Separating A Module From Its Terminal Base - Siemens TX-I/O Quick Start Manual

Hide thumbs Also See for TX-I/O:
Table of Contents

Advertisement

1
Standard DIN mounting rail (not included)
2
Terminal base (plug-in base for the I/O module)
3
Plug-in module (the functioning component of the I/O module assembly)
4
Local override facility (not applicable to all types)
5
LCD display (not applicable to all types)
6
Detachable label holder
7
Module label (not included – print module labels from System Profile)
8
Address key with mechanically encoded module address
9
Plug-in contacts between the terminal base and the plug-in module
10
Electrical contact between terminal base and plug-in module
11
Terminal screws
12
Test pickups (test points)
13
Slide fitting to lock assembly into position on standard mounting rail
14
Bus connector
15
Bus connector cover (provided with P1 BIM, Power Supply, and Bus
Connection Module)
16
Module lock
17
Module disengage catch
18
Module release catch

Separating a Module from Its Terminal Base

Caution:
Swing the address key away from the
I/O module before disengaging an I/O
module from its terminal base.
To 'park' a module – Squeeze module sides above the disengage catch (17)
and pull up slightly to disengage the I/O module from the terminal base. The I/O
module is retained in the terminal base ('parked'), but all wiring connections are
now floating.
To remove a module – Squeeze module sides above the release catch (18) and
pull up to remove the I/O module from the terminal base.
Siemens Building Technologies, Inc
I/O Module Assembly
5

Advertisement

Table of Contents
loading

Table of Contents