Structure Of The Station Status 1(Byte 0) Et 200Eco - Siemens SIMATIC ET 200eco Manual

Distributed i/o station
Hide thumbs Also See for SIMATIC ET 200eco:
Table of Contents

Advertisement

Commissioning and diagnostics
4.4.3
Station status 1 to 3
Definition
Station status 1 to 3 provides an overview of the status of a DP slave.
Station status 1
Table 4-7

Structure of the station status 1(byte 0) ET 200eco

Bit
Meaning
0
1: The DP master can not access the
DP slave.
This bit is always "0" on the DP
slave.
1
1: The DP slave is not ready to ex-
change data.
2
1: Configuration data sent to the DP
slave by the DP master is incompa-
tible to the physical structure of the
DP slave.
3
0: The bit is always "0".
4
1: The DP slave does not support the
requested function (e.g.
SYNC/FREEZE).
5
1: When the station status is being
read from the DP master, is the bit
"1"?
6
1: The DP slave type is incompatible
with the software configuration.
7
1: The DP slave parameters were as-
signed by a different DP master (not
by the DP master currently acces-
sing the DP slave).
4-12
Cause / Remedy
Is the correct PROFIBUS address set on
the DP slave?
Is the bus connector plugged in?
Is the power supply to the DP slave
switched on?
Correct setup of the RS485 repeater?
A RESET was performed on the DP slave
(off/on)?
Wait, the DP slave is currently starting up.
Has the correct station type or configuration
of the DP slave been entered in the
configuration software?
–––
Check the configuration.
The DP master is unable to interpret the DP
slave's answer.
Compare the program and the actual setup.
The bit is always 1 when you access the DP
slave from a PG or other DP master, for
example.
The PROFIBUS address of the DP master
that has assigned the DP slave parameters
is found in the diagnostic byte "Master
PROFIBUS address".
ET 200eco Distributed I/O Station
A5E00158716-02

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents