Plug-in or withdrawable version:
Table 12- 22 Derating factors Thermomagnetic overcurrent trip units (plug-in or withdrawable version
Circuit
breaker
VL160X
VL160 &
VL160X
VL250
VL400
VL630
Example for VL250:
● I
● Ambient temperature = 60 °C
I
= 200 x 0.93 = 186 A for fixed-mounted version
n
I
= 200 x 0,93 x 0.9 = 167 A for plug-in version
n
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
Trip unit
Thermomagnetic TM
From [A]
16
50
125
200
200
315
315
500
= 200 A at 50 °C
n
To [A]
40 °C
40
1
100
1
160
1
250
1
250
1
400
1
400
1
630
1
Technical data
12.5 Derating factors
Coefficient
at
50 °C
60 °C
1
1
1
1
0,9
0,9
0,9
0,9
1
1
0,9
0,9
1
1
0,85
0,85
70 °C
1
1
0,9
0,9
1
0,9
1
0,85
161