Endress+Hauser HART Levelflex FMP56 Operating Instructions Manual
Endress+Hauser HART Levelflex FMP56 Operating Instructions Manual

Endress+Hauser HART Levelflex FMP56 Operating Instructions Manual

Guided level-radar level measurement in bulk solids
Hide thumbs Also See for HART Levelflex FMP56:
Table of Contents

Advertisement

Quick Links

Operating Instructions
Levelflex FMP56, FMP57
Guided Level-Radar
Level measurement in bulk solids
BA01004F/00/EN/10.10
71120867
Valid as of version
01.01.zz

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser HART Levelflex FMP56

  • Page 1 Operating Instructions Levelflex FMP56, FMP57 Guided Level-Radar Level measurement in bulk solids BA01004F/00/EN/10.10 71120867 Valid as of version 01.01.zz...
  • Page 3: Table Of Contents

    ......25 HART device variables and measuring values ..63 Endress+Hauser...
  • Page 4 Disposal ......82 Overview of the operating menu ..83 Endress+Hauser...
  • Page 5: Important Document Information

    The document types listed are available: • On the CD supplied with the device • In the Download Area of the Endress+Hauser Internet site: www.endress.com ® Download 1.1.3 Safety Instructions (XA) for Levelflex FMP56, FMP57 Depending on the approval, the following Safety Instructions (XA) are supplied with the instrument.
  • Page 6: Document Conventions

    A terminal which must be connected to ground prior to establishing any other connections. A0011199 Equipotential connection A connection that has to be connected to the plant grounding system: This may be a potential equalization A0011201 line or a star grounding system depending on national or company codes of practice. Endress+Hauser...
  • Page 7: Tool Symbols

    A0013562 1.2.5 Symbols and notation in graphics Symbol Meaning 1,2,3 ... Item numbers A, B, C, ... Views A-A, B-B, C-C, ... Sections Hazardous area Indicates a hazardous area. A0011187 Safe area (non-hazardous area) Indicates a non-hazardous location. A0011188 Endress+Hauser...
  • Page 8: Basic Safety Instructions

    The manufacturer is not liable for damage caused by improper or non-designated use. Verification for borderline cases: For special measured materials and cleaning agents, Endress+Hauser is glad to provide assistance ► in verifying the corrosion resistance of wetted materials, but does not accept any warranty or liability.
  • Page 9: Operational Safety

    It fulfills general safety requirements and legal requirements. It also conforms to the EC directives listed in the device-specific EC declaration of conformity. Endress+Hauser confirms this fact by applying the CE mark. Endress+Hauser...
  • Page 10: Product Description

    Product description Levelflex FMP56, FMP57 Product description Product design 3.1.1 Compact device Levelflex A0012470 å 1 Design of the Levelflex Electronics housing Process connection (here as an example: flange) Rope probe End-of-probe weight Rod probe Endress+Hauser...
  • Page 11: Electronics Housing

    TRI CLAMP Registered trademark of Alfa Laval Inc., Kenosha, USA Patents This product may be protected by at least one of the following patents. Further patents are pending. US Patents EP Patents 5.827.985 5.884.231 5.973.637 6.087.978 955 527 6.140.940 Endress+Hauser...
  • Page 12 Product description Levelflex FMP56, FMP57 US Patents EP Patents 6.481.276 6.512.358 1 301 914 6.559.657 1 020 735 6.640.628 6.691.570 6.847.214 7.441.454 7.477.059 1 389 337 Endress+Hauser...
  • Page 13: Incoming Acceptance And Product

    316L,316,Alloy C22 Z-65.16-354 FISCO Ex d DeviceID: 452B481005-A91234010AB XA500F-- ex works FW: 01.00.00 Dev.Rev.: 1 Ex i if modification see sep. label Date: 2010-03 250002796-A A0013696 A0014038 Do the nameplate data match the ordering information on the delivery note? Endress+Hauser...
  • Page 14: Product Identification

    Are the CD-ROMs (product documentation, operating tool) and documentation present? If required (see nameplate): Are the Safety Instructions (XA) present? If one of the conditions does not comply, contact your Endress+Hauser distributor. Product identification The following options are available for identification of the measuring device: •...
  • Page 15: Nameplate

