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting Info number Info name I1514 Upload started I1515 Upload finished I1618 I/O module 2 replaced I1619 I/O module 3 replaced I1621 I/O module 4 replaced I1622 Calibration changed I1624 Reset all totalizers...
  • Page 214: 12.13 Device Information

    Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP 12.13 Device information The Device information submenu contains all parameters that display different information for device identification. Navigation "Diagnostics" menu → Device information ‣ Device information Device tag →  214 Serial number →...
  • Page 215: 12.14 Firmware History

    "Manufacturer' s information" document. The manufacturer' s information is available: • In the Download Area of the Endress+Hauser web site: www.endress.com → Downloads • Specify the following details: –...
  • Page 216: Maintenance

    →  238. 13.2 Measuring and test equipment Endress+Hauser offers a wide variety of measuring and test equipment, such as W@M or device tests. Your Endress+Hauser Sales Center can provide detailed information on the services. List of some of the measuring and testing equipment: →  219 13.3...
  • Page 217: Repairs

    • The measuring devices have a modular design. • Spare parts are grouped into logical kits with the associated Installation Instructions. • Repairs are carried out by Endress+Hauser Service or by appropriately trained customers. • Certified devices can only be converted to other certified devices by Endress+Hauser Service or at the factory.
  • Page 218: Disposal

    Repairs Proline Promass F 300 EtherNet/IP 14.5 Disposal 14.5.1 Removing the measuring device 1. Switch off the device. WARNING Danger to persons from process conditions. ‣ Beware of hazardous process conditions such as pressure in the measuring device, high temperatures or aggressive fluids.
  • Page 219: Accessories

    Various accessories, which can be ordered with the device or subsequently from Endress +Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
  • Page 220: For The Sensor

    Is used to stabilize the temperature of the fluids in the sensor. Water, water vapor and other non-corrosive liquids are permitted for use as fluids. If using oil as a heating medium, please consult with Endress+Hauser. Heating jackets cannot be used with sensors fitted with a rupture disk.
  • Page 221: System Components

     For details, see Operating Instructions BA00027S and BA00059S DeviceCare Tool for connecting and configuring Endress+Hauser field devices.  For details, see Innovation brochure IN01047S 15.4 System components...
  • Page 222: Technical Data

    Technical data Proline Promass F 300 EtherNet/IP Technical data 16.1 Application The measuring device is suitable for flow measurement of liquids and gases only. Depending on the version ordered, the measuring device can also measure potentially explosive, flammable, poisonous and oxidizing media.
  • Page 223: Input

    Proline Promass F 300 EtherNet/IP Technical data 16.3 Input Measured variable Direct measured variables • Mass flow • Density • Temperature Calculated measured variables • Volume flow • Corrected volume flow • Reference density Measuring range Measuring ranges for liquids Measuring range full scale values ...
  • Page 224 • Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure measuring device for absolute pressure, e.g. Cerabar M or Cerabar S) •...
  • Page 225 Proline Promass F 300 EtherNet/IP Technical data Current input 0/4 to 20 mA Current input 0/4 to 20 mA (active/passive) Current span • 4 to 20 mA (active) • 0/4 to 20 mA (passive) Resolution 1 µA Voltage drop Typically: 0.6 to 2 V for 3.6 to 22 mA (passive) Maximum input voltage ≤...
  • Page 226: Output

    Technical data Proline Promass F 300 EtherNet/IP 16.4 Output Output signal EtherNet/IP Standards In accordance with IEEE 802.3 Current output 0/4 to 20 mA Current output 0/4 to 20 mA Maximum output values 22.5 mA Current span Can be set to: •...
  • Page 227 Proline Promass F 300 EtherNet/IP Technical data Maximum output current 22.5 mA (active) Open-circuit voltage DC 28.8 V (active) Pulse width Adjustable: 0.05 to 2 000 ms Maximum pulse rate 10 000 Impulse/s Pulse value Adjustable Assignable measured • Mass flow variables •...
  • Page 228 Technical data Proline Promass F 300 EtherNet/IP Relay output Function Switch output Version Relay output, galvanically isolated Switching behavior Can be set to: • NO (normally open), factory setting • NC (normally closed) Maximum switching • DC 30 V, 0.1 A capacity (passive) •...
  • Page 229 Proline Promass F 300 EtherNet/IP Technical data Current output 0/4 to 20 mA 4 to 20 mA Failure mode Choose from: • 4 to 20 mA in accordance with NAMUR recommendation NE 43 • 4 to 20 mA in accordance with US •...
  • Page 230 Technical data Proline Promass F 300 EtherNet/IP Interface/protocol • Via digital communication: EtherNet/IP • Via service interface – CDI-RJ45 service interface – WLAN interface Plain text display With information on cause and remedial measures Web server Plain text display With information on cause and remedial measures...
  • Page 231: Power Supply

