Siemens SENTRON 3VL System Manual page 80

Switching/protection devices, molded-case circuit breakers
Hide thumbs Also See for SENTRON 3VL:
Table of Contents

Advertisement

Application planning
6.7 Use in harsh environments:
Thermomagnetic TM trip units
Figure 6-6
The SENTRON VL thermomagnetic trip units are designed for use in ambient temperatures
up to 70 °C and a non-condensing humidity level up to 95%. The appropriate correction
factors must be applied for ambient temperatures above 50 °C.
Electronic trip unit ETU
Figure 6-7
The SENTRON VL electronic trip units are designed for use in ambient temperatures up to
70 °C and a non-condensing humidity level up to 95%. The appropriate correction factors
must be applied for ambient temperatures above 50 °C.
Electronic trip unit LCD ETU
Figure 6-8
The high-quality SENTRON VL electronic trip units are designed for use in ambient
temperatures up to 70 °C and a non-condensing humidity level up to 95%. The appropriate
correction factors must be applied for ambient temperatures above 50 °C.
80
Thermomagnetic TM
–25 °C to +50 °C, ☂ 95%
Standard ETU
-25 °C to +70 °C, ☂ 95%
LCD-ETU
-25 °C to +70 °C, ☂ 95%
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01