Et 200s distributed i/o power module dc24v (18 pages)
Summary of Contents for Siemens 6DL2804 Series
Page 1
Description SIMATIC ___________________ Mounting Distributed I/O ___________________ Distributed I/O device 6DL2804-xxxxx Maintenance and servicing ___________________ Technical specifications Hardware Installation Manual ___________________ Ground points in the enclosure ___________________ Dimension drawings ___________________ ESD Guidelines ___________________ Service and support Siemens Controls 03/2014 A5E34318119...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
● They are trained or instructed in maintenance and use of appropriate safety equipment according to the safety regulations. ● They should be trained in first aid. Distributed I/O device 6DL2804-xxxxx Siemens Controls Hardware Installation Manual, 03/2014, A5E00378896F-03...
Safety information 2.4 Measures Measures In the interest of safety, observe the following precautionary measures: WARNING Type of protection "Flameproof enclosure d" Devices with "pressure-resistant encapsulation" protection may only be opened when the power has been disconnected. Type of protection "Intrinsic safety i" "Intrinsically-safe"...
• ET 200iSP manual (A5E00247482) • Principles of explosion protection manual (6ES7398-8RA00-8BA0) This information is available on the Internet on the Siemens home page. ● Only open the enclosure in Zones 21 and 22 if no ignitable dust atmosphere is present.
Description 3.3 Product features Product features The device consists of a separately certified wall-mounted enclosure (6DL2804-0xxxx). The enclosure is made of stainless steel and is intended for wall mounting. The device is intended for the installation of control and measuring devices such as: ●...
Z***: This additional data (e.g. ZA01, ZA02, ...) serves to identify design versions which are not included in the data positions of the type designation. The additional data is only specified if required. Distributed I/O device 6DL2804-xxxxx Siemens Controls Hardware Installation Manual, 03/2014, A5E00378896F-03...
● In the case of aggressive environments, check whether use of the enclosure is possible with the material in question. Delivery of enclosures with appropriate surface protection is possible for use with aggressive environmental conditions. Distributed I/O device 6DL2804-xxxxx Siemens Controls Hardware Installation Manual, 03/2014, A5E00378896F-03...
Page 16
Description 3.6 Details of the enclosure Cable and wiring entries (CWE) ● When fitting cables, observe the manufacturer's data on the tightening torques of the cable and wiring entries. ● Use the tightening torque of the clamping screw when connecting the cables. ●...
Page 17
● Electrical equipment as well as combinations of equipment can impair the intrinsic safety of the circuits as a result of their electrical parameters. Prior to installing equipment, check that the intrinsic safety of the circuit is still guaranteed. Distributed I/O device 6DL2804-xxxxx Siemens Controls Hardware Installation Manual, 03/2014, A5E00378896F-03...
Page 18
Description 3.6 Details of the enclosure Distributed I/O device 6DL2804-xxxxx Hardware Installation Manual, 03/2014, A5E00378896F-03...
• Assembly, installation, commissioning and maintenance may only be performed by qualified personnel. • The devices and installed components must only be used for their intended purpose. Distributed I/O device 6DL2804-xxxxx Siemens Controls Hardware Installation Manual, 03/2014, A5E00378896F-03...
Mounting 4.1 Transport and storage Transport and storage Pack and store the enclosure for transport or storage so that there can be no undue strain on the enclosure, particularly on its top cover. If there is too much strain on the top cover of the enclosure, this can damage the seal.
Page 21
8. If you replace installed components, follow the instructions in the manufacturer's description of the device. See also Design of enclosure (Page 12) Distributed I/O device 6DL2804-xxxxx Siemens Controls Hardware Installation Manual, 03/2014, A5E00378896F-03...
Mounting 4.3 Installing the enclosure outdoors Installing the enclosure outdoors The enclosure should have at least IP56 protection when installing outdoors. This prevents damaging amounts of dirt or water from penetrating the enclosure under normal ambient conditions. Take the following additional protective measures depending on the environment of the installation location: ●...
Make sure that the vent of the pneumatic system does not blow directly into the enclosure. The pressure resulting in the enclosure would otherwise damage the seal and screwed glands, and the degree of protection would no longer be provided. Distributed I/O device 6DL2804-xxxxx Siemens Controls Hardware Installation Manual, 03/2014, A5E00378896F-03...
