Wolf BWL-1S-05 Installation And Operating Instructions Manual page 67

Split air/water heat pump
Hide thumbs Also See for BWL-1S-05:
Table of Contents

Advertisement

Contractor
BM-2 designation
Parameter
WP033
Cooling with PV/SG
Active cooling
WP053
T_outs. enable Coolg
WP054
Min flow t cooling
WP055
Offset set flow Coolg
WP058
Enable act. cooling
Night mode
WP061
Night mode end
WP062
Night mode start
Night mode limit
WP064
WP066
Night mode
Compressor
WP080
Comp. dual mode pt
WP090
Enable elec heating
WP091
Dual mode pt el htg
WP092
Power-OFF elec htg
WP093
Temp. deact. WP091
WP094
Electric heater type
WP101
Dual md pt, add HG
WP104
Add HG eBUS
Other
WP121
Max. compressor
starts/h
3064298_201805
Contractor parameters
AM designation
Cooling with PV/SG
Outside temp. to enable cooling
Min. flow temp. for cooling
Offset for set flow temp., cooling
Enable active cooling
Night mode end
Night mode start
Night mode limitation
Night mode
Compressor dual mode point
Electric heater/add HG
Enable electric heater
(heating mode)
Elec heater dual mode pt
(heating mode)
Power-OFF for elec. heater
Temporary deactivation of WP091
Electric heater type
Add HG dual mode point
(heating mode)
Add HG via eBUS
Max. compressor starts per hour
Setting range
OFF, ON
15.0 ... 40.0 °C
5.0 ... 25.0 °C
5.0 ... 40.0 °C
OFF, ON
00:00 ... 23:59
00:00 ... 23:59
75 %, 65 %, 55 %,
45 %
OFF, ON
-20.0 °C ... 45.0 °C
OFF, ON
-20.0 °C ... 45.0 °C
OFF, ON
0 to 40 days
None, 2 kW, 3 kW,
4 kW, 6 kW, 9 kW
-20.0 °C ... 45.0 °C
OFF, ON
3 ... 10 / h
Factory
setting
OFF
25.0 °C
20.0 °C
15.0 °C
OFF
06:00
22:00
75 %
OFF
-20.0 °C
ON
-5.0 °C
ON
0 days
6 kW
0.0 °C
OFF
6 / h
67

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents