P1 Bus Interface Module, TX-I/O Power Supply, and
Bus Connection Module
1
2
3

Power and Communication Connections

Symbol
CS
CD
S - +

Extending Communication

If an installation requires more than one DIN rail, connect the Communication
Supply (CS) and Communication Data (CD) terminals from the P1 BIM to the
same terminals on the first device of every additional DIN rail (a TX-I/O Power
Supply or Bus Connection Module). TX-I/O Power Supplies and Bus Connection
Modules include a second set of CS and CD contacts to simplify connection of
additional DIN rails. Ensure that the system neutral is installed.
NOTE:
Maximum extension of the TX-I/O bus is 50 meters total for all devices.
12
24V
24V
R UN
FLT
COM
S -
+
CS CD
LAN
Connection
P1 Bus Interface Module (P1 BIM) TXB1.P1
Device
All
All
All (feed-thru on TX-I/O Power Supply and Bus
Connection Module)
All (feed-thru on TX-I/O Power Supply and Bus
Connection Module)
P1 BIM
24 Vac In
5
Common
Data
4
+ 24 Vdc
24 Vac IN (from transformer)
Common Ground
24 Vdc Communication Supply
(24 Vdc)
Communication Data (Signal)
LAN connection
Siemens Building Technologies, Inc
24V