    Proline Promass F 300 EtherNet/IP Technical data Configuration of the device • DIP switches on the electronics module for IP addressing (last octet) address • DHCP • Manufacturer-specific software (FieldCare) • Add-on Profile Level 3 for Rockwell Automation control systems •...
  • Page 232: Performance Characteristics

    Technical data Proline Promass F 300 EtherNet/IP terminals Spring-loaded terminals: Suitable for strands and strands with ferrules. Conductor cross-section 0.2 to 2.5 mm (24 to 12 AWG). Cable entries • Cable gland: M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in) •...
  • Page 233 Proline Promass F 300 EtherNet/IP Technical data Density (cryogenic liquids) Order code for "Measuring tube material", option LA ±0.05 g/cm³ Temperature ±0.5 °C ± 0.005 · T °C (±0.9 °F ± 0.003 · (T – 32) °F) Zero point stability...
  • Page 234 Technical data Proline Promass F 300 EtherNet/IP SI units 1:10 1:20 1:50 1:100 1:500 [mm] [kg/h] [kg/h] [kg/h] [kg/h] [kg/h] [kg/h] 2 000 6 500 18 000 1 800 45 000 4 500 2 250 70 000 7 000 3 500...
  • Page 235 Proline Promass F 300 EtherNet/IP Technical data Base repeatability Design fundamentals →  237 Mass flow and volume flow (liquids) ±0.025 % o.r. (PremiumCal, for mass flow) ±0.05 % o.r. Mass flow (cryogenic liquids) Order code for "Measuring tube material", option LA ±0.175 % % o.r.
  • Page 236 Technical data Proline Promass F 300 EtherNet/IP Wide-range density specification (special density calibration) If the process temperature is outside the valid range (→  232) the measured error is ±0.00005 g/cm /°C (±0.000025 g/cm /°F) [kg/m ] [°C] [° ] F...
  • Page 237: Installation

    Proline Promass F 300 EtherNet/IP Technical data Design fundamentals o.r. = of reading, o.f.s. = of full scale value BaseAccu = base accuracy in % o.r., BaseRepeat = base repeatability in % o.r. MeasValue = measured value; ZeroPoint = zero point stability...
  • Page 238: Process

    Technical data Proline Promass F 300 EtherNet/IP Temperature tables Observe the interdependencies between the permitted ambient and fluid temperatures when operating the device in hazardous areas. For detailed information on the temperature tables, see the separate document entitled "Safety Instructions" (XA) for the device.
  • Page 239 Proline Promass F 300 EtherNet/IP Technical data High-temperature version –50 to +350 °C (–58 to +662 °F) For nominal diameters DN 25 (1"), DN 50 (2") and DN 80 (3") Order code for "Measuring tube mat., wetted surface", option TT, Low-temperature version –196 to +150 °C (–320 to +302 °F)
  • Page 240 Technical data Proline Promass F 300 EtherNet/IP Density 0 to 5 000 kg/m (0 to 312 lb/cf) Pressure-temperature An overview of the pressure-temperature ratings for the process connections is ratings provided in the "Technical Information" document Secondary containment For the Standard version with the temperature range –50 to +150 °C (–58 to +302 °F), the sensor housing is filled with dry nitrogen gas and protects the electronics and mechanics inside.
  • Page 241 Proline Promass F 300 EtherNet/IP Technical data If the sensor is to be purged with gas (gas detection), it should be equipped with purge connections. Do not open the purge connections unless the containment can be filled immediately with a dry, inert gas. Use only low pressure to purge. Maximum pressure: 5 bar (72.5 psi).
  • Page 242: 16.10 Mechanical Construction