    Product structure FMP56, FMP57 This overview does not mark options which are mutually exclusive. Option with * = in preparation Approval: 56 57 Non-hazardous area ATEX II 1G Ex ia IIC T6 ATEX II 1/2G Ex ia IIC T6 Endress+Hauser...
  • Page 16 Special version, TSP-no. to be sepc. Display, Operation: 56 57 W/o, via communication SD02 4-line, push buttons + data backup function Special version, TSP-no. to be sepc. Housing: 56 57 GT19 dual compartment, Plastics PBT GT18 dual compartment, 316L Endress+Hauser...
  • Page 17 2" 150lbs RF, 316/316L flange ANSI B16.5 3" 150lbs RF, 316/316L flange ANSI B16.5 4" 150lbs RF, 316/316L flange ANSI B16.5 6" 150lbs RF, 316/316L flange ANSI B16.5 8" 150lbs RF, 316/316L flange ANSI B16.5 DN50 PN10/16 B1, 316L flange EN1092-1 Endress+Hauser...
  • Page 18 Special version, TSP-no. to be sepc. Service: (Multiple options can be selected) 56 57 Customized parametrization HART W/o Tooling DVD (FieldCare setup) Special version, TSP-no. to be sepc. Additional Approval: (Multiple options can be selected) 56 57 Special version, TSP-no. to be sepc. Endress+Hauser...
  • Page 19 56 57 Mounting kit, insulated, rope Special version, TSP-no. to be sepc. Firmware Version: 56 57 01.01.zz, HART, DevRev02 01.00.zz, HART, DevRev01 Tagging: (Multiple options can be selected) 56 57 Tagging (TAG), see additional spec. Bus address, see additional spec. Endress+Hauser...
  • Page 20: Storage, Transport

    Risk of injury if the hosuing breaks away! Transport the measuring device to the measuring point in its original packaging or at the process ► connection. Comply with the safety instructions, transport conditions for devices over 18kg (39.6lbs). ► A0013920 A0014264 Endress+Hauser...
  • Page 21: Mounting

    å 4 Housing GT18 (316L); Dimensions in mm (in) 78 (3.07) 90 (3.54) A0015133 å 5 Housing GT19 (Plastics PBT); Dimensions in mm (in) 90 (3.54) 78 (3.07) A0015134 å 6 Housing GT20 (Alu coated); Dimensions in mm (in) Endress+Hauser...
  • Page 22: Fmp56: Dimensions Of Process Connection And Probe

    Mounting bracket for probe design "Sensor remote" Feature 600) Thread ISO228 G3/4 or ANSI MNPT3/4 (Feature 100) Rope probe 4mm or 1/6" (Feature 060) Rope probe 6mm or 1/4", PA>Steel (Feature 060) LN Length of probe Reference point of the measurement Endress+Hauser...
  • Page 23: Fmp57: Dimensions Of Process Connection And Probe

    Rope probe 6mm or 1/4" (Feature 060) Rope probe 8mm or 1/3", PA>Steel (Feature 060) Rope probe 4mm or 1/6" (Feature 060) Rope probe 6mm or 1/4", PA>Steel (Feature 060) LN Length of probe Reference point of the measurement Endress+Hauser...
  • Page 24: Mounting Requirements

    300 mm (12") during the entire process. A sporadic contact between the probe weight and the cone of the vessel, however, does not influence the measurement as long as the dielectric constant of the medium is at least DC = 1.8. Endress+Hauser...
  • Page 25: Applications With Restricted Mounting

    – Pipe mounting; diameter: 42 to 60 mm (1-1/4 to 2 inch) • The connection cable has got one straight and one angled plug (90°). Depending on the local conditions the angled plug can be connected at the probe or at the electronics housing. Endress+Hauser...
  • Page 26: Notes On The Mechanical Load Of The Probe

    • The specification for tensile forces contains the safety factor 2 (in addition to the safety factors already taken into account by DIN 1055), which compensates for the normal fluctuation range in pourable bulk solids. Endress+Hauser...
  • Page 27 Observe the tensile strength of the probes. Options for reducing the tensile forces: • Shorten the probe. • If the maximum tensile load is exceeded, check whether it would be possible to use a non-contact Ultrasonic or Level-Radar device. Endress+Hauser...
  • Page 28: Notes On The Process Connection

    For the length of the screwed plug refer to the dimensional drawing: • FMP56: (® ä 22) • FMP57: (® ä 23) Nozzle mounting with flange < ( 6) < Ø < mm (in) < Ø A0015122 Endress+Hauser...
  • Page 29 Approx. flush with the lower edge of the nozzle (± 50 mm/2") Plate Pipe Æ 150 to 180 mm (6 to 7 inch) Nozzle diameter Plate diameter 300 mm (12") 280 mm (11") ³ 400 mm (16") ³ 350 mm (14") Endress+Hauser...
  • Page 30: Securing The Probe

    Securing rod probes • Rod probes must be supported if there is a horizontal flow (e.g. from an agitator) or in the case of strong vibrations. • Rod probes may only be supported at the end of the probe. Endress+Hauser...
  • Page 31: Special Mounting Conditions

    Installation, for example, into a thick concrete ceiling should be made flush with the lower edge. Alternatively, the probe can also be installed into a pipe that must not protrude over the lower edge of the silo ceiling. The pipe should be kept at a minimum length. Installation suggestions see diagram. Endress+Hauser...
  • Page 32 Extension rod / Centering HMP40 (see "Accessories") Note for installations with rod extension/center washer (accesories): Strong dust generation can lead to build-up behind the center washer. This can cause an interference signal. For other installation possibilities please contact Endress+Hauser. Installation from the side mm (in) A0014140 •...
  • Page 33 The insulation may not exceed beyond the points labeled "MAX" in the drawings. A0014653 å 8 Process connection with thread - FMP56, FMP57 Tank insulation Compact device Sensor remote (feature 600) Endress+Hauser...
  • Page 34 Mounting Levelflex FMP56, FMP57 mm (in) A0014654 å 9 Process connection with flange - FMP57 Tank insulation Compact device Sensor remote (feature 600) Endress+Hauser...
  • Page 35: Mounting The Device

