37 System log book
37.1 Responsibilities of the operator
As part of the Kyoto Protocol, the European Union is committed to reducing the emissions of fluorinated greenhouse
gases. To this end, EC Regulation No. 517/2014 of 16/04/2014 has been adopted. The overriding goal of this F-gas
Regulation is to reduce emissions of fluorinated greenhouse gases over the entire life cycle of these gases.
In accordance with EC Regulation No. 517/2014, the owner/operator has the following obligations:
37.1.1 Annual tightness test
In accordance with Article 4, systems which contain more than 3 kg of refrigerant and which are not hermetically
sealed or, as of 2017, systems with a CO2 equivalent mass of 5 t or more, must undergo an annual tightness test.
For systems containing less than 3 kg of refrigerant, but with a CO2 equivalent mass of more than 5 t, a transitional
period applies until 31/12/2016. From 01/01/2017, these systems will then be required to undergo an annual tightness
test.
WOLF split heat pumps use F-gas R410A, an HFC mixture with a global warming potential (GWP100) of 2088. This
means that 1 kg of R410A equates to 2.088 t of CO2.
Which WOLF split heat pumps require a tightness test is detailed in the following table.
BWL-1S(B)-05/07
Refrigerant charge
2.15 kg
weight in delivered
(4.49 t CO2 equiv)
condition
Refrigerant per m of
pipe
Tightness test
No
(below 5 t CO2 equiv)
Yes if pipe length has
been extended by more
than 4 m (total length
greater than 16 m).
Conversion to charge weight CO2 equivalent mass:
Refrigerant charge weight x GWP100 = charge weight as CO2 equivalent mass
Example: 2.15 kg R410A * 2088 kg CO2 = 4489 kg CO2 = 4.49 t CO2
The tightness test may only be carried out by certified contractors/refrigeration engineers in accordance with
EC 842/2006, 303/2008 and 517/2014.
3064298_201805
System log book
BWL-1S(B)-10
2.95 kg
(6.16 t CO2 equiv)
60 g R410A/m pipe length corresponds to 125 kg CO
Yes
(over 5 t CO2 equiv)
BWL-1S(B)-14
2.95 kg
(6.16 t CO2 equiv)
equiv. per metre of pipe length
2
Yes
(over 5 t CO2 equiv)
-
-
BWL-1S(B)-16
3.50 kg
(7.31 t CO2 equiv)
Yes
(over 5 t CO2 equiv)
-