Induction motors (rotary)
The following parameters can be entered when the commissioning Wizard is run in
STARTER:
Table 3-13
Parameters
p0304
p0305
p0307
p0308
p0310
p0311
p0335
The following optional parameters can be entered:
Table 3-14
Parameters
p0320
p0322
p0341
p0342
p0344
p0350
p0352
p0354
p0356
p0358
p0360
p0640
p1080
© Siemens AG, 2005. All rights reserved
SINAMICS S120 Function Manual, 06/05 Edition
Motor data type plate
Description
Rated motor voltage
Rated motor current
Rated motor power
Rated motor power factor
Rated motor frequency
Rated motor speed
Motor cooling type
Optional motor data
Description
Motor rated magnetization
current/short-circuit current
Maximum motor speed
Motor moment of inertia
Ratio between the total and
motor moment of inertia and that
of the motor
Motor weight
Motor stator resistance, cold
Cable resistance (component of
the stator resistance)
Motor rotor resistance, cold
Motor stator leakage inductance
Motor rotor leakage inductance
Motor magnetizing inductance
Current limit
Minimum speed
Notes on commissioning vector motor types
If this value is not known, "0" can
also be entered. This value
enables the stator leakage
inductance (p0356, p0357) to be
calculated more accurately.
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
This value is limited to maximum
4 * p0305.
This value is defaulted to 1.5 *
p0305 during commissioning.
--