    Rod probes of FMP52 can not be shortened as they are coated. Shortening rope probes Rope probes must be shortened if the distance to the container floor or outlet cone is less than 10 mm (0.4 in). Rope probes of FMP52 can not be shortened as they are coated. Endress+Hauser...
  • Page 36: Mounting The Device

    Torque: rope 4 mm (0.16 in): 5 Nm (3.7 lbf ft); rope 6 mm (0.24 in): 15 Nm (11 lbf ft). 6.3.3 Mounting the device Mounting devices with thread A0012528 Devices with mounting thread are screwed into a welding boss or a flange and are usually also secured with these. Endress+Hauser...
  • Page 37 • When installing in metal containers, take care to ensure good metallic contact between the process connection and container. Flange mounting If a seal is used, be sure to use unpainted metal bolts to ensure good electrical contact between probe flange and process flange. Endress+Hauser...
  • Page 38: Mounting The "Sensor Remote" Version

    Lay the cable such that it is not exposed to mechanical stress. Minimum bending radius: 100 ► mm (4"). When connecting the cable: Connect the straight plug before the angled one. Torque for both ► coupling nuts: 6 Nm. Endress+Hauser...
  • Page 39 Open-end wrench 18AF 6 Nm 6 Nm = 100 mm (4”) = 100 mm (4”) 6 Nm 6 Nm A0014794 å 11 Connecting the cable. There are the following possibilities: Angled plug at the probe Angled plug at the electronics housing Endress+Hauser...
  • Page 40: Turning The Transmitter Housing

    Screw the cover of the electronics compartment firmly back onto the transmitter housing. If present (i.e. for devices with Dust-Ex/DIP approval): Tighten the securing clamp again using the Allen key (Torque: 2.5 Nm). Endress+Hauser...
  • Page 41: Post-Installation Check

    • Process pressure (refer to the chapter on "Material load curves" of the "Technical Information" document) • Ambient temperature range • Measuring range Are the measuring point identification and labeling correct (visual inspection)? Is the device adequately protected from precipitation and direct sunlight? Are the securing screw and securing clamp tightened securely? Endress+Hauser...
  • Page 42: Electrical Connection

    Active barrier with power supply (e.g. RN221N): Observe terminal voltage (® ä 45) HART communication resistor (³250 W): Observe maximum load (® ä 46) Connection for Field Communicator 375/475 or Commubox FXA195 Analog display device: Observe maximum load (® ä 46) Observe cable specification (® ä 45) Potential equalization Cable entry Endress+Hauser...
  • Page 43: 2-Wire, 4-20 Ma Hart, 4

    Supply voltage for current output 2 (e.g. RN221N); Obesrve terminal voltage (® ä 46) Analog display device ; observe maximum load Terminal for the potential equalization line This version is also suited for single-channel operation. In this case, current output 1 (terminals 1 and 2) must be used. Endress+Hauser...
  • Page 44: 4-Wire, 4-20 Ma Hart

    (flange or threaded connection) or the external ground terminal. When using the public supply mains, an easily accessible power switch must be installed in the proximity of the device. The power switch must be marked as a disconnector for the device (IEC/EN61010). Endress+Hauser...
  • Page 45: Connection Conditions

    • Integrated overvoltage protection (in preparation); Product structure: Feature 610 "Accessory mounted", option NA "Overvoltage protection". • External overvoltage protection, e.g. Endress+Hauser's HAW562Z. When using the external overvoltage protection HAW562Z in explosion hazardous areas observe the associated Safety Instructions XA015R.
  • Page 46: 4-Wire, 4-20Ma Hart, Active

    Feature 20 "Power Supply, Output", Option A "2-wire; 4-20mA HART" Outputs Terminal voltage Feature 010 - Approval 11.5 to 35 V Non-Ex, Ex nA, CSA GP 11.5 to 32 V Ex ic 11.5 to 30 V Ex ia / IS Endress+Hauser...
  • Page 47: Connecting The Measuring Device

    Before switching on the supply voltage: Connect the potential bonding line to the exterior ground ► terminal. Required tools and accessories: • For instruments with safety pin for the lid: M3 Allen key • Wire stripping pliers • When using stranded wires: Wire end sleeves. Endress+Hauser...
  • Page 48 Rigid conductors or flexible conductors with cable sleeve can directly be inserted and are contacted automatically. To remove cables from the terminal: Press on the groove between the terminals using a flat- tip screwdriver £ 3 mm (0.12 inch) while pulling the cables out of the terminals. Endress+Hauser...
  • Page 49: Post-Connection Check

    Is the terminal assignment correct (® ä 42)? If supply voltage is present: Is the device ready for operation and do values appear on the display module? Are all housing covers installed and firmly tightened? Is the securing clamp tightened correctly? Endress+Hauser...
  • Page 50: Operating Options

