Pin-Out Of The Digital Output Sockets X1 To X8; I/O Module 8 Do 2A (6Es7 142-3Bf00-0Xa0) - Siemens SIMATIC ET 200eco Manual

Distributed i/o station
Hide thumbs Also See for SIMATIC ET 200eco:
Table of Contents

Advertisement

6.5

I/O module 8 DO 2A (6ES7 142-3BF00-0XA0)

Properties
The I/O module 8 DO 2A has the following features:
• 8 digital outputs
• output current = 2 A per output
• rated load voltage = 24 VDC
• suitable for magnetic solenoid valves, DC contactors and signal lamps
Pin assignment of the DO sockets
The table below shows the pin assignment of the eight digital output sockets.
Table 6-6

Pin-out of the digital output sockets X1 to X8

Pin
Assignment of
socket X1
1
n.c.
2
n.c.
3
Ground potential, load voltage supply (2M)
4
Output signal
Channel 0
5
PE
Pin
Assignment of
socket X5
1
n.c.
2
n.c.
3
Ground potential, load voltage supply (2M)
4
Output signal
Channel 4
5
PE
ET 200eco Distributed I/O Station
A5E00158716-02
Assignment of
Assignment of
socket X2
socket X3
Output signal
Output signal
Channel 1
Channel 2
Assignment of
Assignment of
socket X6
socket X7
Output signal
Output signal
Channel 5
Channel 6
Technical data
Assignment of
View of the
socket X4
socket (Front
view)
1
Output signal
Channel 3
Assignment of
socket X8
Output signal
Channel 7
2
3
5
4
6-13