Channel substitute value [0.1%]
Defines the substitute value that is output when a CPU STOP occurs and the setting "Output
substitute value" is selected in the "Reaction to CPU STOP" parameter.
Potential group
A potential group consists of a group of directly adjacent I/O modules within an ET 200SP
station, which are supplied via a common supply voltage.
A potential group begins with a light-colored BaseUnit through which the required voltage is
supplied for all modules of the potential group. The light-colored BaseUnit interrupts the
three self-assembling voltage buses P1, P2 and AUX to the left neighbor.
All additional I/O modules of this potential group are plugged into dark-colored BaseUnits.
You take the potential of the self-assembling voltage buses P1, P2 and AUX from the left
neighbor.
A potential group ends with the dark-colored BaseUnit, which follows a light-colored
BaseUnit or server module in the station configuration.