    On-site operation options Display module SD02, push buttons; cover must be open for operation Operating options via CDI interface (= Endress+Hauser Common Data Interface) 2.1 Computer with operating tool (FieldCare) 2.2 Commubox FXA291, connected to the CDI interface of the device...
  • Page 51: Remote Operation Via Hart

    Computer with operating tool (e.g. FieldCare, AMS, Simatic PDM) Handheld terminal DXR375/FC375 Field Xpert VIATOR Bluetooth modem with connection cable Transmitter supply unit RMA422 or RN221N (communication resistor included) Connection for Commubox FXA191, FXA195 or handheld terminal DXR375/FC375 In hazardous areas only use certified operating tools! Endress+Hauser...
  • Page 52: The Operating Menu

    Parameter 1 Parameter N Submenu 1 Submenu N Parameter 1 Diagnostics Parameter N Submenu 1 Submenu N Expert Direct access System Sensor Output Communication Application Diagnostics A0012647 å 14 Basic structure of the operating menu; gray: submenus; white: parameters Endress+Hauser...
  • Page 53: Submenus And User Roles

    Locking the menu via the locking switch (hardware locking) The complete operating menu can be locked by the locking switch below the display and operating module. In the locked state most parameter values can be read but not changed. Endress+Hauser...
  • Page 54 (® ä 97) ® Enter access code Enter the previously defined access code. Setup ® Advanced setup To lock the device again: (® ä 97) ® Enter access code Enter a number other than the previously defined access code. Endress+Hauser...
  • Page 55: Display And Operating Module

    Representation of a parameter (here: a parameter with selection list) 3.1 Header containing parameter name and error symbol (if an error is active) 3.2 Selection list; Â marks the current parameter value. Input matrix for numbers Input matrix for alphanumeric and special characters Endress+Hauser...
  • Page 56 Marks display-only parameters which can not be edited. A0011978 Device locked • In front of a parameter name: The device is locked via software and/or hardware. • In the header of the measured value screen: The device is locked via hardware. A0011979 Endress+Hauser...
  • Page 57 Measuring channel 2 A0012107 Status of the measured value Status "Alarm" The measurment is interrupted. The output assumes the defined alarm value. A diagnostic message is generated. A0012102 Status "Warning" The device continues measuring. A diagnostic message is generated. A0012103 Endress+Hauser...
  • Page 58: Navigation And Selection From A List

    • Confirms a changed parameter value. A0011973 "Escape" key combination (press keys simultaneously) Henceforth represented by S + O. • Closes a parameter without accepting the changes. • Quits the current menu layer and returns to the next higher layer. A0012661 Endress+Hauser...
  • Page 59 / ../Format display 0098-1 1 value, max. Bargr. + 1 value 2 values / ../Format display 0098-1 Val. large+ 1 value, max. Bargr. + 1 value 2 values X X X X X X X Val. large+ 10.50 19.00 A0014010-EN Endress+Hauser...
  • Page 60: Entering Numbers

    Meaning Deletes the character left to the cursor. A0011988 Deletes all characters. A0011989 Moves the cursor one step to the left. A0011991 Moves the cursor one step to the right. A0011992 Terminates the editing without accepting the changes. A0011993 Endress+Hauser...
  • Page 61: Entering Text

    Meaning Deletes the character left to the cursor. A0011988 Deletes all characters. A0011989 Moves the cursor one step to the left. A0011991 Moves the cursor one step to the right. A0011992 Terminates the editing without accepting the changes. A0011993 Endress+Hauser...
  • Page 62: Envelope Curve On The Display And Operating Module

    Levelflex FMP56, FMP57 8.3.5 Envelope curve on the display and operating module In order to assess the measuring signal, the envelope curve and - if a mapping has been recorded - the mapping curve can be displayed: (2s) A0014277 Endress+Hauser...
  • Page 63: Device Integration Via The Hart

    Level linearized Secondary device variable (SV) Distance Third device variable (TV) Absolute echo amplitude Fourth device variable (QV) Relative echo amplitude The allocation of the device variables can be changed in the operating menu: Expert ® Communication ® HART output. Endress+Hauser...
  • Page 64: Commissioning

    Input prompt for the access code to unlock software-locked parameters. Parameters affected by the software lock are marked by a padlock in front of the parameter name. After pressing F an input prompt appears. Enter the user defined locking code to unlock the device (® ä 54). Endress+Hauser...
  • Page 65: Setting The Operating Language

    Levelflex FMP56, FMP57 Commissioning 10.4 Setting the operating language 10.4.1 Setting the operating language via the display module A0013637 10.4.2 Setting the language via operating tool (FieldCare) A0013841_300 Endress+Hauser...
  • Page 66: Configuration Of A Level Measurement

    Factory setting of the current outputs for level measurements Current output Allocated measuring 4mA value 20mA value vlaue Level linearized 0% or the corresponding linearized 100% or the corresponding value linearized value Distance Empty calibration for devices with 2 current outputs Endress+Hauser...
  • Page 67: Adjustment Of The Current Outputs

