Control type
At the module level, specifies the control type in which the module's channels are operated.
● Phase control - phase-angle proportional (default)
● Phase control - power-proportional
● Wave packet control - half waves
● Wave packet control - full waves
Diagnostics No supply voltage L
Enabling of the diagnostics for no or insufficient supply voltage L.
Diagnostics Overtemperature
Diagnostics enabled when overtemperature occurs in the module.
When you enable the Overtemperature diagnostics and the module detects that the
maximum permissible module temperature is exceeded, the Overtemperature diagnostics is
output.
Diagnostics Wire break
Enabling of the diagnostics if the line to the actuator is broken.
Diagnostics overflow
Enabling of the diagnostics when the permitted value range of the process value is
exceeded.
Channel activated
Determines whether a channel is enabled or disabled.
Temperature shutdown
Determines whether a channel remains activate or is deactivated in case of
overtemperature.
When the module has detected that the maximum permissible module temperature has been
exceeded, the channel is either deactivated or remains active depending on the
configuration.
To prevent damage to the module, the channel is automatically deactivated when
temperature shutdown is configured.
You cannot control the channel until the temperature is once again in the valid range.