8.2 Minimum room volume
When siting the heat pump in occupied/communal areas, as opposed to a separate plant room, the minimum
room volume in relation to the refrigerant charge weight must be complied with. In accordance with EN 378-1,
the following limit applies to R410A refrigerant: 0.44 kg/m³ refrigerant per cubic metre room volume.
For refrigerant lines less than 12 m, the refrigerant charge weight provided is sufficient. For refrigerant lines
between 12 m and a maximum of 25 m long, an additional 0.06 kg/m of R410A needs to be added; consequently,
a larger room volume is required for the indoor module (see table).
Type
BWL-1S(B)-05
BWL-1S(B)-07
BWL-1S(B)-10
BWL-1S(B)-14
BWL-1S(B)-16
8.3 Transport to the installation site
To prevent damage during transport, the heat pump must remain packaged whilst being transported to the final
installation site by pallet truck.
3064298_201805
Siting the BWL-1S(B)
Refrigerant line < 12 m
Charge weight
Room volume
2.15 kg
2.15 kg
2.95 kg
2.95 kg
3.50 kg
Only transport the heat pump by pallet truck in its packaging.
Please note: Risk of tipping.
To prevent damage to the appliance, the heat pump outdoor
module must not be tilted by more than 45° during transport.
The components, in particular the plastic casings and the
pipework for the refrigerant circuit and heating side, must not
be used to transport the appliance. Only use the grab handles
provided when transporting the heat pump.
Bear in mind the weight of the heat pump.
Please
Observe the instructions on the packaging.
note
Refrigerant line 12 m - 25 m
Charge weight
up to
> 4.9 m³
2.93 kg
> 4.9 m³
2.93 kg
> 6.7 m³
3.73 kg
> 6.7 m³
3.73 kg
> 8.0 m³
4.28 kg
Room volume
> 6.7 m³
> 6.7 m³
> 8.5 m³
> 8.5 m³
> 9.7 m³