    Setup ® Advanced setup ® Display (® ä 117) 10.8 Protection of the settings against unauthorized changes There are two ways to protect the settings against unauthorized changes: • Via locking switch (hardware locking) (® ä 53) • Via parameter settings (software locking) (® ä 54) Endress+Hauser...
  • Page 68: Trouble Shooting

    (® ä 95). Build-up at the probe. Clean the probe. Diagnostic event F941 or S941 Noise level to high during initialization Enter the Empty calibration again "Echo lost" appears after phase. (® ä 92). switching on the supply voltage. Endress+Hauser...
  • Page 69: Diagnostic Events

    Status symbol (symbol for event level) "Alarm" status The measurement is interrupted. The signal outputs take on the defined alarm condition. A diagnostic message is generated. A0013961 "Warning" status The device continues to measure. A diagnostic message is generated. A0013962 Endress+Hauser...
  • Page 70: Calling Up Remedial Measures

    1. Check process 2. Check current output settings A0013940-EN Event text Status symbol with diagnostics event Event ID for service Operation time of occurrence Remedial measures The user is in the diagnostic message. Press the O key ( symbol). Endress+Hauser...
  • Page 71: List Of Diagnostic Events

    Main electronic failure 1. Emergency operation via display. Alarm 2. Change main electronics. F275 I/O-Modul failure Change I/O module. Alarm F276 I/O-Modul failure 1. Restart device Alarm 2. Change I/O module F282 Electronic memory 1. Restart device. Alarm 2. Contact service. Endress+Hauser...
  • Page 72 2. Check pressure. 3. Check sensor. F936 EMC interference Check installation on Alarm EMC. F941 Echo lost Check parameter "DC Alarm/Warning S941 value" S942 In safety distance 1. Check level. Warning/Alarm 2. Check safety distance. 3. Reset self holding. Endress+Hauser...
  • Page 73: Software History

    Modifications Documentation (FMP56, FMP57) version CD-ROM Operating Description of Technical Information Instructions Parameters 07.2010 01.00.zz Original software CD00518F/00/ BA01004F/00/EN/ GP01000F/00/EN/ TI01004F/00/EN/05.10 A2/05.10 05.10 05.10 01.2011 01.01.zz • SIL integrated CD00518F/00/ BA01004F/00/EN/ GP01000F/00/EN/ TI01004F/00/EN/10.10 • Minor bugfixes A2/13.10 10.10 10.10 Endress+Hauser...
  • Page 74: Repairs

    12.1.1 Repair concept The Endress+Hauser repair concept assumes that the devices have a modular design and that repairs can be done by the Endress+Hauser service or specially trained customers. Spare parts are contained in suitable kits. They contain the related replacement instructions.
  • Page 75: Spare Parts

    å 19 Example for spare part nameplate in connection compartment cover Measuring device serial number: • Is located on the device and spare part nameplate. • Can be read out via the "Serial number" parameter in the "Device information" submenu. Endress+Hauser...
  • Page 76: Maintenance

    Maintenance Levelflex FMP56, FMP57 Maintenance The measuring device requires no special maintenance. 13.1 Exterior cleaning When exterior-cleaning the device, always use cleaning agents that do not attack the surface of the hosuing and the seals. Endress+Hauser...
  • Page 77: Accessories

    DN40 / 1-1/2", inside-d. = 40-45mm, PPS DN50 / 2", inside-d. = 50-57mm, PPS DN80 / 3", inside-d. = 80-85mm, PPS DN80 / 3", inside-d. = 76-78mm, PPS DN100 / 4", inside-d. = 100-110mm, PPS DN150 / 6", inside-d. = 152-164mm, PPS Endress+Hauser...
  • Page 78: Communication-Specific Accessories

    The mounting kit can also be ordered directly with the device (see the Levelflex product structure, feature 620 "Accessory Enclosed", option PG "Mounting kit, isolated, rope"). 14.2 Communication-specific accessories Accessory Description Commubox FXA195 HART For intrinsically safe HART communication with FieldCare via the USB interface. For details refer to Technical Information TI404F/00 Endress+Hauser...
  • Page 79: Service-Specific Accessories

    Levelflex FMP56, FMP57 Accessories Accessory Description Commubox FXA291 Connects Endress+Hauser field devices with CDI interface (= Endress+Hauser Common Data Interface) to the USB interface of a computer. For details refer to Technical Information TI405C/07 Accessory Description HART Loop Converter Evaluates the dynamic HART variables and converts them to analog current signals or limit HMX50 values.
  • Page 80: System Components

    For details refer to Technical Information TI073R/09 and Operating Instructions BA202R/09 RNS221 Transmitter supply for 2-wire sensors or transmitters exclusively for non-Ex areas. Provides bi-directional communication using the HART communication sockets. For details refer to Technical Information TI081R/09 and Operating Instructions KA110R/09 Endress+Hauser...
  • Page 81: Return

    Levelflex FMP56, FMP57 Return Return The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g. for repair or calibration: • Remove all residue which may be present. Pay special attention to the gasket grooves and crevices where fluid may be present.
  • Page 82: Disposal