    Technical data Proline Promass F 300 EtherNet/IP 16.10 Mechanical construction Design, dimensions For the dimensions and installation lengths of the device, see the "Technical Information" document, "Mechanical construction" section. Weight All values (weight exclusive of packaging material) refer to devices with EN/DIN PN 40 flanges.
  • Page 243 Proline Promass F 300 EtherNet/IP Technical data Materials Transmitter housing Order code for "Housing": • Option A "Aluminum, coated": aluminum, AlSi10Mg, coated • Option B "Stainless, hygienic": stainless steel, 1.4404 (316L) • Option L "Cast, stainless": cast, stainless steel, 1.4409 (CF3M) similar to 316L Window material Order code for "Housing":...
  • Page 244 Technical data Proline Promass F 300 EtherNet/IP Order code for "Housing", option L "Cast, stainless" The various cable entries are suitable for hazardous and non-hazardous areas. Cable entry/cable gland Material Cable gland M20 × 1.5 Stainless steel, 1.4404 (316L) Adapter for cable entry with internal thread G ½"...
  • Page 245 Proline Promass F 300 EtherNet/IP Technical data High-temperature version Flanges according to EN 1092-1 (DIN2501) / according to ASME B 16.5 / as per JIS B2220: – Stainless steel, 1.4404 (F316/F316L) – Alloy C22, 2.4602 (UNS N06022) List of all available process connections →  245...
  • Page 246: 16.11 Operability

    Technical data Proline Promass F 300 EtherNet/IP 16.11 Operability Languages Can be operated in the following languages: • Via local operation English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese, Japanese, Korean, Bahasa (Indonesian), Vietnamese, Czech, Swedish • Via Web browser...
  • Page 247 Proline Promass F 300 EtherNet/IP Technical data Via remote display and operating module DKX001 The remote display and operating module DKX001 is available as an optional extra →  219. • The remote display and operating module DKX001 is only available for the following housing versions, order code for "Housing":...
  • Page 248 Technical data Proline Promass F 300 EtherNet/IP Dimensions Information on the dimensions: "Mechanical construction" section of the "Technical Information" document. Remote operation →  73 Service interface →  74 Supported operating tools Different operating tools can be used for local or remote access to the measuring device.
  • Page 249 Proline Promass F 300 EtherNet/IP Technical data Supported functions Data exchange between the operating unit (such as a notebook for example) and the measuring device: – Upload the configuration from the measuring device (XML format, configuration backup) – Save the configuration to the measuring device (XML format, restore configuration) –...
  • Page 250 Technical data Proline Promass F 300 EtherNet/IP Data backup Automatic • The most important device data (sensor and transmitter) are automatically saved in the DAT modules • If the transmitter or measuring device is replaced: once the T-DAT containing the...
  • Page 251: 16.12 Certificates And Approvals

    EU Directives. These are listed in the corresponding EU Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. C-Tick symbol The measuring system meets the EMC requirements of the "Australian Communications and Media Authority (ACMA)".
  • Page 252 For detailed information on the radio approval, see the Special Documentation →  256 Additional certification Marine approval Currently valid certificates are available: • In the Download Area of the Endress+Hauser Internet site: www.endress.com → Downloads • Specify the following details: Search area: Approval & Certificates→ Marine CRN approval Some device versions have CRN approval.
  • Page 253: 16.13 Application Packages

    The application packages can be ordered with the device or subsequently from Endress+Hauser. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
  • Page 254 Technical data Proline Promass F 300 EtherNet/IP Diagnostics functions Package Description Extended HistoROM Comprises extended functions concerning the event log and the activation of the measured value memory. Event log: Memory volume is extended from 20 message entries (standard version) to up to 100 entries.
  • Page 255: 16.14 Accessories

    • The W@M Device Viewer : Enter the serial number from the nameplate (www.endress.com/deviceviewer) • The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2-D matrix code (QR code) on the nameplate. Standard documentation...
  • Page 256 Technical data Proline Promass F 300 EtherNet/IP Device-dependent Safety instructions additional documentation Safety instructions for electrical equipment for hazardous areas. Contents Documentation code ATEX/IECEx Ex d/Ex de XA01405D ATEX/IECEx Ex ec XA01439D cCSAus XP XA01373D cCSAus Ex d/ Ex de...
  • Page 257: Index

    Proline Promass F 300 EtherNet/IP Index Index 0 … 9 Explanation ......61 Current consumption .
  • Page 258 Index Proline Promass F 300 EtherNet/IP Display area Field of application For operational display ..... 55 Residual risks ......11 In the navigation view .
  • Page 259 Proline Promass F 300 EtherNet/IP Index System pressure ......26 Mounting dimensions Thermal insulation ......26 see Installation dimensions Vibrations .
  • Page 260 Index Proline Promass F 300 EtherNet/IP Current output ......109 Current output (Wizard) ....109 Radio approval .
  • Page 261 Proline Promass F 300 EtherNet/IP Index Sensor adjustment ..... . . 143 Value current output 1 to n ....175 Simulation .
  • Page 262 Index Proline Promass F 300 EtherNet/IP Troubleshooting General ....... 184 TSE/BSE certificate of suitability .
  • Page 264 The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in ef- fect. Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect. Contact information is subject to change.