Mounting 4.5 Use of I/O device at temperatures down to -40 C Use of I/O device at temperatures down to -40 °C You must install a heater in the enclosure in order to operate the devices at temperatures down to -40 °C. Note the following: When using a closed enclosure, only switch the installed components on following a specific warming-up time which depends on the enclosure size and heating power: ●...
Temperature response inside the enclosure following switching-on of the heater at an outdoor temperature of -40 °C. After > 3 hours, the internal temperature is above the minimum permissible operating temperature of the installed components of -20 °C. Distributed I/O device 6DL2804-xxxxx Siemens Controls Hardware Installation Manual, 03/2014, A5E00378896F-03...
Page 26
Mounting 4.5 Use of I/O device at temperatures down to -40 C Distributed I/O device 6DL2804-xxxxx Hardware Installation Manual, 03/2014, A5E00378896F-03...
Check the tightening torques. If necessary, re-tighten the glands to the torques specified by the manufacturer. For information on the torques, refer to the respective manufacturer documentation. Distributed I/O device 6DL2804-xxxxx Siemens Controls Hardware Installation Manual, 03/2014, A5E00378896F-03...
Note that the operating temperature of the complete setup must be checked again if further components are subsequently fitted. The temperature range of -40 °C only applies to the enclosure types 6DL2804-1xxx1 (metal cable entries). Installation of a heater is required for this. Distributed I/O device 6DL2804-xxxxx Siemens Controls Hardware Installation Manual, 03/2014, A5E00378896F-03...
Technical specifications Table 6- 2 Technical specifications 6DL2804-xMDxx / xMExx 6DL2804- xMDxx xMExx Wall-mounted enclosure Type 6DL2804-0xxxx, DMT 02 ATEX E 249 U Ex marking See Ex marking Degree of protection IP54/IP55 Dimensions: W x H x D 650 x 450 x 230 950 x 450 x 230 Material Stainless steel: DIN 1.4404, plate thickness 1.5 mm...
II 2 (1) D Ex tb [ia IIIC Da] [Ex ia Da] IIIC T130°C Db I M2 Ex e d ib [ia Ga] I Mb or I M2 Ex e d mb ib [ia Ga] I Mb Distributed I/O device 6DL2804-xxxxx Siemens Controls Hardware Installation Manual, 03/2014, A5E00378896F-03...
Dimension drawings 8.3 Installation: FO conductor Installation: FO conductor ① FO coupler ② Terminals for power supply and distribution 24 V DC Figure 8-4 Distributed I/O device with installation of FO coupler: single and redundant designs Distributed I/O device 6DL2804-xxxxx Hardware Installation Manual, 03/2014, A5E00378896F-03...
The electrostatic discharge current may lead to latent failure of a module, that is, this damage may not be significant immediately, but in operation may cause malfunction. Distributed I/O device 6DL2804-xxxxx Siemens Controls Hardware Installation Manual, 03/2014, A5E00378896F-03...
ESD Guidelines Electrostatic charging Every person without a conductive connection to the electrical potential of his/her surroundings can be electrostatically charged. The figure below shows the maximum electrostatic charge that can build up on a person coming into contact with the materials indicated. These values correspond to IEC 801-2 specifications.
Easy shopping with the A&D Mall Catalog & online ordering system: http://www.siemens.com/automation/mall Training All the training options are listed at: http://www.siemens.com/sitrain Find a contact at: Phone: +49(911) 895-3200 Technical support Tel +49 180 5050 222 Fax +49 180 5050 223 http://www.siemens.com/automation/service...
Page 42
Service and support Distributed I/O device 6DL2804-xxxxx Hardware Installation Manual, 03/2014, A5E00378896F-03...
Page 44
Index Qualified personnel, 7 Safety precautions, 8 Seal, 20 Service technicians, 5 Signal line, 21 Storage, 20 Technical specifications I/O device, 29, 30 Technical support, 41 Test certification, 7 The Ordinance on Industrial Safety and Health, 7 Training, 41 Transport, 20 Type of protection By means of enclosure, 8 Increased safety, 8...