    Disposal Levelflex FMP56, FMP57 Disposal In case of disposal please separate the different components according to their material consistence. Endress+Hauser...
  • Page 83: Overview Of The Operating Menu

    Advanced setup ® Linearization ® Linearization type (® ä 103) Unit linearized (® ä 103) Free text (® ä 104) Maximum value (® ä 104) Diameter (® ä 105) Intermediate height (® ä 105) Table mode (® ä 105) Endress+Hauser...
  • Page 84 Decimal places 4 (® ä 120) Display interval (® ä 91) Display damping (® ä 120) Header (® ä 121) Header text (® ä 121) Separator (® ä 122) Number format (® ä 122) Decimal places menu (® ä 122) Endress+Hauser...
  • Page 85 (® ä 116) Measured current 1 (® ä 132) Terminal voltage 1 (® ä 132) Diagnostics ® Simulation ® Assignment of measured variable (® ä 133) Value measured variable (® ä 133) Simulation current output 1/2 (® ä 133) Endress+Hauser...
  • Page 86 Last check time (® ä 135) Level signal (® ä 135) Launch signal (® ä 136) Diagnostics ® Device reset ® Device reset (® ä 137) Expert The "Expert" menu is described in the document GP01000F ("Description of device parameters"). Endress+Hauser...
  • Page 87: Description Of Device Parameters

    : Marks parameters which can be locked via the software locking (® ä 54). Language Navigation Language Display/operation ® Language Description Language setting for the local display Options • English • One additional operating language (see product structuture, feature 500, "Additional Operation Language") Factory setting English Endress+Hauser...
  • Page 88: Display/Operation" Menu

    (e.g. data upload/download, reset etc.). The parameters can be modified as soon as the processes are complete. • See access status (priority 3) The access authorization displayed in the Access status display parameter applies (® ä 88). Format display Endress+Hauser...
  • Page 89 The display time until the next change is configured using the Display interval parameter (® ä 91). Options • 1 value, max. size • 1 bargraph + 1 value • 2 values • 1 value large + 2 values • 4 values Factory setting 1 value, max. size Endress+Hauser...
  • Page 90 Use this function to adapt the display contrast to the ambient conditions (e.g. the lighting or reading angle). Set the contrast via push-buttons: • Brighter: press the buttons simultaneously • Darker: press the buttons simultaneously Input range 20 to 80 % Endress+Hauser...
  • Page 91: Setup" Menu

    Description Defines the distance unit Selection • m • ft • in • mm Factory setting Bin property Navigation Setup ® Bin property Description Defines the bin property Selection • Concrete • Plastics / wood • Metallic • Aluminium Endress+Hauser...
  • Page 92 Defines the full calibration F. F is the distance between the minimum level (0%) and the maximum level (100%). 100% A0013191 Input range Depending on the selected distance unit and the probe. Factory setting Depending on the selected distance unit and the probe. Endress+Hauser...
  • Page 93 Diagnostics ® Measured val. ® Distance Description Displays the measured distance D from the reference point (lower edge of the flange or threaded connection) to the level. A0013201 Additional information The value is displayed in the selected "Level unit" . Signal quality Endress+Hauser...
  • Page 94 The signal quality indicated in this parameter always refers to the currently evaluated echo: either the level echo or the end-of-probe echo. To differentiate between these two, the quality of the end- of-probe echo is always displayed in brackets. Endress+Hauser...
  • Page 95: Mapping" Sequence

    Only visible if the Manual map option has been selected in the Confirm distance parameter. Description Definition of the distance up to which the mapping curve will be recorded. Input range 0.1 m (0.33 ft) to length of probe (LN) Endress+Hauser...
  • Page 96 The mapping (if one exists) is deleted and the device displays the recalculated measured distance and the mapping range. These values must be confirmed by pressing Â. The device quits the sequence. "End of sequence" is displayed. Factory setting Endress+Hauser...
  • Page 97: Advanced Setup" Submenu

