Siemens SIMATIC ET 200SP Manual page 51

Digital output module dq 4x24..230vac/2a hf 6es7132-6fd00-0cu0
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Technical specifications
Electromagnetic compatibility
The control of loads in the control types phase control power-proportional or phase-angle
proportional results in strong electromagnetic effects on the power supply network.
To observe the limits in accordance with EMC Directives, you must filter the load supply of
the module with phase control in PC mode or when using the function "Output filter with
phase control" in DQ mode.
Conformity was measured with filters of the type "EPCOS SIFI-C B84113C". Use this type of
filter or a filter with the same characteristic curve or with a characteristic curve with greater
damping.
You must ensure conformity with the values in the tables below.
Interference emission in accordance with EN 61000-6-4:2007 + A1:2011 and IEC 61131-2:
Table 5- 1
Frequency
Test environment OATS or SAC
(measured at a distance of 10 m)
Test environment FAR
(measured at a distance of 3 m)
Test environment OATS, SAC or FAR
(measured at a distance of 3 m)
Table 5- 2
Frequency
0.15 MHz to 0.5 MHz
0.5 MHz to 30 MHz
Dimension drawing
See the manual ET 200SP BaseUnits
(http://support.automation.siemens.com/WW/view/en/59753521)
50
Interference emission of electromagnetic fields
30 MHz to 230 MHz
230 MHz to 1000 MHz
30 MHz to 230 MHz
230 MHz to 1000 MHz
1 GHz to 3 GHz
3 GHz to 6 GHz
Interference emission via the AC power supply
Interference emission
<40 dB (µV/m) Q
<47 dB (µV/m) Q
45 to 52 dB (µV/m) Q
<52 dB (µV/m) Q
<76 dB (µV/m) P / <56 dB (µV/m) M
<80 dB (µV/m) P / <60 dB (µV/m) M
Interference emission
<79 dB (µV/m) Q
<66 dB (µV/m) M
<73 dB (µV/m) Q
<60 dB (µV/m) M
DQ 4x24..230VAC/2A HF digital output module (6ES7132-6FD00-0CU0)