Notice The information contained within this document is subject to change without notice by Siemens Industry, Inc. Siemens Industry, Inc. assumes no responsibility for any errors that may appear in this document. All software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license.
Page 4
Copyright Notice Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
Row Orientation....................38 Installation and Commissioning................40 Required Tools ....................40 Common Grounding Requirement ..............41 Power Supply Wiring ..................43 Extending Communication .................44 Commissioning Notes ..................45 Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
Page 6
Replacing a TX-I/O Plug-in Module .................46 Replacing a TX-I/O Module Assembly..............47 Troubleshooting the TX-I/O Island Bus ..........48 Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
Bus Connection Module using island bus connectors. The TC-36 provides the control database and communications for points on TX-I/O modules, but it does not supply power. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only...
Hot-swappable electronic components allow powered electronics to be disconnected and replaced without removing terminal wiring or disturbing the self- forming bus. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
• • 4-20 mA functionality is available only point terminations 5-8 10 Hz counter functionality is available only on point terminations 1-8 Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
The I/O status LED and LCD display change accordingly. Pressing "+" or "–" when local override is disabled results in an error. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only...
Power supply modules (intrinsic consumption) All individual I/O points Field devices (connected to the module supply or to separate transformers) Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
Page 12
Included in intrinsic consumption (no I/O status LED for temperature inputs). The table assumes 5 mA to supply the current sensor, which should be sufficient for most models. If in doubt, please refer to the sensor data sheet. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587...
Address key with mechanically encoded Module disengage catch module address Plug-in contacts between the terminal base Module release catch and the plug-in module Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
CAUTION The address key must be inserted firmly into the terminal base before swiveling it into the plug-in module. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only...
To Remove a Module Squeeze module sides above the release catch and pull up to remove the I/O module from the terminal base. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only...
Output (arrow pointing OUT from center of module). Input (arrow pointing IN toward center module). 24 Vdc output (field supply). 24 Vac output (field supply). Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only...
10 Hz. Each input point has a green LED for status indication. NOTE: Potential free (dry contact) for all points. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
24V ...250V TXM1.6R The TXM1.6R and TXM1.6R-M Digital Output modules provide six NO or NC (form C), maintained or pulsed, voltage free/dry contacts. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only...
Separate knockouts should be used for high voltage and low voltage wiring. Leave at least 2 inches (50.8 mm) of space between the Class 2 wires and other wires in the panel. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587...
Admissable current per module Max. 4 A (total for all four terminals) Fuse 4A, in TX-I/O Power Supply or Bus Connection Module Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
The neutral of analog inputs and outputs must always be connected to the terminal associated with that I/O input. Active input and output support includes analog input and output (0-10 Vdc). Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587...
Symbolic display of process value Notification of faulty operation, short circuit, or sensor open circuit Orange LEDs indicate override status individually per point. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
Page 23
Low or high value Analog Output, Current Low or high value Analog Output, Voltage Low or high value Digital Input, Counter Step indicator Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
AC supply voltage for peripheral devices such as valves and actuators Green LED status per I/O point that varies in intensity according to the voltage and current (directly proportional) Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
Analog output current 4-20 mA (four current outputs maximum per module on Points 5 through 8) 24 Vdc supply voltage for sensors at a maximum of 200 mA per module. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
Page 26
The range monitoring of signal type U10 is done with a short NEGATIVE signal of –3,1 V, 0.05 mA (open circuit detection). If a field device has an open output, a negative voltage could appear there. This can damage any polarized components (e.g. capacitors). Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference...
Min. closing / opening Max. bounce time Max. Counting time [ms] including [ms] frequency bouncing (symmetric) Maintained contact Pulse contact Mechanical Counter 25 Hz Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
Point in manual override No sensor (current) No output signal 24 Vdc supply < 22 Vdc Inactive point Invalid value No voltage Unconfigured point Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
Page 29
Analog Output, Voltage Low or high value Digital Input, Counter Step indicator Digital Input, N/C Contact Active Inactive Digital Input, N/O Contact Active Inactive Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
‒ Indicates the AC fuse status with an LED for easy diagnostics. Routes the bus signal between DIN rails (+24 Vdc Communication Supply (CS) and Communication Data (CD) signals). Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only...
24 Vac input transformer must not exceed 1000 VA. NEC Class 2 wiring may be used up to 96 VA, and NEC Class 1 Power Limited wiring must be used above 96 VA and up to 1000 VA. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference...
- Insufficient or shorted I/O bus supply. - An AC/DC converter is faulty. TX-I/O bus connector (male) Connection for TX-I/O Modules. Includes field device supply. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
24 Vac input transformer must not exceed 1000 VA. NEC Class 2 wiring may be used up to 96 VA, and NEC Class 1 Power Limited wiring must be used above 96 VA and up to 1000 VA. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference...
Field device supply. System neutral. TX-I/O bus connector (male) Connection for TX-I/O Modules. Includes field device supply. Fuse 4A fuse for field supply. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
If the 24 Vdc supply (maximum 1.2 A) is "used up" by the I/O modules and field devices, an additional TX-I/O Power Supply module is required (operating in parallel with the first one). Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only...
Page 36
160 VA The DC power requirement of 20.9 W is within the capability of a single TX-I/O Power Supply module (28.8 W). Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only...
Page 37
AC = 80 VA AC = 80 VA AC = 80 VA 24 Vac (common to Power Supply Module) TX-I/O Island Bus Power Supply Example. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
2 x 16.25 in FXX-485.3 section of the CS CD PX Series enclosure. Modular with TX-I/O Island Bus on Horizontal DIN Rails. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
Page 39
PX Series enclosure. 3-WIRE COMMUNICATION (CS,CD, -36 with TX-I/O Bus on Vertical DIN Rails. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
Minimum shaft length 1” (26 mm); however, 1.6” (40 mm) allows access to the screws while plug-in module is in the "parked" position. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only...
All measuring/neutral terminals are connected in the plug-in I/O module, not in the terminal base. When the plug-in I/O module is removed, these terminals are not connected. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only...
Page 42
Back Detail of PX Series Enclosure Earth Ground Stud (Under Wire Cover). TALON Wiring Guidelines Manual For more information, see the (588-581). Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
The CD, CS, and System Common ( ) signals from the TX-I/O Power Supply module that is connected to the TX-I/O Modules are brought back and tied to the TC-36 at terminals 82, 83, and 84. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587...
TX-I/O Power Supplies and Bus Connection Modules include a second set of CS and CD contacts to simplify connection of additional DIN rails. Ensure that the system neutral is installed. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587...
There’s no control of outputs during this time. If there’s no communication after 4 seconds: The TX-I/O module begins operation with the backup values. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587 CONFIDENTIAL: For internal use only 4/6/2010...
Page 46
As soon as the new module starts communicating with the TC Modular or TC-36, it is configured according to the module address and starts operation shortly afterward. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587...
Page 47
As soon as the new module starts communicating with the TC Modular or TC-36, it is configured according to the module address and starts operation shortly afterward. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587...
Page 48
(module supply 24 Vdc). The power consumption of an I/O island will rise when all relays are active and all current outputs deliver 20 mA. This causes a drop in the supply voltage. Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587...
Page 49
In this case, the TC Modular or TC-36 reacts by switching off the communication after 5 cycles (shortcut between CD and CS, the COM LED will light brightly). Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference 588-587...