    If no key is pressed for 10 minutes, or the user goes from the navigation and editing mode back to the measured value display mode, the device automatically locks the write-protected parameters after another 60 s . Please contact your Endress+Hauser Sales Center if you lose your access code Input range 0 to 9 999...
  • Page 98 Use this function to enter a unique name for the measuring point so it can be identified quickly within the plant. The name is displayed in the header: XXXXXXXXX A0013375 Header text Input range Max. 32 characters, such as letters, numbers or special characters (e.g. @, %, /) Factory setting Levelflex Endress+Hauser...
  • Page 99 Factory setting Unknown Additonal information Dielectric constants of important media commonly used in the industry are summarized in the document SD106F, which can be downloaded from the Endress+Hauser web page (www.endress.com). Process property Navigation Setup ® Advanced Setup ® Level ® Process property...
  • Page 100 Setup ® Advanced setup ® Level ® Adv. conditions Navigation Description Defines additional process conditions (if necessary) Options • Build up • None Additionally for "Medium type" = "Liquid" • Emulsion layer • Probe near bottom Factory setting None Endress+Hauser...
  • Page 101 For level measurement: • with coax probes: 0 mm • with rod and rope probes up to 8 m (26 ft): 200 mm (8") • with rod and rope probes exceeding 8 m (26 ft): 0,025 * (length of probe) Endress+Hauser...
  • Page 102 • -100,0 to 100,0 % • -200,0 to +200,0 m • -656,2 to +656,2 ft • -7874,0 to +7874,0 inch • -200.000,0 to +200.000,0 mm Factory setting Additional information The value specified in this parameter is added to the measured level (before linearization). Endress+Hauser...
  • Page 103 • Horizontal cylinder (F) • Sphere (G) 100% 100% 100% A0013299 Factory setting None Unit linearized Navigation Setup ® Advanced setup ® Linearization ® Unit linearized Condition Only visible if a linearization has been selected (i.e. Linearization type ¹ None) Endress+Hauser...
  • Page 104 Only visible if one of the following linearization types has been selected: • Linear • Pyramid bottom • Conical bottom • Angled bottom • Horizontal cylinder • Sphere Description Definition of the maximum content of the vessel (100%), as measured in the Unit linearized. Input range -50000 ... +50000 Endress+Hauser...
  • Page 105 Definition of the intermediate height H A0013264 Input range 0 to 200 m (0 to 656 ft) Factory setting 0 m (0 ft) Additional information The value must be specified in the selected distance unit (® ä 91). Table mode Endress+Hauser...
  • Page 106 Only visible if the "Table" linearization type has been selected. Description Definition or display of the (unlinearized) level of the respective linearization point. Input range Depending on the parametrized measuring range. See the parameters Empty calibration (® ä 92) and Full calibration (® ä 92). Factory setting Endress+Hauser...
  • Page 107 The measured value is linearized according to the table before being sent to the output. Factory setting Disable Additional information When editing the table, this parameter is automatically reset to the Disable option. After finishing the editing procedure it must be set to the Enable option again. Endress+Hauser...
  • Page 108 • With linearization: As defined in the Unit linearized parameter (® ä 103). Ramp echo lost Navigation Setup ® Advanced setup ® Safety settings ® Ramp echo lost Condition Only visible if the Ramp echo lost option has been selected in the Output echo lost parameter. Endress+Hauser...
  • Page 109 • For a negative slope of the ramp: The measured value is continuously decreased until it reaches • For a positive slope of the ramp: The measured value is continuosly increased until it reaches 100%. Blocking distance (® ä 101) Endress+Hauser...
  • Page 110 The Deactivate SIL/WHG sequence is required to unlock the device if it has been locked according to SIL or WHG. For details refer to the "Functional Safety Manual", SD00326F which describes the unlocking procedure and the parameters of the sequence. Endress+Hauser...
  • Page 111 In the DTM Manual input needs not to be selected explicitly. Here, manual editing of the probe length is always possible. • Length unknown A probe length correction is impossible in this case. The device quits the sequence. ("End of sequence" is displayed.) Factory setting Probe length OK Present length Endress+Hauser...
  • Page 112 Displays the measured length of probe (according to the detected end of probe signal). • Only for Confirm length = Manual input: Input parameter for the actual length of the probe. Input range 0 to 200 m (0 to 656 ft) Factory setting 4 m (13 ft) Endress+Hauser...
  • Page 113 • 4 to 20 mA NAMUR • 4 to 20 mA US • 4 to 20 mA • Fixed current Factory setting 4 to 20 mA NAMUR The "Current output 2" submenu is only available for devices with two current outputs. Endress+Hauser...
  • Page 114 Factory setting 4.0 mA Damping Navigation Setup ® Advanced setup ® Current output 1/2® Damping Description Defines the time constant for the damping of the output current. Input range 0 to 999.9 s Factory setting 0 s (i.e.: no damping) Endress+Hauser...
  • Page 115 The Defined value option is selected in the Failure mode parameter (® ä 115). Description Use this function to define the value the current output adopts in an alarm condition. Input range 3.59 to 22.5 mA Factory setting 22.5 mA Endress+Hauser...
  • Page 116 Setup ® Advanced setup ® Curr. output 1 ® Output curr. 1 Diagnostics ® Measured value ® Output curr. 1 Setup ® Advanced setup ® Curr. output 2 ® Output curr. 2 Diagnostics ® Measured value ® Output curr. 2 Description Displays the output current in mA. Endress+Hauser...
  • Page 117 The arrow displayed between the measured value and the unit indicates that the device computes with more digits than are shown on the local display. Options • x • x.x • x.xx • x.xxx • x.xxxx Factory setting x.xx Endress+Hauser...
  • Page 118 Defines the number of decimal places for the second display value. Options • x • x.x • x.xx • x.xxx • x.xxxx Factory setting x.xx Value 3 display Navigation Setup ® Advanced setup ® Display ® Value 3 display Endress+Hauser...
  • Page 119 The value is only displayed during normal operation. The Format display parameter is used to specify how many measured values are displayed simultaneously and how (® ä 88). Endress+Hauser...
  • Page 120 A time constant is entered for this purpose: if a low time constant is entered, the display reacts very quickly to fluctuating measured variables. If a high time constant is entered, the display reaction is damped. Input range 0 to 999 s Factory setting Endress+Hauser...
  • Page 121 A0013375 Position of the header text on the display User entry Max. 12 characters, such as letters, numbers or special characters (e.g. @, %, /) Factory setting - - - - - - - - - - - - Endress+Hauser...
  • Page 122 This parameter only determines the representation of numbers within the operating menu (e.g. Empty calibration, Full calibration). It does not affect the measured value representation. For measured values, the number of decimal places is defined in the Decimal places 1 to Decimal places 4 parameters (® ä 117). Endress+Hauser...
  • Page 123 Use this function to select an action to save the data to the display module. While this action is in progress, the configuration cannot be edited via the local display and a message on the processing status appears on the display. Endress+Hauser...
  • Page 124 The current device configuration of the HistoROM is corrupt or not compatible with the backup copy in the display module. • Check not done The device configuration of the HistoROM has not yet been compared to the backup copy in the display module. Endress+Hauser...
  • Page 125: The "Diagnostics" Menu

