Smart Grid (Sg) - Wolf BWL-1S-05 Installation And Operating Instructions Manual

Split air/water heat pump
Hide thumbs Also See for BWL-1S-05:
Table of Contents

Advertisement

30.4 Smart Grid (SG)
Terminal X1
Terminal X1
9/10
11/12
(=SG_0):
(=SG_1):
Open
Open
Open
Bridged
Bridged
Open
Bridged
Bridged
Contractor parameters
WP025
WP026
WP027
WP028
WP032
WP033
86
Additional functions
The Smart Grid (SG) function allows the power supply utility (PSU) to optimally
adjust grid utilisation through intelligent control of consumers.
Using external switching commands (floating contacts SG_0 and SG_1 on
terminals X1 – 9/10 and X1 – 11/12), the compressor and/or electric heater
operation can be blocked, or requested with/without an increase in the set heating/
DHW temperatures, or the active cooling function enabled.
The heat pump can be operated using a compressor, electric heater, or both a
compressor and electric heater.
The SG function status message is shown on the status pages of the BM-2
programming unit and in the "Displays"/"Heating appliance" submenu on the
AM display module and BM-2 programming unit.
The SG function for heating is only possible in system configurations with header
return temperature sensor SAF (T_headerRTN) and where the outside temperature
is below the set winter/summer changeover.
For active cooling by the SG function, active cooling must be enabled in the AM/
BM-2 standard settings, as well as in contractor parameters WP058 and WP033.
In addition, the outside temperature must be above the set winter/summer
changeover and the enable temperature for active cooling (WP053).
If standby mode is set on the BM2 programming unit, the SG function is not
available.
Heat pump standard mode
Start recommendation (= activation on heating/cooling demand even
outside set switching times and on shutdown during automatic mode
Heat pump shutdown (see power-OFF)
Start command (= activation on heating/cooling demand even
outside set switching times and on shutdown during automatic mode
(ECO-ABS); during heating or DHW operation with increase of set
temperatures according to settings of WP026 and WP027)
Smart Grid
Set heating temperature increase
Set DHW temperature increase
Heat generator activation
Heating with SG/PV
Cooling with SG/PV
Function:
(ECO-ABS))
Meaning
SG status:
Standard mode
Start
recommendation
Power-OFF
Start command
Setting:
ON
0 ... 20 °C
0 ... 40 °C
OFF, HP, HP+elec.htg, elec. heater
ON, OFF
ON, OFF
3064298_201805