    Diagnostics ® Operatint time fr. restart Description Use this function to display the time the device has been in operation since the last device restart. User interface Days (d), hours (h), minutes (m) and seconds (s) Operating time (® ä 123) Endress+Hauser...
  • Page 126: Diagnsotics List" Submenu

    User interface Symbol for event behavior, diagnostics event, time the event occurred and event text Additional information User interface Example 1 for display format: S441 01d4h12min30s Current output 1 Example 2 for display format: F276 10d8h12min22s I/O module error Endress+Hauser...
  • Page 127: The "Event Logbook" Submenu

    • For event messages in category I (status signal): status signal, event number, time event occurred, event text • For event messages in category F, M, C, S (status signal): diagnostics event, status symbol, time event occurred, event text Endress+Hauser...
  • Page 128 Example 2 for display format: S441 01d4h12min30s Current output 1 HistoROM A HistoROM is a "non-volatile" device memory in the form of an EEPROM. To order the HistoROM with advanced capabilities, see the "Accessories" section of the "Technical Information" document. Endress+Hauser...
  • Page 129: Device Information" Submenu

    Use this function to view the serial number of the device. It can also be found on the nameplate. Uses of the serial number • To identify the device quickly, e.g. when contacting Endress+Hauser. • To obtain specific information on the device using the Device Viewer: www.endress.com/deviceviewer...
  • Page 130 Uses of the order code • To order an identical spare device. • To identify the device quickly and easily, e.g. when contacting Endress+Hauser. Display Max. 20-digit character string comprising letters, numbers, punctuation marks or +, -...
  • Page 131 Diagnostics ® Device info ® Manufacturer ID Prerequisite Device with HART protocol Description Use this function to view the manufacturer ID with which the device is registered with the HART Communication Foundation. Display 2-digit hexadecimal number Factory setting 0x11 (for Endress+Hauser) Endress+Hauser...
  • Page 132: Measured Value" Submenu

    3.59 to 22.5 mA Terminal voltage 1 Diagnostics ® Measured val. ® Terminal volt. 1 Navigation Description Use this function to view the current terminal voltage that is present at the current output. Display range 12 to 36 V Endress+Hauser...
  • Page 133: Simulation" Submenu

    Use this function to switch simulation of the current output on and off. The display alternates between the measured value and a diagnostics message of the "function check" category (C) while simulation is in progress: The simulation value is defined in the Value current output 1-2 parameter (® ä 134). Endress+Hauser...
  • Page 134 The display alternates between the measured value and a diagnostics message of the "function check" category (C) while simulation is in progress: Options • On • Off Factory setting Endress+Hauser...
  • Page 135: The "Device Check" Submenu

    Last check time Navigation Diagnostics ® Device check ® Last check time Description Displays the operating time at which the last device check has been performed. Additional information Display format Days (d), hours (h), minutes (m), seconds (s): 0000d00h00m00s Level signal Endress+Hauser...
  • Page 136 Displays the result of the device check for the launch signal (fiducial). Display • Check not done • Check not ok Check the mounting position of the device. In non-metallic vessels use a metal plate or a metal flange. • Check ok Endress+Hauser...
  • Page 137: Device Reset" Submenu

    • Restart device The restart resets every parameter whose data are in the volatile memory (RAM) to the factory setting (e.g. measured value data). The device configuration is not modified. Factory setting Cancel Endress+Hauser...
  • Page 138: Index

    Device name (Parameter) ..... . 129 Extended order code 1 (Parameter) ....130 Endress+Hauser...
  • Page 139 Medium property (Parameter) ....99 Design ....... . . 10 Endress+Hauser...
  • Page 140 Value 4 display (Parameter) ..... 119 Value current output 1 (Parameter) ....134 Endress+Hauser...
  • Page 141 Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
  • Page 142 www.endress.com/worldwide *71120867* BA01004F/00/EN/10.10 71120867 CCS/COSIMA 71120867...

This manual is also suitable for:

Hart levelflex fmp57

Table of Contents